ANSUL WATER OSCILLATING MONITORS INSTALLATION – OPERATION – MAINTENANCE MANUAL Part No. 77435-02...
Page 2
This manual is intended for use with ANSUL WOM-3 and WOM-4 Water Oscillating Monitors. Those who install, operate, maintain, or service these monitors should read this entire manual. Specific sections will be of particular interest, depending upon one’s responsibilities. Water oscillating monitors are mechanical devices. They need peri- odic care.
(supplied by others). 4. The ANSUL Support Stand (Part No. 400987) or other added force. The actual support required must be determined by support may be required to absorb the monitor operating the system designer.
Page 6 The following test procedures should be performed after 14. For WOM-3 monitor, loosen speed ball handle and raise or installation, after any adjustments, and at each maintenance lower tiller bar to check for free movement. See Figure 1.
1. Turn on main water supply to monitor. The monitor will oscil- late automatically at set limits. 2. To adjust stream elevation of WOM-3 monitor, loosen speed ball handle and raise or lower tiller bar. Then retighten speed ball handle. (See Figure 1.) To adjust stream elevation of WOM-4 monitor, turn handwheel clockwise to raise or counterclockwise to lower.
WOM-3 monitor/3 1/2 in. engagement for WOM-4 monitor). b. Return selector valve handle to RUN position (pointed to back of enclosure). 3. Using handwheel (WOM-4) or tiller bar (WOM-3), return monitor to desired elevation. On WOM-3 monitors, tighten speed ball handle.
5. Lubricate monitor base couplings and elevation couplings with monolithium grease. (To grease the WOM-3 monitor base coupling, the monitor must be rotated approximately 90° to the right so that grease fitting can be reached through access hole at side of enclosure.) See Figures 1, 2, and 4 for grease...
OSCILLATION SPEEd CONTROL AdjUSTMENT Page 10 The speed of oscillation can be adjusted using test mode or under 2. Remove plug from speed adjustment access hole located on actual operating conditions. right side of enclosure. WARNING 3. Connect a garden hose (3/4-11 1/2 NH) to fitting at back of oscillating mechanism enclosure.
OSCILLATION ARC AdjUSTMENT Page 11 To set the monitor arc of oscillation, complete the following steps. Oscillation limits are listed on Page 1. See Figure 4 for adjustment locations. 1. Remove cover from oscillating mechanism enclosure. 2. Loosen the pair of front adjustment nuts (9/16 in.). Then spin nuts to front end of threaded rod.
WINTERIzING PROCEdURE Page 12 To help protect the monitor from freezing during periods of low temperature, complete the following steps. (Refer to Figure 4). 1. Manually rotate monitor to right stop (valve may click at this time). 2. Manually rotate monitor to left stop until valve clicks. 3.
Page 19
402766 Inlet Adaptor 402765 ANSUL, and the product names listed in this material are marks and/or * This parts list covers the bent tube assembly portion of the WOM-4 Monitor. registered marks. Unauthorized use is strictly prohibited. See Form No. F-86181 for WOM-4 oscillating mechanism parts.
Page 20
WOM-3/WOM-4 FOAM SYSTEMS MONITOR PARTS LIST OSCILLATING MECHANISM...
Page 22
400044 Cap Screw 400005 400005 * This parts list covers the oscillating mechanism portion of the water oscillating monitor. See Form No. F-86182 for WOM-3 bent tube assembly parts or Form No. 86183 for WOM-4 bent tube assem- bly parts.
Page 23
TYCO FIRE PROTECTION PRODUCTS MARINETTE, WI 54143-2542...
Page 24
* This parts list covers the bent tube assembly portion of the WOM-3 Monitor. See Form No. F-86181 for WOM-3 Oscillating Mechanism Parts. ANSUL, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. One Stanton Street...