Venmar DECO-TOUCH WALL CONTROL Installation And Owner's Manual

Venmar DECO-TOUCH WALL CONTROL Installation And Owner's Manual

Advertisement

Quick Links

VENMAR AVS SOLO, DUO, HE, COMPACT, CONSTRUCTO 1.0*, HRV
VÄNEE GOLD SERIES, HE*, 60H*, HRV
*CONSTRUCTO 1.0 AND VÄNEE 60H BUILT IN AUGUST 2008 AND LATER, AND VÄNEE HE BUILT IN JULY 2006 OR LATER. THE DATE CODE ON
THE UNIT IS PART OF ITS 13-DIGIT SERIAL NUMBER. FOR EXAMPLE, THE SERIAL NUMBER XXXX0708XXXXX, WHERE 07 IS THE YEAR AND
08 THE MONTH (AUGUST); THE DATE CODE IS ALWAYS THE FIFTH, SIXTH, SEVENTH AND EIGHTH DIGITS.
A
LWAYS DISCONNECT THE UNIT BEFORE MAKING ANY CONNECTIONS
TO THE WALL CONTROL OR ELECTRONIC MODULE INSIDE THE UNIT
F
AILURE TO COMPLY WITH THE FOLLOWING CAN CAUSE ERRATIC OPERATION OF THE UNIT
• N
EVER INSTALL MORE THAN ONE MAIN WALL CONTROL PER VENTILATION UNIT
• K
EEP CONTROL LOW VOLTAGE WIRING AT LEAST
. D
DISTRIBUTION PANEL
O NOT ROUTE CONTROL WIRING ALONGSIDE HOUSE POWER WIRING
• E
NSURE THE WIRES ARE SECURELY CONNECTED
1. U
NPLUG THE VENTILATION UNIT FROM POWER SOURCE
2. C
2
/
"
1 ³/
"
7
UT A
8
X
8
HOLE IN WALL AT A
CONVENIENT LOCATION FOR THE WALL CONTROL
R
OUTE THE CABLE FROM THE UNIT TO THIS
.
HOLE
NOTE: D
IMENSIONS SHOWN ARE FOR AN
INSTALLATION WITHOUT WALL BOX
3. T
EMPORARILY PLACE THE SWITCH OVER THE
HOLE AND MARK BOTH MOUNTING SCREW
.
HOLE POSITIONS
4. R
,
EMOVE THE SWITCH
DRILL BOTH SCREW
(Ø 3/16")
HOLES
IN WALL AND INSERT WALL
(
).
ANCHORS
INCLUDED
I
F THE BACKLIGHT IS NOT ILLUMINATED
)
WHICH BUTTON
SHALL TURN ON THE BACKLIGHT
10
FOR
SECONDS AFTER THE LAST BUTTON PRESSED
O
PERATING
T
O CHANGE THE OPERATION MODE OF THE VENTILATION UNIT
OR
UP
DOWN
THE
OR
THEN SCROLL UP OR DOWN ON
P
UT THE UNIT ON STAND
OVERRIDE WALL CONTROLS
H
OUSE IS VISIBLE SHOWING THE CONTROL IS POWERED ON
T
HIS IS THE FACTORY DEFAULT MODE
A
IR IS RECIRCULATED INSIDE THE HOUSE AT HIGH SPEED
DECO-TOUCH WALL CONTROL INSTALLATION AND OWNER GUIDE
THIS WALL CONTROL CAN BE USED WITH THE FOLLOWING VENTILATION UNITS:
IT IS NOT COMPATIBLE WITH OTHER VENTILATION UNITS.
W
1
FOOT
.
.
.
.
Ø 3/16" , typ.
VC0116A
B
ACKLIGHT
,
THE FIRST BUTTON PRESSED
. T
HE BACKLIGHT REMAINS ILLUMINATED
.
M
ODES
. O
ARROW BUTTON
PERATING MODE LABEL WILL
LCD
.
SCREEN
OFF
-
,
BY MODE
SO IT WILL ONLY RESPOND TO
(
). O
LCD
IF PRESENT
N
SCREEN
.
RECIRC
ERV EKO 1.5, NOVOFIT, KUBIX HRV PLUS
AND
ERV 90H-V ECM, NOVO+, VIGÖR HRV PLUS
AND
C
I
ALL
ONTROL
NSTALLATION
WARNING
!
. F
AILURE TO DISCONNECT POWER COULD RESULT IN ELECTRIC SHOCK OR DAMAGE
.
CAUTION
:
.
(305
)
MM
AWAY FROM MOTORS
5. S
TRIP THE END OF THE CABLE TO ACCESS THE
4
. S
WIRES
U
SING A SMALL FLAT BLADE SCREWDRIVER
CONNECT EACH WIRE TO ITS CORRESPONDING
TERMINAL ON THE BACK OF THE WALL
: YELLOW
CONTROL
"R" , GREEN
TO
"B" .
WIRE TO
6. M
OUNT THE WALL CONTROL TO THE WALL
P
LUG THE VENTILATION UNIT AND TEST THE
WALL CONTROL OPERATION
W
C
U
ALL
ONTROL
SE
(
NO MATTER
,
PRESS
,
ONLY THE
.
.
VIGÖR ERV
AND
,
,
LIGHTING BALLAST
LIGHT DIMMING CIRCUIT AND POWER
.
.
TRIP THE END OF EACH WIRE
,
"Y" , RED
WIRE TO
WIRE
"G"
BLACK
WIRE TO
AND
.
.
O
M
PERATING
ODES
20
T
HE VENTILATION UNIT EXCHANGES AIR INTERMITTENTLY ON A ONE HOUR
: OFF
CYCLE AS FOLLOWS
FOR
40
.,
HIGH SPEED FOR
MIN
SEE NEXT
20
THEN EXCHANGE AIR DURING
MIN
20
.
AFTER THE
MIN
OF AIR EXCHANGE
MIN
A
IR IS EXCHANGED WITH THE OUTSIDE ON LOW SPEED
MAX
A
IR IS EXCHANGED WITH THE OUTSIDE ON HIGH SPEED
KUBIX ERV
AND
Y
R
G
B
VE0243
VC0115
(
'
)
CONT
D
/
MIN
H
40
. (
MIN
OR RECIRCULATION ON
S
)
ECTION ON BACK PAGE
AND
.
. R
ON LOW SPEED
EPEAT CYCLE
.
.
.
09947
. B
REV

Advertisement

loading
Need help?

Need help?

Do you have a question about the DECO-TOUCH WALL CONTROL and is the answer not in the manual?

Questions and answers

Summary of Contents for Venmar DECO-TOUCH WALL CONTROL

  • Page 1 DECO-TOUCH WALL CONTROL INSTALLATION AND OWNER GUIDE THIS WALL CONTROL CAN BE USED WITH THE FOLLOWING VENTILATION UNITS: VENMAR AVS SOLO, DUO, HE, COMPACT, CONSTRUCTO 1.0*, HRV ERV EKO 1.5, NOVOFIT, KUBIX HRV PLUS KUBIX ERV VÄNEE GOLD SERIES, HE*, 60H*, HRV ERV 90H-V ECM, NOVO+, VIGÖR HRV PLUS...
  • Page 2 ’ ONTROL CONT (RH) OW TO SET THE RELATIVE HUMIDITY LEVEL AND CHOOSE BETWEEN RECIRCULATION EHUMIDISTAT VERRIDE ELECTION IN STANDBY OR IN STAND ETTING THE RELATIVE HUMIDITY LEVEL ALLOWS TO SELECT THE MAXIMUM DESIRED MIN, MAX, 20 RECIRC, N THE OPERATING MODES H AND THE USER CAN ).