INSTALLATION AND MAINTENANCE INSTRUCTIONS
GENERAL
These instructions must be carefully read before any work involving products supplied by VALSTEAM ADCA
ENGINEERING S.A. is undertaken.
The installation procedure is a critical stage in a life of a steam trap and care should be taken to avoid damage
to the trap or equipment.
They give their maximum performance only when the equipment associated with them is correctly sized and
installed in accordance with our recommendations.
Note:
Current regional safety regulations should be take in to account and followed, while doing the installation and
maintenance work.
Handling, installation and maintenance work must be carried out by trained personnel. A supervisor must follow
and check all activities.
For the problems that cannot be solve with the help of this instructions, please contact the supplier or the
manufacturer.
The manufacturer reserves the right to change the design and material of this product without notice.
BODY LIMITING CONDITIONS
FLANGED
PN16*
ALLOW. PRES.
ALLOW. PRES.
16 bar
14,5 bar
13,4 bar
12,7 bar
PMO - Max. operating pressure
TMO - Max. operating temperature
* According to EN1092-1:2007 ; ** Acc. to EN1759-1:2004
Body limiting conditions PN16 or below, depending on the type
of connection adopted. Rating PN16 for thread.
CE Marking: This product has been designed for use on steam and water which are in Group 2 of the PED-
European Pressure Equipment Directive 97/23/EC and it comply with those requirements. The product fall within
category SEP and must not be CE marked.
VALSTEAM
ADCA
Produced in accordance with Article 3, paragraph 3 of the PED - European Pressure Equipment Directive - 97/23/EC
FLOAT AND THERMOSTATIC STEAM TRAPS
FLANGED
RELATED
ANSI 150 **
TEMP.
16 bar
100 ºC
14,8 bar
150 ºC
13,6 bar
200 ºC
12 bar
250 ºC
14 bar
198 ºC
FLT14I
MODEL
FLT14I - 4,5
FLT14I - 10
FLT14I - 14
ADCA
Max. Differential pressure
4,5 bar
10 bar
14 bar
IMI 1.3960 E 04.14

Advertisement

loading

Summary of Contents for VALSTEAM ADCA FLT14I Series

  • Page 1 FLT14I GENERAL • These instructions must be carefully read before any work involving products supplied by VALSTEAM ADCA ENGINEERING S.A. is undertaken. • The installation procedure is a critical stage in a life of a steam trap and care should be taken to avoid damage to the trap or equipment.
  • Page 2: Transport And Storage

    abcde ADCA If malfunction of any other equipment or system operation failure may result in a dangerous overpressure, over temperature or even vacuum condition, a safety device must be included in the system to prevent such situations. At start up, the presence of small particles in the fluid (dirt, scale, weld splatters, etc) may cause an imperfect closure of the seat.
  • Page 3: Installation

    abcde ADCA INSTALLATION Account for over pressure conditions, according with the local laws or standards. Steam traps must not be used with other purpose than the one they were built for (e.g. climbing aids or as connecting points for lifting gear). For the problems that cannot be solve with the help of this instructions, please contact the supplier or the manufacturer.
  • Page 4: Maintenance

    abcde ADCA START UP Current regional safety regulations should be take in to account and followed. Protective insulation and warning notice may be required. Until the start up of an existing or a new plant, the following must be checked: All works are completed.
  • Page 5: Troubleshooting Chart

    abcde ADCA TROUBLE SHOOTING CHART FAULT POSSIBLE REASON SOLUTION Damaged seat. Substitute seat. Continuous steam discharge check the installation position Incorrect installation. (see IMI 1.344 E 08.03). Obstructed strainer. Proceed to an accurate clean and identify the possible reason of contamination.
  • Page 6 abcde ADCA FLT14I DN25 PARTS P O S.Nr. DESIG NATIO N M ATERIAL Body CF8M / 1.4408 Cover CF8M / 1.4408 *Gas ket Stainless s t./Graphite *Seat A ISI 410 / 1.4006 *V alve A ISI 440C / 1.4125 *Lever A ISI 304 / 1.4301 *Float A ISI 304 / 1.4301...
  • Page 7 Valsteam ADCA engineering. Health and safety data sheets regarding substances identified as hazardous or potentially hazardous must be provided with the information mention above.

This manual is also suitable for:

Flt14i-4,5Flt14i-10Flt14i-14Flt14i