Description

The SE1000 is a microprocessor-based pulse monitor-
ing interface designed to monitor up to four pulse inputs.

Features

• Stand-alone or network operation
• Independently programmable inputst
• 32 character LCD display
• Four pulse inputs

Mounting

The SE1000 is designed for mounting using two #10
sheet metal screws.
2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com
SE1000
Utility Meter Pulse Transducer
Contents
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Communicating Controls
1
1
1
2
3
5
. . . . . . . . . . . . . . . . . . . .
6
7

Advertisement

loading

Summary of Contents for TCS Basys Controls SE1000

  • Page 1: Table Of Contents

    ......• Four pulse inputs Mounting The SE1000 is designed for mounting using two #10 sheet metal screws. 2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com...
  • Page 2: Wiring

    Powering the se1000 transformer, the polarity of the power wiring must be maintained because all TCS devices The SE1000 is powered from 24 VAC +/- 20 %. are half-wave rectified and have common return If wiring for communications, dedicated power must be paths.
  • Page 3: Programming

    Select either Yes or No to program Meter input two. If no is selected skip to step 18. Controller address screen. SET ADDRESS: If using a PC to access the SE1000, set a unique address from 0 to 255, exclud- ing 248. meter 2 type screen.
  • Page 4 meter 2 Pulse Per revoltion screen. meter 3 Cubic Feet Per Pulse screen. METER 2 P/REV: METER 3 CU FT/P: Enter the value for the Pulses per revolt- Enter the value for Cubic Feet per pulse. ion for meter input 2 (this value should be This only applies to Water, GAS and BTU 4.00 5.00...
  • Page 5: Operation

    CU FT/P: The value for Cubic Feet per pulse. This ticular meter. For each of the four SE1000 meter inputs, only applies to Water, GAS and BTU, and is usually there are five selectable options: found on the utility meter itself.
  • Page 6: Checkout & Troubleshooting

    5. Go back into programming mode and adjust various parameters as required to make the value appear cor- rectly. 6 If a value shown as 0, the SE1000 is not retrieving a pulse signal. Verify the pulse signal is being generated meter 2 Consumption screen.
  • Page 7: Led Description

    meter 3 demand screen. METER 3 DEMAND Displays Current Demand, units will vary based on type of meter selected. 0.00kW meter 3 Count screen. METER 3 COUNT Displays Current Consumption, units will vary based on type of meter selected meter 3 Consumption screen. CONSUMPTION 3 Displays Current pulse count, units will vary based on type of meter selected.