Table of Contents

Advertisement

Temperature Controllers
USER MANUAL
Bulletin 900-TC8, 900-TC16, & 900-TC32
Series B

Advertisement

Table of Contents
loading

Summary of Contents for Rockwell Automation Allen-Bradley 900-TC8

  • Page 1 Temperature Controllers USER MANUAL Bulletin 900-TC8, 900-TC16, & 900-TC32 Series B...
  • Page 3: Important User Information

    Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
  • Page 4: European Communities (Ec) Directive Compliance

    IMPORTANT application and understanding of the product. Trademark List 900Builder and 900BuilderLite are registered trademarks of Rockwell Automation, Inc. European Communities (EC) Directive Compliance If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
  • Page 5: Table Of Contents

    Table of Contents Important User Information ....... . 1-3 Safety Precautions ........1-3 Safety Signal Words .
  • Page 6 Table of Contents Panel Mounting ........2-13 Bulletin 900 Wiring Terminals.
  • Page 7 Table of Contents PV Change Rate Alarm ........3-45 Precaution.
  • Page 8 Table of Contents Switching 100% AT Execute/Cancel ..... 4-24 Switching 40% ATExecute/Cancel ..... . 4-25 Switching Setting Change Enable/Disable.
  • Page 9 Table of Contents Chapter 5 Parameter Functions & Definitions Conventions Used in This Chapter ......5-1 About the Parameter Display .
  • Page 10 Table of Contents Leakage Current 2 Monitor (900-TC8, 900-TC16) ..5-29 Heater Burnout Detection 1 (900-TC8, 900-TC16)..5-30 Heater Burnout Detection 2 (900-TC8, 900-TC16)..5-31 HS Alarm 1 (900-TC8, 900-TC16) .
  • Page 11 Table of Contents Alarm Type for Alarm 2 (900-TC8 & 900-TC16) ... 5-59 Alarm Type for Alarm 3 (900-TC8) ..... . 5-59 Alarm 1 Hysteresis .
  • Page 12 Table of Contents Heater Short Alarm (HSA) Hysteresis (900-TC8, 900-TC16) ....... . . 5-89 Loop Break Alarm (LBA) Detection Time.
  • Page 13 Table of Contents Chapter 6 Troubleshooting & Error Error Displays ......... . . 6-1 Indication Input Error.
  • Page 14 1-10 Table of Contents Calibrating an Analog Voltage (e.g., 1…5V DC) Input (900-TC8 & 900-TC16) ....... C-16 Checking Indication Accuracy .
  • Page 15: Conventions Used In This Manual

    Preface Conventions Used in This Meanings of Abbreviations Manual The following abbreviations are used in parameter names, figures, and in text explanations. These abbreviations mean the following: Table P.A Symbol Term Process value Set point Set value Auto-tuning Self-tuning Heater Burnout Heater Short ➊...
  • Page 16: Series B Controllers

    P-ii Preface Series B Controllers Series B Upgrades Series B controllers have the following upgrades. 900-TC8x Although the upgraded controllers are compatible with the previous controllers, terminal arrangements have been changed. Terminal sizes and panel mounting depth have not been changed. Other changes are outlined in the following tables.
  • Page 17 Preface P-iii Table P.B Series A Series B ALM1 ALM1 ALM2 ALM2 ALM3 ALM3 900-TC16 OUT1 STOP OUT1 STOP OUT2 MANU OUT2 MANU • ALM indicator was changed to SUB indicator SUB1 SUB2 ALM1 ALM2 SUB3 ALM3 900-TC8 OUT1 OUT2 STOP MANU OUT1...
  • Page 18: Terminal Arrangements

    P-iv Preface Terminal Arrangements Table P.C — Terminal Arrangements Series A Series B One CT Voltage output Long-life relay One CT Control Output 2 Two CTs Two CTs output Control Output 2 Control Output 2 Control Output 2 250 VAC, 3 A −...
  • Page 19: Body Removal

    Preface Body Removal Table P.D — Body Removal Series A Series B • Removal using hooks • Removal using screws 900-TC8 900-TC16 --- • No change for body removal 900-TC32 --- • No change for body removal 900-TC8, 900-TC16, & 900-TC32 Ratings Table P.E —...
  • Page 20: Characteristics

    P-vi Preface 900-TC8, 900-TC16, & 900-TC32 Ratings Table P.E — 900-TC8, 900-TC16, & 900-TC32 Ratings Series A Series B The following types of thermocouple input were added: W and PLII. Input sensor types for thermocouple inputs Input range increased for E thermocouple: Input range for E thermocouple: 0...600 ºC -200...600 ºC •...
  • Page 21: Communications Characteristics

    Preface P-vii Table P.F — Characteristics Series A Series B Control output ON/OFF count alarm Outputs MV change rate limiter 40% AT Automatic cooling coefficient Controls adjustment for heating/cooling control PV rate of change alarm Alarms OC alarm (only for models with heater burnout detection) Inverting direct/reverse operation Other...
  • Page 22: Other Upgrades

    P-viii Preface Other Upgrades Table P.H Series A Series B Mounting Bracket (900-TC8 only) Modified section Note: The mounting bracket for the Series A models cannot be used for Series B models. Terminal Cover for 900-TC16 Note: The terminal covers for the Series A models cannot be used for Series B models.
  • Page 23: Option Units

    Preface P-ix Option Units (Series B Controller Compatible— One Option Unit per Controller) This unit provides communications event input etc. functionality. Table P.I Bulletin No. Name Function Cat. No. (Series) RS-232C communications➊ 900-TC8232 (B)➍ Communications Unit 900-TC8 RS-485 communications 900-TC8COM(B)➍ (Series B) Event Input Unit Event Input➋...
  • Page 24: How To Read Display Symbols

    Preface How to Read Display The following table shows the relationship between the symbols exhibited on the controller’s front panel displays to alphabet characters. Symbols Table P.J 11 — Segment Display Selection Symbol A B C D E F G H I J K L M Alphabet Symbol Alphabet...
  • Page 25: I/O Configurations & Main Functions

    Chapter Bulletin 900 Input & Output Overview I/O Configurations & Main Functions Figure 1.1 — 900-TC8 I/O Configuration Temperature Input Control Output Control Ouput 1 Control or Analog Input Heating Section Control Output Control Ouput 2 Cooling Heating/Cooling Auxillary Output 3 Auxillary Output 3 CT1 Input Auxillary Output 2...
  • Page 26 Bulletin 900 Input & Output Overview Figure 1.2 — 900-TC16 I/O Configuration Control Output Temperature Input Control Control Ouput 1 Heating or Analog Input Section Control Output Control Ouput 2 Cooling Heating/Cooling CT1 Input Auxillary Output 2 Auxillary Output 2 CT2 Input Auxillary Output 1 Event Inputs...
  • Page 27 Bulletin 900 Input & Output Overview Figure 1.3 — 900-TC32 I/O Configuration Control Output Control Control Temperature (Heating) Section Output 1 Input Control Output (Cooling) Heating/ Cooling Auxillary Standard Output 1 Alarm 1 Input Error Program End Output Communications Function Bulletin 900-TC8, 900-TC16, and 900-TC32 temperature controllers allow the user to: •...
  • Page 28: Features

    Bulletin 900 Input & Output Overview Features • Watertight construction (equivalent to IP66 indoor use). • Conform to cULus/IEC safety standards and EMC standards. Main Functions The following introduces the main functions of the Bulletin 900-TC8, 900-TC16, and 900-TC32 temperature controllers. For details on each function and how to use them, refer to Chapter 3 and onward.
  • Page 29 Bulletin 900 Input & Output Overview Figure 1.4 — Triac Diagram Triac Varistor Relay Output Inductive Load Varistor Select a surge absorber that satisfies the following conditions. Publication 900-UM007D-EN-E - January 2011...
  • Page 30 Bulletin 900 Input & Output Overview Table 1.A — Surge Absorber Selection Voltage Used Varistor Voltage Surge Resistance 100…120V AC 240…270V 1000 A minimum 200…240V AC 440…470V • Always connect an AC load to the triac relay output. The output will not turn OFF if a DC load is connected.
  • Page 31: Controller Hardware Versions

    Bulletin 900 Input & Output Overview Controller Hardware The following tables provide a list of controller base features with associated Cat. Nos. Versions Publication 900-UM007D-EN-E - January 2011...
  • Page 32: 900-Tc8

    Bulletin 900 Input & Output Overview 900-TC8 Table 1.B — Controller Versions Power Control Control Supports Cat. No. for DIN Size No. of Sensor Input Supply Output 1 Output 2 Heater Burnout Enhanced (mm) Alarms Type Voltage Type Type Alarm 900-TC8 Line Relay On/Off Yes (1-Phase)
  • Page 33: 900-Tc16

    Bulletin 900 Input & Output Overview Table 1.C — Controller Option Units Event Out Comms Cat. No. for Enhanced Option Units Series — RS232 900-TC8232B Option Unit — RS485 900-TC8COMB — 900-TC8EIMA 900-TC16 Table 1.D — Controller Versions DIN Size Power Supply Control Output Cat.
  • Page 34: 900-Tc32

    1-10 Bulletin 900 Input & Output Overview Table 1.E — Controller Option Units Heater Voltage (SSR) Cat. No. for Enhanced Burnout Event Out Comms Control Output 2 Option Units Series 1-Phase HB — RS485 — 900-TC16NCOM — — RS485 — 900-TC16NACCOM 1-Phase HB —...
  • Page 35: Front Panels & General Functions

    Bulletin 900 Input & Output Overview 1-11 Front Panels & General Figure 1.5 — Bulletin 900-TC8 Functions Operation Indicators SUB1 SUB2 SUB3 Temperature Unit No.1 Display No.2 Display OUT1 STOP No.3 Display Operation Indicators OUT2 MANU Up Key Mode Key Function Key/ Auto/Manual Key Function Group Key...
  • Page 36: Display Meanings

    1-12 Bulletin 900 Input & Output Overview Figure 1.7 — Bulletin 900-TC32 Display Meanings Display Meaning SUB1 SUB2 SUB3 No. 1 Displays the Process Value or Parameter Type during configuration. Lights for approximately 1 second during startup. No. 2 Displays the Set Point, parameter operation read value, manipulated variable, or during configuration, the value of the displayed (No.
  • Page 37: Operation Indicators 1,2,3

    Bulletin 900 Input & Output Overview 1-13 Operation Indicators 1,2,3... Operation Indicator Definition Function SUB 1 Sub 1 Lights when the function configured for the Auxiliary Output 1 Assignment parameter is ON. SUB2 Sub 2 900-TC8 and 900-TC16 Only: Lights when the function configured for the Auxiliary Output 2 Assignment parameter is ON.
  • Page 38: Basic Keypad Functions

    1-14 Bulletin 900 Input & Output Overview Basic Keypad Functions The following describes the basic functions of the front panel keys. Definition Function Function (Auto/Manual) 900-TC8 Only: This is a function key. When it is pressed for at least 1 second, the function configured in the PF Setting parameter will operate.
  • Page 39: Hardware Installation

    Chapter Preparations Hardware Installation Approximate Dimensions The recommended panel thickness for mounting the 900-TC16 and 900-TC32 is 1 to 5 mm and the 900-TC8 is 1 to 8 mm. Note: Dimensions are in millimeters. Dimensions are not intended to be used for manufacturing purposes.To convert millimeters to inches, multiply by 0.0394.
  • Page 40: Panel Cutout Dimensions

    Preparations Figure 2.3 — 900-TC32 44.8 Panel Cutout Dimensions Dimensions are in millimeters. Dimensions are not intended to be used for manufacturing purposes. Figure 2.4 — 900-TC8 (48 x number of units -2.5) 60 min. ➊ Publication 900-UM007D-EN-E - January 2011...
  • Page 41 Preparations Figure 2.5 — 900-TC16 60 min. (48 number of units -2.5) min. Figure 2.6 — 900-TC32 Publication 900-UM007D-EN-E - January 2011...
  • Page 42: System Wiring And Installation Guidelines

    Preparations Horizontal group-mounting of two or more temperature controllers, or mounting temperature controllers above each other may cause heat to build up inside the temperature controllers. This will shorten their service life. When mounting temperature controllers like this, consider forced cooling measures, such as a cooling fan. If forced air cooling is used, limit cooling to the terminal block.
  • Page 43 Preparations Do not allow metal fragments or lead wire scraps to ATTENTION fall inside the Bulletin 900 Controller. These may cause electric shock, fire, or malfunction. Never disassemble, repair, or modify the Bulletin 900 Controller with line or field device power applied. Doing so may cause electric shock, fire, or malfunction.
  • Page 44 Preparations Do not use the Bulletin 900 Controller in the following ATTENTION places which might exceed its specifications: – Places subject to dust or corrosive gases (in particular, sulfide gas, and ammonia gas) – Places subject to high humidity, condensation, or freezing –...
  • Page 45: Panel Mounting - 900-Tc8

    Preparations Store within the following temperature and humidity ATTENTION ranges: Temperature: –25…+65 C Humidity: 25…85% (with no icing or condensation) Avoid using the Bulletin 900 Controller in places near a radio, television configured, or wireless installation. These devices can cause radio disturbances which may adversely affect the performance of the Bulletin 900 Controller.
  • Page 46 Preparations 4. Tighten the upper and lower adapter mounting screws alternately with only one turn of the screwdriver at a time to maintain an even torque balance. Tighten the screw until the ratchet mechanism operates. 5. To allow heat to escape, do not block the area around the Bulletin 900-TC8 Temperature Controller.
  • Page 47: Setting Up The 900-Tc8 Controller With The Optional Units

    Preparations 900-TC8 (Series B) Case Removal while Panel-Mounted The control unit can be removed from its case whether or not it is mounted on the control panel. This allows you to perform maintenance or to add option units without opening the control panel enclosure or removing the terminal compartment.
  • Page 48 2-10 Preparations Table 2.A Name Cat. No. Function (Series)➊ Communications board 900-TC8COM (B) RS-485 Communications support 900-TC8232 (B) RS-232 Communications support Event input unit 900-TC8EIM (A) Event input support ➊ One (1) unit per controller. This series of option units are compatible with Series A or Series B controllers. Panel Mounting —...
  • Page 49: Panel Mounting

    Preparations 2-11 4. Tighten the two screws on the adapter against the panel. Tighten the two screws alternately keeping the torque to approximately 0.29…0.39 N•m (2.57…3.45 lb-in.). 5. To allow heat to escape, do not block the area around the Bulletin 900-TC16 Temperature Controller.
  • Page 50 2-12 Preparations Table 2.B Function 900-TC16 Option Module Cat. Heater Burnout Event Voltage (SSR) No.(Series) Comms. & Heater Short Input Control Output 2 ➊➋ 1-Phase HB — RS485 — 900-TC16NCOM (B) — — RS485 — 900-TC16NACCOM (B) 1-Phase HB — —...
  • Page 51 Preparations 2-13 Panel Mounting — 900-TC32 Mounting to the Panel Figure 2.13 Note: For waterproof mounting, waterproof packing must be installed on the controller. Waterproofing is not possible when group mounting several controllers. Waterproof packing is not necessary when there is no need for the waterproofing function.
  • Page 52 2-14 Preparations The body of the controller can be replaced by removing the terminal block from the 900-TC32. Figure 2.14 1. Insert a flat-blade screwdriver into the tool holes (one on the top and one on the bottom) to release the hooks. Do not apply excessive force. 2.
  • Page 53: Bulletin 900 Wiring Terminals

    Preparations 2-15 Bulletin 900 Wiring Terminals Figure 2.15 — 900-TC8 (Series B) Terminal Arrangement Option Units Communications • 100 to 240 VAC 900-TC8232 900-TC8COM 900-TC8EIM • 24 VAC/VDC (no polarity) RS-232C RS-485 Event inputs B (+) Control output 1 Relay output Event Inputs 250 VAC, 5A DO NOT USE...
  • Page 54 2-16 Preparations Figure 2.17 — 900-TC32 Terminal Arrangement Control Output 1 Relay Output 250 VAC, 2 A RS-495 (resistive load) Universal B(+) A(-) Communications DO NOT DO NOT DO NOT DO NOT TC/Pt Input Voltage Output 12 VDC, 21 mA 10 10 11 11 12 12...
  • Page 55: Wiring Guidelines And Precautions

    Preparations 2-17 Wiring Guidelines and Precautions Do not wire unused terminals. ATTENTION Make sure to observe correct polarity when wiring the controller terminals. To reduce induction noise, separate the high-voltage or large-current power lines from other lines, and avoid parallel or common wiring with the power lines when you are wiring to the terminals.
  • Page 56: Wiring

    2-18 Preparations Figure 2.18 — Wiring 7.2 mm max. 7.2 mm max. Wiring Power Supply The controller requires an external power source for operation. For the 900-TC8 connect to terminals 1 and 2 and for the 900-TC16 connect to terminals 9 and 10. The following table shows the specifications. Table 2.C Input Power Supply Bulletin 900-TC8...
  • Page 57 Preparations 2-19 When mounting a noise filter on the power supply, make sure to first check the filter’s voltage and current capacity, and then mount the filter as close as possible to the Bulletin 900 Controller. Reinforced insulation is applied to the power supply I/O sections.
  • Page 58 2-20 Preparations • To reduce induced electrical noise, the leads on the temperature controller’s terminal block must be wired separately from large-voltage/large-current power leads. Also, avoid wiring leads in parallel with power leads or in the same wiring path. Other methods such as separating conduits and wiring ducts, or using shield wire are also effective and recommended.
  • Page 59 Preparations 2-21 The following tables show the specifications for each output type. Table 2.D — 900-TC8 Output Type Output 1 Specifications Relay 250V AC, 5 A (resistive load), electrical durability: 100,000 operations Voltage (PNP) PNP type, 12V DC +15%/−20%, 40 mA (with short-circuit protection).
  • Page 60 2-22 Preparations Output Wiring Considerations Do NOT connect a DC load to the Triac (AC) relay. The PNP voltage (SSR) output (Control Output 1) is not electrically isolated from the controller’s internal circuits. SSR Control Output 2 of the 900-TC16 is also not isolated. However, SSR Control Output 2 of the 900-TC8 is isolated.
  • Page 61 Preparations 2-23 (LBA) and Heater Short Alarm (HSA) that are provided for the Bulletin 900 Controller.) Figure 2.20 Varistor Triac (AC) relay output Inductive load Varistor Select a surge absorber that satisfies the following conditions. Table 2.G Voltage Used Varistor Voltage Surge Resistance 100…120V AC 240…270V...
  • Page 62 2-24 Preparations Table 2.I — 900-TC16 Output Type Output 2 Specifications PNP type, 12V DC ±15%, 21 mA (with short-circuit protection) Voltage (PNP) • Always connect an AC load to a Triac (AC) relay output. The output will not turn OFF if a DC load is connected. •...
  • Page 63 Preparations 2-25 Select a surge absorber that satisfies the following conditions. Table 2.J Voltage Used Varistor Voltage Surge Resistance 100…120V AC 240…270V 1,000 A min. 200…240V AC 440…470V Wiring Auxiliary Outputs (1, 2, and 3) • On the 900-TC8, Auxiliary Output 1 (SUB1) is output across terminals 9 and 10, Auxiliary Output 2 (SUB2) is output across terminals 7 and 8, and Auxiliary Output 3 (SUB3) is output across terminals 5 and 6.
  • Page 64 2-26 Preparations Figure 2.23 SUB3 SUB2 SUB2 SUB1 SUB1 SUB1 900-TC8 Alarms 900-TC16 Alarms 900-TC32 Alarms Note: ALM1, 2, 3 can be output to auxiliary output 1, 2, 3 or changed with the Advanced Function level.The auxiliary relay specifications are as follows: Table 2.K 900-TC8 and 900-TC16 SPST-NO 250V AC 3 A...
  • Page 65 Preparations 2-27 Wiring the Event Input When the appropriate option event input unit is mounted in the Bulletin 900-TC8 or 900-TC16 controller, an event input function is available by wiring to the controllers terminals as shown in the following diagrams. Figure 2.25 A Do NOT apply an external voltage source to the Event Input Terminals 900-TC16...
  • Page 66 2-28 Preparations RS-232C Communication to a Personal Computer —Bulletin 900-TC8 Only By using the appropriate option communications unit in the Bulletin 900-TC8 or 900-TC16 Controller, you can communicate with a personal computer. Figure 2.27 — Communication Unit Connection Diagram RS-232C SD(TXD) RD(RXD) RS(RTS)
  • Page 67 Preparations 2-29 Figure 2.28 — Communication Unit Connection Diagram 900-TC8 & 900-TC16 Shielded Cable PC with RS232 to RS485 converter such as 900-CONV Controller No. X Controller X + 1 RS-485 RS-485 Abbr. Abbr. A (–) A (–) A<B : “1” mark B (+) A>B : “0”...
  • Page 68: Using The Direct Pc Communications Port

    2-30 Preparations Figure 2.30 900-TC8 and/or TC16 900-TC8 900-TC16 RS-232 RS-485 900-CONV Note: The PC must have 900BuilderLite software installed to configure/monitor the Bulletin 900-TC8, 900-TC16, and/or 900-TC32 on an RS-485 network. Using the Direct PC The direct PC communication port, available on the Series A and Series B Bulletin 900-TC, 900-TC16, and 900-TC32 Controllers, enables direct PC to Communications Port controller communications without the use of a communication option unit.
  • Page 69 Preparations 2-31 Hardware Installation EXAMPLE Figure 2.31 — Temperature Controller Connection Method Personal Computer 900-CPOEM1 Cable USB Port Communications Port for Support Software Bottom View of Temperature Controllers Communications Communications Port Communications Port for Support for Support Software Port for Support Software Software 900-TC32...
  • Page 70 2-32 Preparations Driver Installation When the cable is connected with the personal computer, the personal computer’s operating system detects the product as a new device. At this time, install the driver using the installation wizard. For details on installation methods, refer to the user’s manual for the 900-CPOEM1-Serial Conversion Cable.
  • Page 71: Configuration & Basic Operation

    Chapter Configuration & Basic Operation Figure 3.1 — 900-TC8 Temperature Unit No. 1 Display Operation Indicators No. 2 Display Up Key Function Group Key Mode Key Down Key Figure 3.2 — 900-TC16 Operation Indicators SUB1 SUB2 SUB3 Temperature Unit No.1 Display No.2 Display OUT1 STOP...
  • Page 72 Configuration & Basic Operation Figure 3.3 — 900-TC32 Publication 900-UM007D-EN-E - January 2011...
  • Page 73 Configuration & Basic Operation How Function Groups Are Parameters are divided into control categories, each called a function group. Each of the items/values that can be configured in these function groups is Configured and Operating called a parameter. The function groups on the Bulletin 900 controller are the Keys on the Front Panel divided into the following: Figure 3.4 —...
  • Page 74 Configuration & Basic Operation Table 3.A — Control Categories Function Group Control In Progress Control Stopped Protect — Operation — Adjustment — Manual Control — Monitor/Setting Item — Initial Setting — Advanced Setting — Calibration — Communications Setting — To activate the Advanced Setting function group, set the Protect function group of the Initial/Communications Protect to 0.
  • Page 75 Configuration & Basic Operation Note: The key pressing time can be altered to your requirements. Refer to the Move to Protect function group Time parameter in the Advanced Setting function group. Operation Function Group — This function group is displayed when you turn the power ON.
  • Page 76 Configuration & Basic Operation Note: Pressing the key for at least 3 seconds in the Operation function group’s auto/manual switching display will move to the Manual Control function group, and not the Initial Setting function group. Advanced Setting Function Group — To move to the Advanced Setting function group, set the Initial Setting/Communications Protect parameter in the protect function group to 0 and then, in the Initial Setting function group, input the password ( 169).
  • Page 77: Selecting Parameters

    Configuration & Basic Operation Selecting Parameters Within each function group, the parameter is changed in order (or in reverse order) each time the M key is pressed. (In the Calibration function group, however, parameters cannot be changed in reverse order.) For details, refer to Parameter Functions &...
  • Page 78: Communications Function

    Configuration & Basic Operation Communications Function The Bulletin 900 temperature controller can be provided with a communications function that allows you to check and set controller parameters from a personal computer that has configuration and/or monitoring software installed. If the communications function is required, mount the appropriate option unit (refer to Table 1.C or 1.E) for the Bulletin 900 temperature controller.
  • Page 79: Setting Up Communications Parameter Data

    Configuration & Basic Operation Setting Up Communications Parameter Data Set the Bulletin 900 controller communication parameter specifications so that they match the communication parameter setup for the personal computer, using configuration/monitoring software such as 900BuilderLite. In a multidrop (RS-485) 1:N configuration, match the setting data except for the communications unit numbers on all 900-TC controllers.
  • Page 80 3-10 Configuration & Basic Operation Figure 3.8 — Typical Example 1 Setup Procedure Input type: 5 (K thermocouple, −200°C to 1,300°C) Power ON Power ON Control method: ON/OFF control Alarm type: 2 (upper limit) Operation Alarm value 1: 20°C (deviation) function Set point: 100°C...
  • Page 81 Configuration & Basic Operation 3-11 Figure 3.9 — Typical Example 2 Input type: 9 (T thermocouple, −200°C to 400°C) Control method: PID control PID constants found using auto-tuning (AT). Alarm type: 2 upper limit Alarm value 1: 30°C Set point: 150°C Setup Procedure Power ON...
  • Page 82: Configuring The Input Type

    3-12 Configuration & Basic Operation Configuring the Input Type The Bulletin 900-TC8, 900-TC16, and 900-TC32 controller support three input/sensor types: (1) platinum resistance thermometer (RTD), (2) thermocouple, and (3) non-contact temperature sensor. The Bulletin 900-TC8 and 900-TC16 controller support a fourth input/sensor type, analog inputs. Program/configure the Input Type matched to your sensor using the Input Type parameter (See Table 3.C).
  • Page 83 Configuration & Basic Operation 3-13 Table 3.C — List of Global Temperature (GT) Input Types Input Type Specifications Set Value Input Temperature Setting Range −200…850 (°C)/−328…1,562 (°F) ControllerType Platinum Resistance Pt100 with Thermometer (RTD) −199.9…500.0 (°C)/−327.8…932.0 (°F) Thermocouple and Resistance 0.0…100.0 (°C)/32.0…212.0 (°F) Thermometer −199.9…500.0 (°C)/−327.8…932.0 (°F)
  • Page 84: Selecting °C/°F

    3-14 Configuration & Basic Operation Table 3.D — Analog Input Types (not supported by 900-TC32) Input Type Specifications Set Value Process Input Setting Range Models with Current input 4…20 mA Either of the following ranges can be used by scaling −1,999…9,999 Analog Input 0…20 mA...
  • Page 85: Configuring The Sp

    Configuration & Basic Operation 3-15 2. Select the Temperature Unit parameter by pressing the M key. Press the U or D key to select either C (c) or F (f). Figure 3.15 — Temperature Unit Parameter Temperature unit 3. To return to the Operation function group press the key for at least 1 second.
  • Page 86: Selecting Pid Control Or On/Off Control

    3-16 Configuration & Basic Operation 2. Press the U or D key until the set point displayed is 200 C. To load the value into the controller memory, either press the key or wait 2 seconds. Figure 3.18 Selecting PID Control or Overview ON/OFF Control The Bulletin 900 Controller supports two control methods: (1) 2-PID control...
  • Page 87: Configuring The Output Parameters

    Configuration & Basic Operation 3-17 Configuring the Output Control Period Parameters The Control Period parameter is used in the PID control method and allows you to adjust the minimum amount of time between ON cycles of the ON/OFF output (MV). This is sometimes referred to as timed proportional PID control.
  • Page 88 3-18 Configuration & Basic Operation Figure 3.21 — Direct/Reverse Operation Manipulated variable (MV) Manipulated variable (MV) 100% 100% High temperature High temperature Low temperature Set value (SP) Low temperature Set value (SP) Direct operation Reverse operation For example, when the process value (PV) temperature is lower than the set point (SP) temperature in a heating control system, the manipulated variable (OUT1) increases (ON) by the difference between the PV and SP values.
  • Page 89 Configuration & Basic Operation 3-19 Figure 3.22 2. The Input Type is displayed. When you are monitoring/configuring the Input Type for the first time, the set value is 0: K type thermocouple default. (0 is set if you have a platinum resistance thermometer compatible controller.
  • Page 90: Assigned Output Functions

    3-20 Configuration & Basic Operation 6. To return to the Operation function group press the key for at least 1 second. Figure 3.27 PV/SP 7. Select the Move to Advanced Setting function group parameter by pressing the M Key. Figure 3.28 Move to amov Advanced Setting...
  • Page 91 Configuration & Basic Operation 3-21 Table 3.F — 900-TC8 and 900-TC16 Without Control Output 2 With Control Output 2 Parameter Heating/ Heating/ Name Symbol Standard Cooling Standard Cooling out 1 Control Output 1 Control output Control Control Control Assignment (heating) output output output...
  • Page 92 3-22 Configuration & Basic Operation Control Output (Cooling); Auxiliary Output 1: Alarm 1; Auxiliary Output 2: Alarm 2 1. Press the key for at least 3 seconds to move from the Operation function group to the Initial Setting function group. Figure 3.29 PV/SP 2.
  • Page 93 Configuration & Basic Operation 3-23 6. Select the Control Output 1 Assignment parameter by pressing the M key. Figure 3.34 Control output 1 out1 assignment 7. Press the U or D key to set o. (The default is o.) Figure 3.35 out1 8.
  • Page 94 3-24 Configuration & Basic Operation 12. Select the Auxiliary Output 2 Assignment parameter by pressing the M key. Figure 3.39 Auxiliary Output sub2 2 Assignment alm2 13. Press the U or D key to set alm2. (The default is alm2.) Figure 3.40 Auxiliary Output sub2...
  • Page 95: Auxiliary Output Opening Or Closing In Alarm

    Configuration & Basic Operation 3-25 Auxiliary Output Opening or Note: Refer to Page 5.73, Auxiliary Output * Open in Alarm (* = 1 to 3), for definition and furhter explanation of open in and close in alarm. Closing in Alarm •...
  • Page 96 3-26 Configuration & Basic Operation The default is onof. Hysteresis In the ON/OFF control method, hysteresis is used to provide a margin/differential for switching the control output ON when the controlled temperature moves away from the required set point. The Hysteresis parameter is used to give stability to the output around the set point.
  • Page 97: On/Off Control Setup

    Configuration & Basic Operation 3-27 Table 3.I — Parameters Symbol Parameter Name and Group Location Application s-hc Standard or Heating/Cooling: Initial Setting For specifying the control function group method cntl PID ON/OFF: Initial Setting function group For specifying the control method orev Direct/Reverse Operation: Initial Setting function...
  • Page 98 3-28 Configuration & Basic Operation 3. Select the PID ON/OFF parameter by pressing the M key. Figure 3.47 • ON/OFF cntl onof 4. Check that the configured control method parameter is onof (Note: ON/OFF is the default). 5. To return to the Operation function group, press the key for at least 1 second.
  • Page 99 Configuration & Basic Operation 3-29 Setting the Hysteresis Operating Procedure ° The third part of the example is to configure the hysteresis to 2.0 1. Press the key to move from the Operation function group to the Adjustment function group. Figure 3.50 Figure 3.51 2.
  • Page 100: Determining Pid Constants (At, St, Manual Setup)

    3-30 Configuration & Basic Operation Determining PID Constants AT (Auto-Tuning) (AT, ST, Manual Setup) Figure 3.55 Overview When you configure the controller to execute Auto-Tuning, the optimum PID constants for the current set point during program execution are automatically configured by the controller forcibly changing the manipulated variable (MV) to calculate the characteristics (called the limit cycle method) of the control target.
  • Page 101 Configuration & Basic Operation 3-31 If you move to the Operation function group during AT execution, the No. 2 display blinks to indicate that AT is still in the process of being executed. Figure 3.58 PV/SP No. 2 display AT execution in progress Note: Only the Communications Writing, RUN/STOP, AT Execution/Cancel, and Program Start parameters can be changed during AT execution.
  • Page 102 3-32 Configuration & Basic Operation 100% AT Operation will be as shown in the following diagram, regardless of the deviation (DV) at the start of AT execution. To shorten the AT execution time, select 100% AT. Note: The Limit Cycle MV Amplitude parameter is disabled at 100% AT. Figure 3.60 —...
  • Page 103 Configuration & Basic Operation 3-33 3. off will be displayed when AT ends. Figure 3.64 4. To return to the operation function group, press the O Key. Note: The newly configured value or parameter is loaded into controller memory if you do NOT operate any key on the front panel for at least or M key.
  • Page 104: St (Self-Tuning)

    3-34 Configuration & Basic Operation EXAMPLE Operation Procedure: Execute Self-Tuning (ST) 1. Press the key for at least 3 seconds to move from the Operation function group to the Initial Setting function group. Figure 3.66 Input type in-t 2. Select the ST parameter by pressing the M key. 3.
  • Page 105: Self-Tuning (St) Stable Range

    Configuration & Basic Operation 3-35 Table 3.J At Start of Program Execution When Set Point is Changed (Self-Tuning ON) (Self-Tuning ON) 1. The set point at the start of program 1. The new set point differs from the set execution differs from the set point point used when the previous SRT was when the previous SRT was executed.
  • Page 106: Rt (Robust Tuning)

    3-36 Configuration & Basic Operation In this example, the ST stable range will be configured to 20 C. EXAMPLE Operation Procedure 1. Select the ST Stable Range parameter by pressing the M key in the Advanced Setting function group. To move to this function group, refer to page 4-31, To Move to the Advanced Setting Function Group.
  • Page 107 Configuration & Basic Operation 3-37 When there are large variations in ambient temperatures due to factors such as seasonal changes or differences between day and night temperatures When there are large variations in air flow in the control cabinet When heater characteristics change depending on the control system temperature When an actuator with disproportional I/O, such as a phase-control-type power regulator, is used...
  • Page 108 3-38 Configuration & Basic Operation Figure 3.72 — Executing AT or ST in RT Mode Temperature Temperature Improved with RT Set point value Set point value Time Time Start of control Start of control When the manipulated variable (MV) is saturated, the amount of overshooting may be somewhat higher in comparison to PID control based on AT or ST in normal mode.
  • Page 109: Manual Pid Setup

    Configuration & Basic Operation 3-39 4. Press the M key to select rt (Robust Tuning). Figure 3.76 5. Press the U key to select on. off is the default. Figure 3.77 6. To return to the Initial Setting function group, press the key for at least 1 second.
  • Page 110 3-40 Configuration & Basic Operation 1. Press the key to move from the Operation function group to the Adjustment function group. Figure 3.79 Adjustment Function l.adj Group Display 2. Select Proportional Band by pressing the M key. Figure 3.80 Proportional band 3.
  • Page 111 Configuration & Basic Operation 3-41 7. Press the U or D key to set the parameter to 45. Note: This also loads the derivative time into controller memory. Figure 3.85 8. To return to the Operation function group, press the key.
  • Page 112: Alarm Outputs

    3-42 Configuration & Basic Operation Alarm Outputs Alarm Types The Bulletin 900-TC8 supports up to three alarm outputs, Bulletin 900-TC16 supports two alarm outputs, and Bulletin 900-TC32 supports one alarm output.. The controller alarm output conditions are determined by the combination of the selected Alarm Type, Alarm Value, Alarm Hysteresis, and Set Point (SP) parameters.
  • Page 113 Configuration & Basic Operation 3-43 Table 3.N — Alarm Values Alarm Output Operation When Alarm Value When Alarm Value Set Value Alarm Type X is Positive X is Negative Absolute-value Lower-Limit Absolute-value Upper-Limit with standby sequence Absolute-value Lower-Limit with standby sequence Loop Break Alarm (LBA) —...
  • Page 114: Alarm Value

    3-44 Configuration & Basic Operation Alarm Value Figure 3.86 Lower-limit alarm value Alarm value Upper-limit alarm value Alarm types can be configured independently for each Alarm 1 to 3 in the Initial Setting function group. The default is 2 (Upper Limit Alarm.) Alarm values are indicated by X in Table 3.M.
  • Page 115 Configuration & Basic Operation 3-45 1. Press the key for at least 3 seconds to move from the Operation to the Initial Setting function group. Figure 3.87 Input type in-t 2. Select the Alarm 1 Type parameter by pressing the M key. Check that the Alarm Type parameter is set to 2.
  • Page 116 3-46 Configuration & Basic Operation Precaution If a shorter PV rate of change calculation period is configured, outputs for the PV change rate alarm may repeatedly turn ON and OFF for a short period of time. Therefore, it is recommended that the PV change rate alarm be used with the alarm latch turned ON.
  • Page 117 Configuration & Basic Operation 3-47 Table 3.P — Heater Burnout & Heater Overcurrent Detection Heating Control Output Status Control Output Operation Heater Overcurrent (Heating) Indicator Power to Heater HBA Output HS Alarm Output Alarm Yes (Normal) — — No (Heater burnout) —...
  • Page 118 3-48 Configuration & Basic Operation Turn the heater power ON simultaneously or before turning power ON to the 900-TC8 or 900-TC16 controller. If the heater power is turned ON after turning ON the 900-TC8 and 900-TC16 power, the HBA will be activated.
  • Page 119 Configuration & Basic Operation 3-49 Figure 3.95 — CT Position for Single-Phase Heaters Load (such as a heater) Load AC line To controller CT input Three-phase Heaters When a 3-phase power supply is used, regardless of the types of connecting lines, two current transformers (CTs) are required to detect heater burnout and 1.
  • Page 120 3-50 Configuration & Basic Operation 3. For V connecting power lines: Refer to the following diagram for CT installation positions. Note: Heater voltage fluctuations are not considered here. Take this into account when setting the detection current. Figure 3.98 — CT Installation Positions, V Connecting Power Lines To controller CT input Load (such as a heater) AC line...
  • Page 121 Configuration & Basic Operation 3-51 The allowable controller heater current range is 0.1…49.9 A. Heater burnout, HS, and heater overcurrent are not detected when the configured alarm value is 0.0 or 50.0. When the configured alarm value is 0.0, the Heater Burnout Alarm is always OFF, the HS, and HO Alarm is always ON.
  • Page 122 3-52 Configuration & Basic Operation EXAMPLE Using Three 200V AC, 1 kW Heaters The heater power supply provides 15 A when the current is normal, and 10 A when there is a burnout. Figure 3.100 — Using Three 200V AZ, 1 kW Heaters Normal Burnout 15 A→...
  • Page 123 Configuration & Basic Operation 3-53 The heater burnout current when there is a burnout at the load is as follows: (heater burnout detection current) = (17.3 + 10) / 2 13.65 [A] To enable detection in either case, use 16.1 A as the heater burnout detection current.
  • Page 124 3-54 Configuration & Basic Operation Figure 3.104 — Heater Burnout Detection Burnout Burnout 5 A→ Load (such as a heater) Load (such as a heater) 200 V 200 V 200 V 200 V 5 A→ 5 A→ 200 V 200 V To CT input To CT input Burnout...
  • Page 125 Configuration & Basic Operation 3-55 Figure 3.106 — Heater Burnout Detection Burnout 5 A→ 10 A→ 200 V 200 V To CT input To CT input 10 A→ 200 V 200 V 200 V 200 V Burnout 5 A→ To CT Controller input To CT Controller input Current when there is a burnout = 10 A ×...
  • Page 126 3-56 Configuration & Basic Operation 1. Move to the Advanced Setting function group. Press the key for at least 3 seconds to move from the Operation function group to the Initial Setting function group. Figure 3.107 PV/SP 2. Select Move to Advanced Setting function group by pressing the M key. Figure 3.108 Input type in-t...
  • Page 127 Configuration & Basic Operation 3-57 Setting Heater Burnout Detection 1. Press the key for at least 1 second to move from the Advanced Setting function group to the Initial Setting function group and then to the Operation function group. Figure 3.111 PV/SP 2.
  • Page 128 3-58 Configuration & Basic Operation HS Alarm Setup To activate the HS alarm, set the HS Alarm Use parameter to ON in the Advanced Setting function group and set the HS Alarm 1 and HS Alarm 2 parameters in the Adjustment function group. EXAMPLE Operating Procedure: Moving to the Advanced Setting Function Group The HS Alarm Use parameter setting is already ON by default, so set the HS...
  • Page 129 Configuration & Basic Operation 3-59 HS Alarm Settings 1. Press the key for at least 1 second to move from the Advanced Setting function group to the Initial Setting function group and then to the Operation function group. Figure 3.120 PV/SP 2.
  • Page 130 3-60 Configuration & Basic Operation Heater Overcurrent Alarm To activate the heater overcurrent alarm (HOA), set the: Set-up 1. Heater Overcurrent Use parameter to ON in the Advanced Setting function group and 2. Heater Overcurrent Detection 1 and Heater Overcurrent Detection 2 parameters in the Adjustment function group.
  • Page 131 Configuration & Basic Operation 3-61 5. Press the M Key to select the Heater Overcurrent Use parameter.Check that this parameter is set to ON (the default), and then set the Heater Overcurrent Detection 1 parameter. Figure 3.128 Heater Overcurrent Configure Overcurrent Detection 1.
  • Page 132 3-62 Configuration & Basic Operation 5. For this example, set 20.0. To return to the Operation function group, press the O Key for less than one second. Figure 3.133 20.0 Set-up of the No. 3 Display This section describes how to configure the No. 3 Display (900-TC8). The Multi-SP, MV or Soak Time Remain parameters can be displayed on the No.
  • Page 133 Configuration & Basic Operation 3-63 EXAMPLE When the PV/SP Display Screen Parameter Is Set to 2 Figure 3.134 Operation Function Group PV/SP (Display 1) PV/SP (Display 2) Press the 50.0 PV/SP/Multi-SP PV/SP/MV MV Display for Heating and Select either the manipulated variable (heating) or manipulated variable (cooling) as the MV to be displayed for PV/SP/MV during heating and Cooling Control cooling control.
  • Page 134 3-64 Configuration & Basic Operation 2. Press the M Key to select the Move to Advanced Setting function group. Figure 3.136 Move to amov Advanced Function Setting -169 Level 3. Use the D Key to enter the password (“-169”). It is possible to move to the Advanced Setting function group by either pressing the M Key or waiting two seconds without pressing any key.
  • Page 135 Configuration & Basic Operation 3-65 8. Press the M Key to confirm that the Multi-SP is displayed on the No. 3 display. Figure 3.142 PV/SP System Setup/Operational 1. Allow at least a 30 minute warm-up period for the system to fully stabilize.
  • Page 136 3-66 Configuration & Basic Operation Notes: Publication 900-UM007D-EN-E - January 2011...
  • Page 137 Chapter Parameter Adjustments & Application Considerations Shifting Input Values Overview The Input Shift parameter allows you to configure the controller to compensate for possible deviation of the measured temperature (PV) to the actual temperature at the source (control target). The controller supports two types of input shifts, 1-point and 2-point.
  • Page 138 Parameter Adjustments & Application Considerations EXAMPLE Operation Procedure: Operation Function Group In this example, apply a 1 °C by 1-shift to the input value of a type K thermocouple sensor. 1. Press the key to move from the Operation function group to the Adjustment function group.
  • Page 139 Parameter Adjustments & Application Considerations 2-Point Shift Overview The 2-point shift can be applied to thermocouple, RTD, and a non-contact sensor (infrared type K thermocouple). Figure 4.8 — Temperature Limit Shift Value Upper-limit insh temperature input shift value Lower-limit insl temperature input shift value •...
  • Page 140 Parameter Adjustments & Application Considerations Preparations 1. Set to the temperature range to match the input specifications of the non-contact temperature sensor (refer to Table 3.C, — List of Global Temperature (GT) Input Types). Note: The non-contact infrared sensor is supported only in thermocouple Input Type Bulletin 900-TCX controllers.
  • Page 141 Parameter Adjustments & Application Considerations Figure 4.12 — One-Point Temperature Input Shift Controller readout (A) After shift Temperature readout Input shift value (e.g. 10°C) after shift (e.g. 120°C) Temperature readout before shift (e.g. 110°C) Before shift Temperature readout of control target (B) Near set point (e.g.
  • Page 142 Parameter Adjustments & Application Considerations Figure 4.13 — Two-Point Temperature Input Shift Controller readout (A) Set temperature upper limit YH After shift (e.g. 260°C) Upper-limit temperature Temperature readout input shift value after input shift X2 (e.g. 110°C) Before shift Temperature readout before input shift Y2 (e.g.
  • Page 143 Parameter Adjustments & Application Considerations In this example, we use the non-contact (infrared) sensor EXAMPLE type K thermocouple 0…260 °C specification to do a 2-point shift. YL and YH in equations 1 and 2 are set temperature Lower-Limit (YL = 0 °C) and set temperature Upper-Limit (YH = 260 °C).
  • Page 144 Parameter Adjustments & Application Considerations Alarm Functions/ Alarm Hysteresis Parameters You can configure/program how much deviation (hysteresis) is allowed from the alarm value before the alarm comes on and reset. The hysteresis of alarm outputs when alarms are switched ON/OFF can be set as follows: Figure 4.15 —...
  • Page 145 Parameter Adjustments & Application Considerations Alarm Latch Alarm latch is a function where you can configure the alarm output once turned ON to stay ON regardless of the process temperature. The alarm latch function can be canceled by: 1. Turning the controller power OFF. Note, however, that it can also be canceled by switching to the Initial Setting function group, Communications Setting function group, Advanced Setting function group, or Calibration function group.
  • Page 146 4-10 Parameter Adjustments & Application Considerations Configuration of Scaling Figure 4.17 in-h Upper-Limits and Scaling Scaling Upper Limit Lower-Limits for Analog in-l Scaling Lower Limit Input Decimal Point Overview When an analog input sensor is selected, scaling to engineering units (e.g., lbs) that match the application is possible.
  • Page 147 Parameter Adjustments & Application Considerations 4-11 EXAMPLE Operation Procedure In this example, configure the scaling upper- and Lower-Limits so that inputs 4…20 mA become 10.0%…95.0%. 1. Press the key for at least 3 seconds to move from the Operation function group to the Initial Setting function group. Figure 4.19 Input type in-t...
  • Page 148 4-12 Parameter Adjustments & Application Considerations 6. Select the decimal point position by pressing Figure 4.24 — Press the U or D key to set the parameter to 1. Decimal point Figure 4.25 7. To return to the Operation function group press the key for at least 1 second.
  • Page 149 Parameter Adjustments & Application Considerations 4-13 Table 4.C — Example: 900-TC8 & 900-TC16 Without Control Output 2 With Control Output 2 Parameter Name Symbol Standard Heating/Cooling Standard Heating/Cooling out1 Control Output 1 Control Output Control Output Control Output Control Output Assignment (heating) (heating)
  • Page 150 4-14 Parameter Adjustments & Application Considerations Figure 4.26 — Dead Band Overlap band: Dead band: Output Output dead band width = negative dead band width = positive Heating side Cooling side Heating side Cooling side Set point Set point Cooling Coefficient (Heating and Cooling Control) When the heating and cooling control mode and PID control method are selected, the Cooling Coefficient parameter can be used.
  • Page 151 Parameter Adjustments & Application Considerations 4-15 Table 4.E Parameter Name Setting Range Default Automatic Cooling OFF: Disabled, ON: Coefficient Adjustment Enabled Note: If there is strong non-linear gain for the cooling characteristics, such as when cooling water boils for cooling control, it may not be possible to obtain the optimum cooling coefficient at the Controller, and control may take the form of oscillating waves.
  • Page 152 4-16 Parameter Adjustments & Application Considerations Figure 4.29 Cooling c-sc coefficient 1.00 2. Press the key to set the parameter to 10.00. The setting range is 0.01…99.99. c-sc 10.00 EXAMPLE Operation Procedure: Configuring the Dead Band Dead Band = 5 1.
  • Page 153 Parameter Adjustments & Application Considerations 4-17 Setting Event Input • Event inputs can be used for Multi-SP, RUN/STOP, Auto/Manual Switch, Program Start, Invert Direct/Reverse Operation, 100% AT Execute/Cancel, 40% AT Execute/Cancel, Setting Change Enable/Disable, and Alarm Latch Cancel. • Of these, only the number of event inputs (0 to 2) set in the Number of Multi-SP Uses parameter (Initial Setting function group) are used for the multi-SP function.
  • Page 154 4-18 Parameter Adjustments & Application Considerations • When using event inputs to switch the multi-SP, the event input assignment display will not appear. Whether the set value and event input assignments 1 and 2 will be displayed or hidden is shown in the tables below.
  • Page 155 Parameter Adjustments & Application Considerations 4-19 Multi-SP Selecting Multi-SP by Event Input Multi-SP by event input is a function for setting the value of set points 0…3 in advance, and selecting these set points by a combination of Event Inputs 1 and Multi-SP selection from external (event) inputs can be used when the proper option event input unit is mounted in the Bulletin 900 and the Number of Multi-SP Uses parameter is set to 1 or 2 (refer to Tables 4.G and 4.H).
  • Page 156 4-20 Parameter Adjustments & Application Considerations The following table shows the relationship between the Multi-SP Uses parameter value and the selected set point. Table 4.I Multi-SP Uses Parameter Value Selected Set Point Select Set Point 0 value Select Set Point 1 value Select Set Point 2 value Select Set Point 3 value Note: The set point can also be switched using PC communications.
  • Page 157 Parameter Adjustments & Application Considerations 4-21 2. Select Move to Advanced Setting function group by pressing the key. Figure 4.34 Input type in-t 3. Press the key to enter the password (–169) to cancel protection. You can now move to the Advanced Setting function group by pressing the key or leaving the setting for at least 2 seconds.
  • Page 158 4-22 Parameter Adjustments & Application Considerations Figure 4.39 —Event Inputs 900-TC8 900-TC16 − − Note: Do not apply an external voltage source to the Event Input Terminals. Operation Commands Other than Multi-SP The following table shows the functions assigned when an Event Input Assignment (1 or 2) is displayed.
  • Page 159 Parameter Adjustments & Application Considerations 4-23 Executing RUN/STOP Controller Mode Change When the Event Input Assignment 1 or Event Input Assignment 2 parameter is set to STOP (RUN/STOP), control is started (RUN) when event input 1 or 2 is OFF. Control is stopped when 1 or 2 is ON (refer to Table 4.K). While control is stopped, the controller’s STP (stop) LED lights.
  • Page 160 4-24 Parameter Adjustments & Application Considerations Table 4.M Setting Input Contact Program Status Event Input 1 or 2 reset Event Input 1 or 2 Start Control by Inverting Direct/Reverse Operation When DRS (Invert Direct/Reverse Operation) is set for the Event Input Assignment 1 or Event Input Assignment 2 parameter and the Direct/Reverse Operation parameter is set for reverse operation, control starts with direct operation (cooling control) when event input 1 or 2 turns ON and control...
  • Page 161 Parameter Adjustments & Application Considerations 4-25 Switching 40% ATExecute/Cancel When AT-1 (40% AT Execute/Cancel) is set for either the Event Input Assignment1 or Event Input Assignment 2 parameter, 40% AT will be executed when event input 1 or 2 turns ON and will be cancelled when the input turns OFF Table 4.P Setting...
  • Page 162 4-26 Parameter Adjustments & Application Considerations Parameters Table 4.S Symbol Parameter: Level Description eV-1 Event Input Assignment 1: Initial Function of event input function Setting function group eV-2 Event Input Assignment 2: Initial Setting function group eV-m Number of Multi-SP Uses: Initial Setting function group Configuring the SP Upper- Set Point Limiter...
  • Page 163 Parameter Adjustments & Application Considerations 4-27 Application Considerations If a change is made to the set point upper and/or lower-limit value with the current set point outside the limiter range, the set point is forcibly changed by the controller to the sensor’s upper SP limit or lower SP limit value, whichever is closer.
  • Page 164 4-28 Parameter Adjustments & Application Considerations Figure 4.42 Input type in-t 2. Select Set Point Upper-Limit parameter by using the key. Figure 4.43 Set point upper- sl-h limit 1300 3. Press the key to set the value to 1000. EXAMPLE Operation Procedure: Configuring the Set Point Lower-Limit sl-h 1000...
  • Page 165 Parameter Adjustments & Application Considerations 4-29 Executing the SP Ramp SP Ramp Function to Limit the SP With the SP ramp function, the controller can limit the rate at which a change Rate of Change in the set point will impact the control according to the user-defined SP ramp value.
  • Page 166 4-30 Parameter Adjustments & Application Considerations SP Ramp Application Considerations SP Ramp Operation at Startup If the SP ramp function is enabled when the Bulletin 900 controller is turned ON, or when RUN is switched to from STOP, the process value (PV) may reach the Set Point SP ramp value in the same way as when the set point is changed.
  • Page 167 Parameter Adjustments & Application Considerations 4-31 Alarms During SP Ramp Operation The operation of alarms during SP ramp operation depends on whether alarms are configured to be based on the ramp set point or the target set point (refer to the Figure 4.48). The set point to be used is configured in the Alarm SP Selection parameter.
  • Page 168 4-32 Parameter Adjustments & Application Considerations 2. The controller moves to the Protect function group, and Operation/Adjustment Protection is displayed. Figure 4.49 Operation/adjust- oapt ment protect 3. Press the key once to move to Initial Setting/Communications Protection. Figure 4.50 Initial setting/ icpt communica- tions protect...
  • Page 169 Parameter Adjustments & Application Considerations 4-33 7. Select the Move to Advanced Setting function group parameter by pressing the key. Figure 4.54 Move to ad- amov vanced function setting level -169 8. Press the keys to enter the password (–169), and either press the key or leave the setting for at least 2 seconds to move to the Advanced Setting function group from the Initial Setting function group.
  • Page 170 4-34 Parameter Adjustments & Application Considerations Operation/Adjustment Protection To move to the Protect function group from the Operation or Adjustment function groups, press the O and keys simultaneously for at least 3 seconds. Note: The key pressing time can be changed using the Move to Protect function group time in the Advanced Settings function group.
  • Page 171 Parameter Adjustments & Application Considerations 4-35 Initial Setting/Communications Protection This portion of the Key Protect function group restricts movement by keypad operation to the Initial Setting function group, Communications Setting function group, and Advanced Setting function group (refer to Table 4.W). Figure 4.59 icpt Table 4.W —...
  • Page 172 4-36 Parameter Adjustments & Application Considerations PF Key Protect pfpt Table 4.Y Set Value Description ➊ PF Key enabled PF Key disabled (Operation as function key prohibited). ➊Default Entering the Password to Move to the Protect Function Group For additional system security, you can configure your controller so that you need to enter a user-defined Password to Move to the Protect function group.
  • Page 173 Parameter Adjustments & Application Considerations 4-37 1. Press the O and M keys simultaneously for at least the time configured in the Move to Protect function group time parameter to move from the Operation function group to the Protect function group. Figure 4.62 Operation/adjust- oapt...
  • Page 174 4-38 Parameter Adjustments & Application Considerations EXAMPLE Operating Procedure: To Move to the Protect Function Group With a Password of 1234 Use the following procedure to move to the Protect function group. Figure 4.65 PV/SP 1. Press the O and M keys simultaneously for at least the time configured in the Move to Protect function group time parameter to move from the Operation function group to the Protect function group.
  • Page 175 Parameter Adjustments & Application Considerations 4-39 EXAMPLE Operating Procedure: With No Password Set Figure 4.69 PV/SP 1. Press the O and M keys simultaneously for at least the time configured in the Operation/Adjustment Protect parameter to move from the Operation function group to the Protect function group. When a password is not configured, the Operation/Adjustment Protect parameter will be displayed.
  • Page 176 4-40 Parameter Adjustments & Application Considerations There are three display colors, orange, red, and green, and you can select from the following three modes and eight functions. Figure 4.71 colr PV change color • Constant: This mode displays orange, red, or green all the time. •...
  • Page 177 Parameter Adjustments & Application Considerations 4-41 Table 4.S (Continued) Mode Setting Function PV Color Change Application Example Linked to PV Stable stable stable band band Band Within High Within PV stable High Application example band r-g.r Red to Green to Green To display stable status g-o.r...
  • Page 178 4-42 Parameter Adjustments & Application Considerations Setting Configuring the PV Color Change to Indicate Stable Status To display the PV as a constant green color (to indicated a stable condition) display when the PV is within ±15.0°C of the set point, configure the PV Color Change and PV Stable Band parameters.
  • Page 179 Parameter Adjustments & Application Considerations 4-43 3. Use the D key to enter −169 (the password). Move to the Advanced Setting function group by pressing the M key or leaving the setting for at least 2 seconds. Figure 4.77 Parameter init initialization 4.
  • Page 180 4-44 Parameter Adjustments & Application Considerations Alarm Delays Alarm Delays For 900-TC8 and 900-TC16, ON and OFF timed delays can be configured for the Alarm Outputs 1, 2, and 3. For 900-TC32, ON and OFF timed delays can be configured for the Alarm Output 1.The ON and OFF delay for Alarm 1 operate only for the alarm process function.
  • Page 181 Parameter Adjustments & Application Considerations 4-45 Parameters Related to Alarm Delays Table 4.AA Parameter Name Symbol Configurable Range a1on Alarm 1 ON delay 0…999 (s) a2on Alarm 2 ON delay (900-TC8, 900-TC16) 0…999 (s) a3on Alarm 3 ON delay (900-TC8) 0…999 (s) a1of Alarm 1 OFF delay...
  • Page 182 4-46 Parameter Adjustments & Application Considerations 3. Press the D key to enter the password (−169) and move from the Initial Setting function group to the Advanced Setting function group. Figure 4.87 Parameter init initialization 4. Press the M key to select the Alarm 1 ON Delay parameter. Figure 4.88 Alarm 1 ON a1on...
  • Page 183 Parameter Adjustments & Application Considerations 4-47 9. Press the O key for at least 1 second to move from the Initial Setting function group to the Operation function group. Figure 4.93 PV/SP Loop Break Alarm Loop Break Alarm (LBA) With a Loop Break Alarm, there is assumed to be an error in the operation control loop if the control deviation (SP −...
  • Page 184 4-48 Parameter Adjustments & Application Considerations If the control deviation is reduced in the area between 5 and 6 (i.e., the set point is approached) and the amount the control deviation is reduced is at least equal to the LBA Band, the Loop Break Alarm will turn OFF. If the control deviation is reduced in the area between 6 and 7 (i.e., the set point is approached) and the amount the control deviation is reduced is less than the LBA Band, the Loop Break Alarm will turn ON.
  • Page 185 Parameter Adjustments & Application Considerations 4-49 Parameters Related to Loop Break Alarms Table 4.AB Configurable Range Application Parameter Name Symbol Sensor Type (Units) Considerations LBA Detection Time 0…9999 (s) Setting 0 disables the LBA function. lbal 0.1…999.9 (°C/°F) ➊ LBA Level Controllers with Default: 8.0 (°C/°F) Thermocouple and...
  • Page 186 4-50 Parameter Adjustments & Application Considerations Determining the LBA Detection Time To manually configure the LBA detection time, configured the LBA Detection Time parameter to twice the LBA reference time given in the example below. EXAMPLE Procedure 1. Set the output to the maximum value. 2.
  • Page 187 Parameter Adjustments & Application Considerations 4-51 EXAMPLE Operating Procedure: Loop Break Alarm Configurations In this example, the LBA Detection Time is configured to 10, the LBA Level is configured to 8.0, and the LBA Band is configured to 3.0. Figure 4.96 PV/SP 1.
  • Page 188 4-52 Parameter Adjustments & Application Considerations 5. Press the D key to enter the password (−169), and move from the Initial Setting function group to the Advanced Setting function group. Figure 4.101 Parameter init initialization 6. Select the LBA Detection Time parameter by pressing the M key. Figure 4.102 LBA detection time...
  • Page 189 Parameter Adjustments & Application Considerations 4-53 12. Press the O key for at least 1 second to move from the Advanced Setting function group to the Initial Setting function group. Figure 4.107 Input type in-t 13. Press the O key for at least 1 second to move from the Initial Setting function group to the Operation function group.
  • Page 190 4-54 Parameter Adjustments & Application Considerations The overall manual operation is illustrated in the following figure. Figure 4.109 — Overall Manual Operation MV (%) Balanceless-bumpless Time MV switched Manual Power in- terrupted Automatic Table 4.AC —Related Displays and Parameters Parameter Name Symbol Function Group Remarks...
  • Page 191 Parameter Adjustments & Application Considerations 4-55 display the Manual Control function group. It is not possible to move to any displays except for the PV/MV parameter during manual operation. Press the O key for at least 1 second from the PV/MV display in the Manual Control function group to return to automatic mode and display the top parameter in the Operation function group.
  • Page 192 4-56 Parameter Adjustments & Application Considerations Using the PF Key to Move to the Manual Control Level 1. When the PF Setting parameter is configured to A-M (Auto/Manual), pressing the PF Key for at least one second while in the adjustment or operation group will change the mode to manual mode and move to the manual control function group.
  • Page 193 Parameter Adjustments & Application Considerations 4-57 EXAMPLE Operating Procedure Use the following procedure to set the manipulated variable in Manual mode. Figure 4.111 PV/SP 1. Press the O key for at least 3 seconds to move from the Operation function group to the Initial Setting function group. Figure 4.112 Input type in-t...
  • Page 194 4-58 Parameter Adjustments & Application Considerations 4. Select the Auto/Manual Select Addition parameter by pressing the M key. Figure 4.116 Auto/manual amad select addition 5. Use the U key to set the parameter to ON. Figure 4.117 amad 6. Press the O key for at least 1 second to move from the Advanced Setting function group to the Initial Setting function group.
  • Page 195 Parameter Adjustments & Application Considerations 4-59 10. Press the U or D key to set the manual MV. (In this example, the MV is configured to 500%.) Note: The manual MV setting must be fixed, but values changed with key operations are reflected in the control output immediately.
  • Page 196 4-60 Parameter Adjustments & Application Considerations 3. Select the PID ON/OFF parameter by pressing the U Key. Figure 4.126 Move to Advanced amov Setting Group 4. Select the Move to Advanced Setting parameter by pressing the M Key 5. Press the D Key to enter the password (-169), and move from the Initial Setting function group to the Advanced Setting function group.
  • Page 197 Parameter Adjustments & Application Considerations 4-61 9. Press the O Key for at least one second to move from the Advanced Setting function group to the Initial Setting function group. Figure 4.131 Input Type in-t 10. Press the O Key for at least one second to move from the Initial Setting function group to the Operation function group.
  • Page 198 4-62 Parameter Adjustments & Application Considerations Using the Transfer Output Transfer Output Function Fort 900-TC8 and 900-TC16, if a control 1 output is an analog linear current output it can be used as a transfer output. To use the transfer output, configure the Transfer Output Type parameter to any setting other than OFF (refer to Table 4.AE).
  • Page 199 Parameter Adjustments & Application Considerations 4-63 Transfer Output Scaling • Reverse scaling is possible by configuring the Transfer Output Lower-Limit parameter larger than the Transfer Output Upper-Limit parameter. If the Transfer Output Lower-Limit and Transfer Output Upper-Limit parameters are configured to the same value when 4…20 mA is configured, the transfer output will output continuously a 0% (4 mA) signal.
  • Page 200 4-64 Parameter Adjustments & Application Considerations EXAMPLE Operating Procedure The following procedure configures the Transfer Output Type as a SP with a range (limit) of −50…200. Figure 4.137 — Operation function group PV/SP 1. Press the O key for at least 3 seconds to move from the Operation function group to the Initial Setting function group.
  • Page 201 Parameter Adjustments & Application Considerations 4-65 5. Use the D key to set the parameter to 200. The default is 1300. Figure 4.142 tr-h 6. Select the Transfer Output Lower-Limit parameter by pressing the M key. Figure 4.143 Transfer output tr-l lower limit -200...
  • Page 202 4-66 Parameter Adjustments & Application Considerations Using the Simple Program Simple Program Function Function The simple program function can be used to perform a simple one step ramp and soak operation. Figure 4.146 Wait band Set point Wait band Soak time END display RSET →...
  • Page 203 Parameter Adjustments & Application Considerations 4-67 Program Pattern Either of two program patterns (STOP or Continue) can be selected. The simple program operation will not be performed if the Program Pattern parameter is configured to OFF. Pattern 1 (STOP) Control will stop and the STOP control mode will be entered when the simple program has ended.
  • Page 204 4-68 Parameter Adjustments & Application Considerations Starting Method Any of the following three methods can be used to start the simple program. • Setting the Program Start parameter to STRT. • For 900-TC8 & 900-TC16: Turning ON an event input. (The program start must be assigned to an event input.
  • Page 205 Parameter Adjustments & Application Considerations 4-69 within the wait band around the set point (i.e., SP ± wait band). In the pre-ceding diagram, the timer will be stopped between the start and (1), (2) and (3), and (4) and (5) and will measure the time only between (1) and (2), (3) and (4), and (5) and the end.
  • Page 206 4-70 Parameter Adjustments & Application Considerations The program END output is also provided in communications status. Clearing the Program End Status The program END output and display will be cleared when the Program Start parameter is changed from STRT to RSET. The setting is changed from STRT to RSET while the Program Start parameter is displayed.
  • Page 207 Parameter Adjustments & Application Considerations 4-71 1. Press the O key for at least 3 seconds to move from the Operation function group to the Initial Setting function group. Figure 4.153 Input type in-t 2. Select the Program Pattern parameter by pressing the M key. Figure 4.154 Program Pattern ptrn...
  • Page 208 4-72 Parameter Adjustments & Application Considerations 7. Use the U key to set the parameter to 10. (The soak time unit is configured in Soak Time Unit parameter in the Advance Setting function group. The default is (minutes). Figure 4.159 soak 8.
  • Page 209 Parameter Adjustments & Application Considerations 4-73 EXAMPLE Using a Simple Program The program will be started by changing the configuration of the Program Start parameter. The following shows an example using a simple program with the program pattern configured to STOP. Figure 4.163 Wait band Set point...
  • Page 210 4-74 Parameter Adjustments & Application Considerations Table 4.AG Timing Description The Program Start parameter was changed from RSET to STRT using either an event or key operations. The RUN/STOP status automatically changes to RUN mode when the above operation is performed. The Program Start parameter was changed from STRT to RSET using either an event or key operations before the soak time expired.
  • Page 211 Parameter Adjustments & Application Considerations 4-75 Output Adjustment Output Limits Functions Output limits can be configured to limit the output using the Upper- and Lower-Limits to the calculated MV. The following MV takes priority over the MV limits. • Manual MV •...
  • Page 212 4-76 Parameter Adjustments & Application Considerations Table 4.AH Parameter Configurable Range Unit Default MV at Stop −5.0…105.0 for standard control 0.00 −105.0…105.0 (heating/cooling control) Note: The order of priority is as follows: Manual MV > MV at stop > MV at PV error.
  • Page 213 Parameter Adjustments & Application Considerations 4-77 Using the Extraction of Square Root Parameter Extraction of Square Roots Figure 4.167 — Extraction of Square Root Enable • For analog inputs, the Extraction of the Square Root parameter is provided for inputs so that differential pressure-type flow meter signals can be directly input.
  • Page 214 4-78 Parameter Adjustments & Application Considerations Table 4.AJ Parameter Name Configurable Range Unit Default Extraction of the Square Root Enable OFF: Disabled, ON: Enabled Extraction of Square Root Low-cut Point 0.0...100 Operating Procedure This procedure sets the Extraction of Square Root Low-cut Point parameter to 10.0% Figure 4.170 —...
  • Page 215 Parameter Adjustments & Application Considerations 4-79 4. Press the O Key for at least one second to move from the Initial Setting to the Operation function group. Figure 4.174 PV/SP 5. Press the O Key to move from the Operation function group to the Adjustment function group.
  • Page 216 4-80 Parameter Adjustments & Application Considerations Setting the Rate of MV Variation The MV Change Rate Limit parameter sets the maximum allowable rate of change in the MV in units of percent per second. If the change in the MV exceeds this setting, the MV will be changed by the MV change rate limit until the calculated value is reached.
  • Page 217 Parameter Adjustments & Application Considerations 4-81 2. Select the PID ON/OFF parameter by pressing the M Key. Figure 4.181 PID·ON/OFF cntl onof 3. Use the U Key to select 2-PID control. Figure 4.182 PID·ON/OFF cntl 4. Press the M Key to select the ST parameter. Figure 4.183 5.
  • Page 218 4-82 Parameter Adjustments & Application Considerations 8. Press the M Key to select the MV Change Rate Limit parameter. Figure 4.187 Change Rate Limit 9. Use the U Key to set the parameter to 5.0. Figure 4.188 Change Rate Limit 10.
  • Page 219 Parameter Adjustments & Application Considerations 4-83 Table 4.AL Set Value Symbol Operation Function Alarm Latch Cancel Specifies canceling all alarm latches (see note 2) Auto/Manual Specifies reversing the Auto/Manual status (see note 3) pfdp PFDP Monitor/Setting Specifies the monitor/setting item Item display.
  • Page 220 4-84 Parameter Adjustments & Application Considerations table shows the details of the settings. For setting (monitor) ranges, refer to applicable parameter. Table 4.AM — Setting Detail Remarks Set Value Operation/Function Monitor/Setting Symbol Disabled PV/SP/Multi-SP Can be configured. (SP) --- PV/SP/MV (see note) Can be configured.
  • Page 221 Parameter Adjustments & Application Considerations 4-85 Operating Procedure This procedure sets the PF Setting parameter to PFDP, and the Monitor/Setting Item 1 parameter to 7 (Alarm Value 1). Figure 4.190 — Operation Function Group PV/SP 1. Press the O Key for at least three seconds to move from the Operation to the Initial Setting function group.
  • Page 222 4-86 Parameter Adjustments & Application Considerations 5. Press the U Key to select PFDP (Monitor/Setting Item). Figure 4.195 PF Setting pfdp 6. Press the M Key to select the Monitor/Setting Item 1 parameter. Figure 4.196 Monitor/Setting pfd1 Item 1 7. Press the U Key to select 7 (Alarm Value 1). Figure 4.197 Monitor/Setting pfd1...
  • Page 223 Parameter Adjustments & Application Considerations 4-87 Counting Control Output Control Output ON/OFF Count Function ON/OFF Operations With Control Output 1 and 2 ON/OFF outputs (relay outputs or voltage outputs for driving SSR), the number of times that a control output turns ON and OFF can be counted.
  • Page 224 4-88 Parameter Adjustments & Application Considerations Controller. The ON/OFF count alarm configured value function is disabled by setting the ON/OFF count alarm configured value to 0. Table 4.AO Configurable Parameter Name Range Unit Default Control Output 1 ON/OFF Alarm Setting 0 to 9999 100 times 0 Control Output 2 ON/OFF Alarm Setting...
  • Page 225 Parameter Adjustments & Application Considerations 4-89 2. Select the Move to Advanced Setting function group parameter by pressing the M Key. Figure 4.202 Move to Advanced amov Setting Function Group -169 3. Use the D Key to enter the password (“-169”). It is possible to move to the Advanced Setting function group by either pressing the M Key or waiting two seconds without pressing any key.
  • Page 226 4-90 Parameter Adjustments & Application Considerations Displaying PV/SV Status PV and SV Status Display Functions The PV in the PV/SP, PV, or PV/Manual MV Display and the control and alarm status specified for the PV status display function are alternately displayed in 0.5-s cycles.
  • Page 227 Parameter Adjustments & Application Considerations 4-91 SV Status Display Function The SP, Blank, or Manual MV in the PV/SP, PV, or PV/Manual MV Display and the control and alarm status specified for the SV status display function are alternately displayed in 0.5-s cycles. Table 4.AR —...
  • Page 228 4-92 Parameter Adjustments & Application Considerations 2. Select the Move to Advanced Setting function group parameter by pressing the M Key Figure 4.209 Move to Advanced amov Setting Function Group -169 3. Use the D Key to enter the password (-169). It is possible to move to the Advanced Setting function group by either pressing the M Key or waiting two seconds without pressing any key.
  • Page 229 Chapter Parameter Functions & Definitions Conventions Used in This About the Parameter Display Chapter Parameters are displayed on the controller only when the item(s) listed in the Conditions of Use section for each parameter is satisfied. However, the configuration of protected parameters is still valid and the protected parameters are not displayed regardless of the Conditions of Use.
  • Page 230 Parameter Functions & Definitions Figure 5.1 Power ON Operation Adjustment Function Group Function Group Press the + M Keys. The display will flash. Press the for less than 1 second. Press and hold the Press and hold the + M Keys + M Keys for at least 1 second.
  • Page 231 Parameter Functions & Definitions pmov Move to Protect Function Group Conditions of Use: The Password to Move to Protect function group parameter must NOT be set to 0. Function: This parameter allows you to specify a password that must be entered to move to the Protect function group.
  • Page 232 Parameter Functions & Definitions icpt Initial Setting/Communications Protection This portion of the Protect function group restricts movement by keypad to the Initial Setting function group, Communications Setting function group, and Advanced Setting function group. Table 5.B — Initial Setting/Communications Protection Configured Initial Setting Communications Setting...
  • Page 233 Parameter Functions & Definitions pfpt PF Key Protect Conditions of Use: The Controller must have a PF Key (900-TC8) Function: The PF Key Protect parameter enables and disables PF Key operation from the controller keypad (900-TC8). Table 5.E PF Key Protect Configured Value Description PF Key enabled from keypad PF Key disabled from keypad (Operation as a function key is...
  • Page 234 Parameter Functions & Definitions Table 5.G Configuration Range Default −1999…9999 Set this parameter to 0 when no password is to be configured. Related Parameters Move to Protect function group (Protect function group, page 5-3) Note: Protection cannot be cleared or changed without the password. Be careful not to forget it.
  • Page 235 Parameter Functions & Definitions Operation Function Group Page Page Process value Alarm 1 value al-1 5-16 Process value/set point Alarm 1 value al1h 5-18 upper-limit Auto/manual switch Alarm 1 value al1l 5-10 5-18 lower-limit Multi-SP set point Alarm 2 value m-sp al-2 5-10...
  • Page 236 Parameter Functions & Definitions Note: When a temperature input (e.g., RTD) is selected, the decimal point position depends on the currently selected sensor, and when an analog input is selected, it depends on the Decimal Point parameter setting. Related Parameters Refer to the Initial Setting function group: Input Type (page 5-50) Set Point Upper-Limit, Set Point Lower-Limit (page 5-54)
  • Page 237 Parameter Functions & Definitions Table 5.K Configured Value No. 3 Display Contents PV/SP/Multi-SP and PV/SP/Soak time remain are displayed in order. PV/SP/MV and PV/SP/Soak time remain are displayed in order. Only PV/SP/Soak time remain are displayed. Note: When a temperature input (e.g., RTD) is selected, the decimal point position depends on the currently selected sensor, and when an analog input is selected, it depends on the Decimal Point parameter setting.
  • Page 238 5-10 Parameter Functions & Definitions Auto Manual Switch Conditions of Use: The Event Input Assignment 1 or 2 parameters must NOT be set to Auto/Manual and the Auto/Manual Select Addition parameter must be configured to ON. The control mode MUST be configured to 2-PID control.
  • Page 239 Parameter Functions & Definitions 5-11 Function: This parameter allows you to monitor the value of the Set Point during a SP Ramp function. Ramp is a function for restricting the amount the set point can change, from the current value to a new value, as a rate of change. The currently configured value is displayed when using the SP Ramp Set Value parameter in the Advanced Setting function group.
  • Page 240 5-12 Parameter Functions & Definitions Table 5.M Monitoring Range Units 0.0…55.0 A (Amps) ffff is displayed when 55.0 A is exceeded. If a heater burnout detection 1 or heater overcurrent detection 1 alarm is output, the HA indicator will light and the No. 1 display for the heater current 1 value monitor will flash.
  • Page 241 Parameter Functions & Definitions 5-13 Function: This parameter measures the heater current from two CT inputs used for detecting heater alarm conditions in 3-phase heaters and displays the value on the controller. Table 5.N Monitoring Range Units 0.0...55.0 A (Amps) Heater burnout, heater short, and heater overcurrent conditions are not detected if the Control Output (heating) ON time is 100 ms or less.
  • Page 242 5-14 Parameter Functions & Definitions Table 5.O Monitoring Range Units 0.0…55.0 A (Amps) HS alarm is not detected if the Control Output (heating) OFF time is 100 ms or less. ffff is displayed when 55.0 A is exceeded. If an HS alarm 1 alarm is output, the HA indicator will light and the No. 1display for the leakage current 1 monitor will flash.
  • Page 243 Parameter Functions & Definitions 5-15 Related Parameters Refer to the Advanced Setting function group: HS Alarm 1, HS Alarm 2 (page 5-31) HS Alarm Use (page 5-88) lcr2 Error Displays (Chpater 6, page 6-5) prst Program Start Conditions of Use: The Program Pattern parameter must NOT be set to OFF.
  • Page 244 5-16 Parameter Functions & Definitions Function: This parameter measures and displays the soak time remaining for the simple program function. Table 5.R Monitoring Range Units 0…9999 Minutes or hours Related Parameters Program Start (Operation function group, page 5-15) Soak Time, Wait Band (Adjustment function group, page 5-40) Program Pattern (Initial Setting function group, page 5-57) Soak Time Unit (Advanced Setting function group, page 5-96) RUN/STOP...
  • Page 245 Parameter Functions & Definitions 5-17 Function: This parameter sets the alarm value for alarm 1. This parameter is set to one of the input values “X” in the alarm type list. During temperature input, the decimal point position depends on the currently selected sensor, and during analog input it depends on the Decimal Point parameter setting.
  • Page 246 5-18 Parameter Functions & Definitions al-3 Alarm Value 3 (900-TC8) Conditions of Use: Alarm 3 must be assigned. The alarm 3 type must not be 0, 1, 4, 5, or 12. Function: This parameter sets the alarm value for alarm 3. This parameter is set to one of the input values “X”...
  • Page 247 Parameter Functions & Definitions 5-19 When using a temperature input, the decimal point position depends on the currently selected sensor, and when using an analog input it depends on the Decimal Point parameter setting. Table 5.V Configurable Range Units Default Value –1999…+9999 Related Parameters Input Type (page 5-50), Scaling Upper-Limit, Scaling Lower-Limit,...
  • Page 248 5-20 Parameter Functions & Definitions Related Parameters Input Type (page 5-50), Scaling Upper-Limit, Scaling Lower-Limit, Decimal Point (page 5-52), Alarm 2 Type (page 5-59) (Initial Setting function group) Standby Sequence Reset (page 5-72), Auxiliary Output 2 Open in Alarm (page 5-73), Alarm 2 Hysteresis (page 5-62), Alarm 2 Latch (page 5-79) (Advanced Setting function group) al3 h Upper-Limit Alarm Value 3...
  • Page 249 Parameter Functions & Definitions 5-21 Related Parameters Input Type (page 5-50), Scaling Upper-Limit, Scaling Lower-Limit, Decimal Point (page 5-52), Alarm 3 Type (page 5-59) (Initial Setting function group) Standby Sequence Reset (page 5-72), Auxiliary Output 3 Open in Alarm (page 5-73), Alarm 3 Hysteresis (page 5-62), Alarm 3 Latch (page 5-79) (Advanced Setting function group) MV Monitor (Heating) Conditions of Use: The Manipulated Variable (MV) display parameter must...
  • Page 250 5-22 Parameter Functions & Definitions MV Monitor (Cooling) Conditions of Use: The control method must be heating and cooling control. The Manipulated Variable Display parameter must be configured to ON. Function: This parameter is for monitoring the manipulated variable (cooling output) during heating and cooling control.
  • Page 251 Parameter Functions & Definitions 5-23 To move to the Adjustment function group from the Operation function group, press the key for less than 1 second. 1. Adjustment function group parameters can be changed after configuring the Operation/Adjustment Protect parameter to 0. Displays and moving to other function groups is not possible if the Operation/Adjustment Protect parameter is set from 1 to 3.
  • Page 252 5-24 Parameter Functions & Definitions Figure 5.5 Adjustment Function Group Page Page Page Adjustment 5-24 l.adj Function Group SP 0 Dead Band sp-0 c-db 5-33 5-37 Display AT Execute/Cancel SP 1 Manual Reset Value 5-25 sp-1 of-r 5-33 5-38 50.0 Communications SP 2 Hysteresis (Heating)
  • Page 253 Parameter Functions & Definitions 5-25 AT Execute/Cancel Conditions of Use: The Bulletin 900-TC8, 900-TC16, or 900-TC32 must be in operation (RUN), and the control method must be 2-PID control. Function: This parameter allows you to initiate (turn ON) the controller’s AT (auto-tuning) function.
  • Page 254 5-26 Parameter Functions & Definitions cmwt Communications Writing Conditions of Use: An RS-232 (900-TC8 only) or RS-485 (900-TC8 and/or 900-TC16 and/or 900-TC32) communication option unit must be mounted in the controller. Function: This parameter enables/disables writing of parameters to the temperature controller from a personal computer using communications.
  • Page 255 Parameter Functions & Definitions 5-27 Table 5.AB Monitoring Range Units 0.0…55.0 A (Amps) Note: Not all controllers support heater current monitor and heater burnout/short (refer to Tables 1.B and 1.E). If a heater fault (open/short or overcurrent) is less than or equal to 100 ms it is not detected.
  • Page 256 5-28 Parameter Functions & Definitions Note: If the Heater burnout or heater overcurrent fault is less than or equal to 100 ms it is not detected. Table 5.AC Monitoring Range Units 0.0…55.0 A (Amps) ffff is displayed when 55.0 A is exceeded. If a heater burnout detection 2 or heater overcurrent detection 2 alarm is output, the HA indicator will light and the No.
  • Page 257 Parameter Functions & Definitions 5-29 Table 5.AD Monitoring Range Units 0.0…55.0 A (Amps) ffff is displayed when 55.0 A is exceeded. If a HS alarm 1 alarm is output, the HA indicator will light, and the leakage current value will flash on the No. 1 display. Related Parameters Refer to the Advanced Setting function group: HS Alarm 1, HS Alarm 2 (page 5-31)
  • Page 258 5-30 Parameter Functions & Definitions Related Parameters Refer to the Advanced Setting function group: HS Alarm 1, HS Alarm 2 (page 5-31) HS Alarm Use (page 5-88) lcr2 Error Displays Heater Burnout Detection 1 (900-TC8, 900-TC16) Conditions of Use: Heater Burnout (HBA) and Heater Short (HSA) alarms and heater overcurrent detection must be supported.
  • Page 259 Parameter Functions & Definitions 5-31 Heater Burnout Detection 2 (900-TC8, 900-TC16) Conditions of Use: Heater Burnout (HBA) and Heater Short (HSA) alarms and heater overcurrent detection must be supported. Alarm 1 must be assigned. The Heater Burnout Detection parameter must be set to ON. Two CTs must be wired to the controller.
  • Page 260 5-32 Parameter Functions & Definitions Table 5.AH Configurable Range Units Default 0.0…50.0 A (Amps) 50.0 The HS alarm is output when the heater current value goes above the setting of this parameter. When the configured value is 50.0, the HS alarm is turned OFF. When the configured value is 0.0, the HS alarm will turn ON.
  • Page 261 Parameter Functions & Definitions 5-33 Related Parameters Refer to the Advanced Setting function group: Leakage Current 2 Monitor (page 5-14) HS Alarm Use, HS Alarm Latch, HS Alarm Hysteresis (page 5-88) sp-0 Set Point 0 sp-1 Set Point 1 sp-2 Set Point 2 sp-3 Set Point 3...
  • Page 262 5-34 Parameter Functions & Definitions Related Parameter PV/SP (Operation function group, page 5-8), Input Type (Initial Setting function group) (page 5-50) Refer to the Advanced Setting function group: Event Input Assignment 1 (page 5-66) Event Input Assignment 2 (page 5-66) Number of Multi-SP Uses (page 5-65) Multi-SP Uses (page 5-71) Temperature Input Shift...
  • Page 263 Parameter Functions & Definitions 5-35 insh Upper-Limit Temperature Input Shift Value, insl Lower-Limit Temperature Input Shift Value Conditions of Use: The Input Type parameter must be configured for a thermocouple on RTD sensor and the Input Shift Type parameter must be configured for 2-Point Shift.
  • Page 264 5-36 Parameter Functions & Definitions Proportional action: P refers to control in which the Manipulated Variable (MV) is proportional to the deviation (control error). Integral action: I gives a control action that is proportional to the time integral of the deviation. With proportional control, there is normally an offset (control error).
  • Page 265 Parameter Functions & Definitions 5-37 In the heating and cooling control mode, the cooling Control Output side P is calculated by the following formula to configure the cooling coefficient: Cooling Control Output side P = Cooling coefficient x P (proportional band) Table 5.AN Configurable Range Units...
  • Page 266 5-38 Parameter Functions & Definitions of-r Manual Reset Value Conditions of Use: The control mode must be standard control with the 2-PID control method configured. In addition, the Integral Time parameter must be set to 0. Function: This parameter allows you to configure the manipulated variable to remove offset during stabilization of P or PD control.
  • Page 267 Parameter Functions & Definitions 5-39 Table 5.AQ Configurable Parameters Controller Type Range Units Default °C or °F ➊ Hysteresis (heating) With Thermocouple or Resistance Thermometer (RTD) 0.1…999.9 With Analog Inputs 0.01…99.99 0.10 °C or °F ➊ Hysteresis (cooling) With Thermocouple or Resistance Thermometer (RTD) 0.0…999.9 With Analog Inputs 0.01…99.99...
  • Page 268 5-40 Parameter Functions & Definitions wt-b Wait Band Conditions of Use: The Program Pattern parameter must NOT be set to OFF. Function: This parameter enables you to configure the stable band within which the soak time is measured for the simple program function. Table 5.AS Configurable Controller Type...
  • Page 269 Parameter Functions & Definitions 5-41 Related Parameters RUN/STOP (Operation function group, page 5-16) MV at Stop and Error Addition (Advance Setting function group, page 5-87) mv-e MV at PV Error Conditions of Use: The control must be configured for 2-PID control. The MV at Stop and Error Addition parameter must be ON.
  • Page 270 5-42 Parameter Functions & Definitions Table 5.AV Parameter Configurable Range Units Default Value SP Ramp Value OFF, 1…9999 Related Parameters Input Type (page 5-50), Scaling Upper-Limit, Scaling Lower-Limit (page 5-52), Decimal Point, ST (page 5-56) (Initial Setting function group) SP Ramp Time Units (Advanced Setting function group, page 5-71) ol-h MV (Manipulated Variable) Upper-Limit, ol-l...
  • Page 271 Parameter Functions & Definitions 5-43 MV Lower-Limit The configurable ranges allowed during the standard control and heating and cooling control modes are different. The manipulated variable at the cooling Control Output side during heating and cooling control is expressed as a negative value (refer to Table 5.AX). Table 5.AX Control Mode Configurable Range...
  • Page 272 5-44 Parameter Functions & Definitions Related Parameters Proportional Bband (Adjustment function group, page 5-35) 5qrp Extraction of Square Root Low-cut Point, Condition of Use: The input type must be an analog input, and the Extraction of Square Root Enable parameter must be set to ON. Function: This parameter sets the extraction of square root low-cut point used for the inputs.
  • Page 273 Parameter Functions & Definitions 5-45 Monitor/Setting Item Level Monitor/setting items can be displayed by means of the PF function key when the PF Setting parameter (Advanced Setting function group) is configured to (900-TC8) PFDP: Monitor/Setting Item. Power ON Operation Adjustment Function Group Function Group Press the...
  • Page 274 5-46 Parameter Functions & Definitions Table 5.BA Remarks Value Setting Monitor/Setting Symbol al-2 Alarm value 2 Can be set. al2h Alarm value upper limit 2 Can be set. al2l Alarm value lower limit 2 Can be set. al-3 Alarm value 3 Can be set.
  • Page 275 Parameter Functions & Definitions 5-47 Figure 5.6 Operation Adjustment Function Group Function Group Press the Key for Press and hold the at least 1 second. Key for at least PF PF 1 second. Press the Key for at Press the Key for at least least 1 second or the 1 second.
  • Page 276 5-48 Parameter Functions & Definitions (900-TC8) the PV, SP and the Manual MV can be displayed if the third parameter is enabled (refer to the following graphics displays) PV/SP/Manual MV With No. 3 Display Without No. 3 Display 50.0 50.0 50.0 MANU MANU...
  • Page 277 Parameter Functions & Definitions 5-49 Figure 5.7 Operation Function Group Press the Press the for 1 second. for at least 3 seconds. Inital Setting Function Group Control in Progress Control Stopped To move from the Operation function group to the Initial Setting function group, press key for 3 seconds with any parameter displayed except for auto/man switch parameter.
  • Page 278 5-50 Parameter Functions & Definitions Figure 5.8 Initial Setting Function Group Page Page Transfer Output Lower 5-63 tr-l 5-50 Input Type Control Period (Heating) in-t 5-57 Limit Linear Current Output 5-64 o1-t Scaling Upper Limit Control Period (Cooling) 5-52 in-h c-cp 5-57 4-20...
  • Page 279 Parameter Functions & Definitions 5-51 If a platinum resistance thermometer (RTD) is mistakenly connected while a setting for other than a platinum resistance thermometer is in effect, the controller error code S.ERR will be displayed. To clear the S.ERR display, check the wiring and then cycle the controller power. Table 5.BD —...
  • Page 280 5-52 Parameter Functions & Definitions Table 5.BE — Analog Input Type Controllers (900-TC8 & 900-TC16) Input Type Specifications Set Value Input Temperature Range Current input 4…20 mA Controller One of the following ranges depending on the scaling. −1,999…9,999 Type with 0…20 mA −199.9…999.9 Analog...
  • Page 281 Parameter Functions & Definitions 5-53 Table 5.BG Decimal Point Parameter Controller Type Configurable Range Default Decimal Point Controllers with 0…1 Thermocouple/Resistance Thermometer (RTD) inputs Controllers with Analog Inputs 0…3 Table 5.BH Configured Value Meaning Example 0 digits to the right of the decimal point 1234 1 digits to the right of the decimal point 123.4...
  • Page 282 5-54 Parameter Functions & Definitions sl-h Set Point Upper-Limit, sl-l Set Point Lower-Limit Function: These parameters allow you to configure the maximum allowable range for an operator to enter the set point value. The SP can be configured within the range defined by the Upper- and Lower-Limit values in the Set Point Upper-Limit and Set Point Lower-Limit parameters.
  • Page 283 Parameter Functions & Definitions 5-55 cntl PID ON/OFF Function: This parameter allows you to configure the controller for either the 2-PID control or ON/OFF control method. The Auto-Tuning (AT) and Self-Tuning (ST) parameter functions can only be used in the 2-PID control method. Table 5.BL Selections Default Selection...
  • Page 284 5-56 Parameter Functions & Definitions Table 5.BM Selections Default Selection stnd: Standard stnd: Standard h-c: Heating and cooling Related Parameters MV Monitor (Heating) (page 5-21), MV Monitor (Cooling) (page 5-22) (Operation function group) Cooling Coefficient, Dead Band (page 5-36), Hysteresis (heating), Hysteresis (Cooling) (page 5-38) (Adjustment function group) Control Period (Heat), Control Period (Cool) (Initial Setting function group, page 5-57)
  • Page 285 Parameter Functions & Definitions 5-57 ptrn Program Pattern Function: This parameter allows you to select the type of control when using the simple program function. If the program functionis set to: OFF, the simple program will not operate. STOP, the RUN/STOP status will change to STOP after the soak time has expired.
  • Page 286 5-58 Parameter Functions & Definitions Table 5.BP Parameter Configurable Range Units Default Value Control Period (heat) 0.5 or 1…99 Seconds Control Period (cool) 0.5 or 1…99 Seconds When the standard control mode is selected, use the Control Period (cool) parameter. The Control Period (heat) parameter cannot be used. When the heating control output is an analog output the control period cannot be used.
  • Page 287 Parameter Functions & Definitions 5-59 alt1 Alarm Type for Alarm 1 Conditions of Use: Alarm 1 must be configured and supported by the controller. Function: This parameter allows you to configure the type of alarm operation for Alarm Output 1. Select one of the following Alarm 1 types: Deviation, Deviation range, Absolute value, LBA, or PV change rate alarm.
  • Page 288 5-60 Parameter Functions & Definitions Related Parameters Alarm value 2 (page 5-17), Alarm value upper limit 2 (page 5-19), Alarm value lower limit 2 (page 5-19) (Operation function group) Standby sequence reset (page 5-72), Auxiliary output * open in alarm: (page 5-73), Alarm 2 hysteresis (page 5-62), Alarm 2 latch (page 5-79) (Advanced Setting function group) Alarm value 3 (page 5-18), Alarm value upper limit 3 (page 5-20), Alarm...
  • Page 289 Parameter Functions & Definitions 5-61 Table 5.BR — Details Alarm Output Operation When Alarm Value When Alarm Value Set Value Alarm type X is Positive X is Negative Loop Break Alarm (LBA) — (Alarm 1 Type only) PV Change Rate Alarm —...
  • Page 290 5-62 Parameter Functions & Definitions alh2 Alarm 2 Hysteresis Conditions of Use: Alarm 2 must be assigned. The alarm 2 type must NOT be 0, 12, or 13. alh3 Alarm 3 Hysteresis Conditions of Use: Alarm 3 must be assigned. The alarm 3 type must NOT be 0, 12, or 13.
  • Page 291 Parameter Functions & Definitions 5-63 Table 5.BT — Transfer Output Destination Transfer Output Control Output 1 Type Control Output 2 Type Destination Current Output • No Control Output 1 • Relay Output • Voltage Output (for driving SSR) • Relay Output •...
  • Page 292 5-64 Parameter Functions & Definitions Table 5.BV Default Transfer Output Transfer Output Type Configurable Range Lower-Limit Upper-Limit Units Set Point SP Lower-Limit to SP Upper-Limit SP Lower-Limit SP Upper-Limit Set Point during SP SP Lower-Limit to SP Upper-Limit Ramp Temperature Senor setting range Lower-Limit to Sensor Setting Sensor Setting...
  • Page 293 Parameter Functions & Definitions 5-65 ev-m Number of Multi-SP Uses (900-TC8, 900-TC16) Conditions of Use: An event input unit must be assigned. An optional event input unit must be installed in the controller. Function: Multi-SP is a function for setting set points 0 to 3 in advance, and switching between these set points using a combination of event input ON/OFF signals.
  • Page 294 5-66 Parameter Functions & Definitions The following table shows the functions assigned when an Event Input Assignment (1 or 2) is displayed. Table 5.CB Selection Function none None stop RUN/STOP manu Auto/Manual Switch prst Program start (see note 1.) Invert Direct/Reverse Operation at-2 100% AT Execute/Cancel at-1...
  • Page 295 Parameter Functions & Definitions 5-67 Function: The following functions can be assigned to event inputs 1 and 2: • RUN/STOP • Auto/Manual Switch • Program Start • Invert Direct/Reverse Operation • 100% AT Execute/Cancel • 40% AT Execute/Cancel • Setting Change Enable/Disable •...
  • Page 296 5-68 Parameter Functions & Definitions Extraction of Square Root Enable (900-TC8, 900-TC16) Conditions of Use: An analog input must be supported. Function: This parameter enables and disables square root extraction. Table 5.CD Setting Range Default on: Enabled, off: disabled None Related Parameter Extraction of square root low-cut point (Adjustment function group, page 5-44)
  • Page 297 Parameter Functions & Definitions 5-69 Advanced Setting Function This function group is for using the Bulletin 900 controller to its maximum capability. Group Figure 5.9 Power ON Adjustment Operation function group function group Press the O Key less than 1 s. Press the Press Press the O Key for at...
  • Page 298 5-70 Parameter Functions & Definitions Figure 5.10 Advanced Setting Function Group Heater Alarm 1 Latch Parameter 5-100 HS Alarm Use init a1lt 5-79 Overcurrent 5-88 Initialization 5-71 Hysteresis Multi-SP Uses Alarm 2 Latch PF Setting mspu 5-101 a2lt HS Alarm Latch 5-79 5-71 5-89...
  • Page 299 Parameter Functions & Definitions 5-71 init Parameter Initialize Function: This parameter allows you to return/reset all of the controller’s parameter settings to their initial/default values. Table 5.CE Parameter Selection Default off: Initialization is not executed. fact: Initializes to the factory settings described in the manual. mspu Multi-SP Uses Conditions of Use: The controller must NOT have an event input option...
  • Page 300 5-72 Parameter Functions & Definitions Table 5.CF Configurable Range Default s: EU/s, m: EU/min Related Parameters Ramp SP Monitor (Operation function group, page 5-10) SP Ramp Set Value (Adjustment function group, page 5-41) rest Standby Sequence Reset Method Conditions of Use: The Alarm Type for alarms 1 3 must be configured for 5, 6, 7, 10 or 11 (refer to Table 5.BR).
  • Page 301 Parameter Functions & Definitions 5-73 Table 5.CG Selections Default Selection a: Condition A b: Condition B Related Parameters Alarm 1…3 Type(see note) (Initial Setting function group, page 5-59) Alarm 1…3 Latch (see note) (Advanced Setting function group, page 5-79) Note: Alarm 3 is not applicable for 900-TC16. Alarm 2 and 3 are not applicable for 900-TC32.
  • Page 302 5-74 Parameter Functions & Definitions HB ON/OFF (900-TC8, 900-TC16) Conditions of Use: The controller hardware that supports the Heater Burnout (HB), Heater Short (HS), and Heater Overcurrent (HO), Alarm 1 must be configured and the appropriate number of Current Transformers (CT) to support the application are connected to the controller.
  • Page 303 Parameter Functions & Definitions 5-75 Table 5.CJ Selections Default Selection on: Latch Enabled off: Latch Disabled Related Parameter HB ON/OFF (Advanced Setting function group, page 5-74) Event Input Assignment 1 and 2 (Initial Setting function group, page 5-66) Heater Burnout Hysteresis (900-TC8, 900-TC16) Conditions of Use: The Heater Burnout ON/OFF parameter must be configured to ON.
  • Page 304 5-76 Parameter Functions & Definitions used when the Self-Tuning (ST) parameter is set to OFF (refer to Table 5.CL and Table 5.CL). Table 5.CL — Self-Tuning Stable Range Configurable Range Units Default Value °C or °F 0.1…999.9 15.0 Note: Analog inputs do not apply to ST Stable Range because units are °...
  • Page 305 Parameter Functions & Definitions 5-77 at-g AT Calculated Gain at-h AT Hysteresis lcma Limit Cycle MV Amplitude Conditions of Use: Control must be configured to 2-PID control. Normally use the default values for these parameters Function: The AT Calculated Gain parameter sets the gain when PID values are calculated using AT.
  • Page 306 5-78 Parameter Functions & Definitions Figure 5.12 PV before passing through filter PV after passing through filter 0.63 A Time Time Constant Input Digital Filter Table 5.CO Configurable Range Units Default Value 0.0…999.9 Seconds puad Additional PV Display Function: This parameter allows you to configure the controller so that only the PV is displayed.
  • Page 307 Parameter Functions & Definitions 5-79 Table 5.CQ Selections Default Selection on: Displayed off: Not displayed Related Parameters MV Monitor (heating) (page 5-21) MV Monitor (cooling) (page 5-22) (Operation function group) Automatic Display Return Time Function: If you do not operate any of the keys on the front panel for the time set by this parameter in the Operation function group, Adjustment function group, or Monitor function group, the display automatically returns to the PV/SP display.
  • Page 308 5-80 Parameter Functions & Definitions Function: When this parameter is set to ON, the alarm function is held until one of the following conditions are satisfied: The power to the controller is cycled. The latch is cancelled by the PF Key. (PF Setting = LAT: Alarm Latch Cancel) The latch is cancelled by an event input.(Event Input Assignment 1 and 2 = LAT: Alarm Latch Cancel)
  • Page 309 Parameter Functions & Definitions 5-81 Table 5.CT Configurable Range Units Default Value 1…30 Seconds Related Parameters Operation/Adjustment Protection, Initial Setting/Communications Protection, Setting Change Protection (Protect function group, page 5-1) sero Input Error Output Conditions of Use: Alarm 1 must be assigned. Function: When this parameter is configured to ON, the output assigned to the Alarm 1 output turns ON at an input error condition.
  • Page 310 5-82 Parameter Functions & Definitions Cold Junction Compensation Method Conditions of Use: The Input Type must be thermocouple or non-contact infrared temperature sensor. Function: This parameter allows you to specify whether cold junction compensation is to be performed internally by the controller or to be performed externally when the Input Type setting value is 5 to 22, 24, or 25.
  • Page 311 Parameter Functions & Definitions 5-83 Modes: Constant: This mode displays orange, red, or green all the time. Linked to Alarm 1: This mode switches the PV display color from red to green when Alarm 1 turns ON or from green to red when Alarm 1 turns ON.
  • Page 312 5-84 Parameter Functions & Definitions Table 5.CW — Settings Mode Setting Function PV Color Change Application Example Linked to PV Within Within stable band PV stable PV stable band band Within High PV stable band High Application example r-g.r Red to Green Green To display stable status to Red...
  • Page 313 Parameter Functions & Definitions 5-85 Table 5.CX Configurable Controller Models Range Units Default ➊ Controllers with Thermocouple and 0.1…999.9 °C or °F Resistance Thermometer (RTD) inputs Controllers with Analog Inputs 0.01…99.99 5.00 ➊ Set NONE as the unit for Controllers with Millivolt Inputs. Related Parameter PV Color Change (Advanced Setting function group, page 5-82) a1on...
  • Page 314 5-86 Parameter Functions & Definitions a1of Alarm 1 OFF Delay a2of Alarm 2 OFF Delay a3of Alarm 3 OFF Delay Conditions of Use: Alarm 1 must be assigned, and the Alarm 1 Type parameter must NOT be 0, 12, or 13. Alarm 2 must be assigned, and the Alarm 2 Type parameter must NOT be 0, 12, or 13.
  • Page 315 Parameter Functions & Definitions 5-87 Related Parameters Temperature Input Shift, Upper-Limit Temperature Input Shift Value, Lower-Limit Temperature Input Shift Value (Adjustment function group, page 5-34) Input Type (Initial Setting function group, page 5-50) mvse MV at Stop and Error Addition Conditions of Use: The control method must be configured to 2-PID control.
  • Page 316 5-88 Parameter Functions & Definitions Robust Tuning (RT) Conditions of Use: The control method must be configured to 2-PID control. The Input Type must be configured to temperature input. Function: This parameter executes robust tuning (RT). When Auto-tuning (AT) or Self-tuning (ST) is executed with RT selected, PID constants are automatically set which make it hard for control performance to degenerate even when control object characteristics have changed.
  • Page 317 Parameter Functions & Definitions 5-89 Heater Short Alarm (HSA) Latch (900-TC8, 900-TC16) Conditions of Use: Heater Burnout (HBA), Heater Short Alarms (HSA), and heater overcurrent detection must be supported. Alarm 1 must be assigned. The HS Alarm parameter must be set to ON. Optional controller hardware and/or support hardware (e.g., CTs) must be installed.
  • Page 318 5-90 Parameter Functions & Definitions Function: This parameter allows you to configure the hysteresis (allowed deviation from setting) for the operation of the Heater Short Alarm (HSA). Table 5.DG Configurable Range Units Default 0.1…50.0 A (Amps) Related Parameter HS Alarm Use (Advanced Setting function group, page 5-88) Loop Break Alarm (LBA) Detection Time Conditions of Use: Alarm 1 must be assigned.
  • Page 319 Parameter Functions & Definitions 5-91 Function: This parameter allows you to configure the SP and PV process condition for the LBA Level parameter. If the deviation between the SP and PV exceeds the LBA Level, a control loop error is detected. Table 5.DI Configurable Controller Models...
  • Page 320 5-92 Parameter Functions & Definitions Related Parameters Process Value/Set Point (Operation function group, page 5-8) Alarm 1 Type (Initial Setting function group, page 5-59) LBA Detection Time, LBA Level (Advanced Setting function group, page 5-90) out1 Control Output 1 Assignment Conditions of Use: The Transfer Output Type parameter must be set to OFF when the Control Output is an analog current output.
  • Page 321 Parameter Functions & Definitions 5-93 out2 Control Output 2 Assignment (900-TC8 & 900-TC16) Conditions of Use: Control Output 2 must be assigned/available. For a list of controllers or option units that provide Control Output 2 functionality refer to Tables 1.B and 1.E. Function: This parameter sets the function to be assigned to Control Output 2.
  • Page 322 5-94 Parameter Functions & Definitions Table 5.DM Auxiliary Output 1 Function Default none: alm1 ➌ No function is assigned to auxiliary output 1 Heating Control Output is output c-o: Cooling Control Output is output ➊➍ alm1: Alarm 1is output alm2: Alarm 2 is output alm3: Alarm 3 is output (900-TC8 only)
  • Page 323 Parameter Functions & Definitions 5-95 Table 5.DN Auxiliary Output 2 Function Default none: alm2➌ No function is assigned to auxiliary output 2 (see note to Heating Control Output is output follow) c-o: Cooling Control Output is output➊ alm1: Alarm 1is output alm2: Alarm 2 is output alm3:...
  • Page 324 5-96 Parameter Functions & Definitions Table 5.DO Auxiliary Output 3 Function Default none: alm3 ➌ No function is assigned to auxiliary output 3 Heating Control Output is output c-o: Cooling Control Output is output➊ alm1: Alarm 1is output alm2: Alarm 2 is output alm3: Alarm 3 is output p.end:...
  • Page 325 Parameter Functions & Definitions 5-97 Function: This parameter allows you to configure the units of time used for the soak time when the simple program function is used. Table 5.DQ Selections Default m: Minutes, h: Hours Related Parameters Program Start, Soak Time Remain (Operation function group, page 5-15) Soak Time, Wait Band (Adjustment function group, page 5-40) Program Pattern (Initial Setting function group, page 5-57)
  • Page 326 5-98 Parameter Functions & Definitions Function: This parameter allows you to configure whether the MV Upper Limit and MV Lower Limit parameters are to be enabled when in manual mode. Table 5.DR Selections Default on: Enabled, off: Disabled Related Parameter MV upper limit, MV lower limit (Adjustment Level function group, page 5-42) pvrp...
  • Page 327 Parameter Functions & Definitions 5-99 Function: By setting the Automatic Cooling Coefficient Adjustment parameter to ON, autotuning can be executed during heating/cooling control to automatically calculate the cooling coefficient at the same time as the PID parameters. If there is strong non-linear gain for the cooling characteristics, such as when cooling water boils for cooling control, it may not be possible to obtain the optimum cooling coefficient at the Controller, and control may take the form of oscillating waves.
  • Page 328 5-100 Parameter Functions & Definitions Function: When you configure this parameter to ON, the HS alarm is held until any of the following conditions is satisfied: Heater overcurrent detection is set to 50.0 A. The controller power is cycled. The latch is cancelled by the PF Key. (900-TC8) PF Setting = LAT: Alarm Latch Cancel The latch is cancelled by an event input.
  • Page 329 Parameter Functions & Definitions 5-101 Related Parameters Heater overcurrent use (Advanced Setting function group, page 5-99) PF Setting Conditions of Use: The PF Key must be supported (900-TC8) Function: This parameter allows you to configure which function the PF Key will have.
  • Page 330 5-102 Parameter Functions & Definitions * (*: Monitor/ Setting Item 1 to 5) Conditions of Use: The PF Setting parameter must be configured to PFDP. Function: When you configure the PF Key parameter to Monitor/Setting Item it enables using the function key to display monitor/setting items. The items that will be displayed are configured using the Monitor/Setting Item 1 to 5 parameters.
  • Page 331 Parameter Functions & Definitions 5-103 spdp PV/SP Display Screen Selection Conditions of Use: The No. 3 display must be supported (900-TC8) Function: This parameter allows you to configure what will be displayed on the PV/SP Screen No. display and the order of the display. The default is 4. Note: A 2- level display is set at the time of shipping from the factory (set value = 0).
  • Page 332 5-104 Parameter Functions & Definitions Function: This parameter allows you to select the MV display for PV/SP/MV during heating and cooling control. Either heating MV or cooling MV can be selected. Table 5.EA Selections Default o: MV (heating) c-o: MV (cooling) pvdp PV Decimal Point Display Conditions of Use: The input type must be set to temperature input.
  • Page 333 Parameter Functions & Definitions 5-105 pvst PV Status Display Function Function: The PV in the No. 1 display for the PV/SP, PV, or PV/Manual MV Screen is alternately displayed in 0.5-second cycles with the control and alarm status specified for the PV status display function. Table 5.EC Selections Default...
  • Page 334 5-106 Parameter Functions & Definitions svst SV Status Display Function Function: The SP, Blank, or Manual MV in the No. 2 display for the PV/SP, PV, or PV/Manual MV Screen is alternately displayed in 0.5-second cycles with the control and alarm status specified for the SV status display function. Table 5.ED Selections Default...
  • Page 335 Parameter Functions & Definitions 5-107 ra 1m Control Output 1 ON/OFF Count Monitor Conditions of Use: Control output 1 must be supported. Relay or voltage outputs (for driving SSR) must be used. The Control Output 1 ON/OFF Count Alarm Set Value parameter must NOT be set to 0. Function: This parameter monitors the number of times that control output 1 is turned ON and OFF.
  • Page 336 5-108 Parameter Functions & Definitions count alarms to auxiliary outputs and to have them displayed on the screen. This function is disabled when the set value is 0. Table 5.EH Configurable Range Units Default 0 to 9999 100 times Related Parameter Control output 1 ON/OFF count monitor (Advanced Setting function group, page 5-107) Control Output 2 ON/OFF Count Alarm Set...
  • Page 337 Parameter Functions & Definitions 5-109 Function: This parameter resets the ON/OFF counter for specified control outputs. Table 5.EJ Selections Default 0: Disable the counter reset function 1: Reset the control output 1 ON/OFF counter 2: Reset the control output 2 ON/OFF counter Note: After the counter has been reset, the count value will be automatically returned to 0.
  • Page 338 5-110 Parameter Functions & Definitions Figure 5.14 Power ON Started in automatic mode. Operation Function Group Press the for less than 1 second. Press the Key for at least Press the 1 second. The display will flash. for at least 1 second. Press the for at least 3 seconds.
  • Page 339 Parameter Functions & Definitions 5-111 Note: Each parameter is enabled when the controller power is reset. Table 5.EK Parameter Symbol Selection or Configurable Values Settings Default psel Protocol Setting cwf, mod 900-TC or Modbus u-no Communications Unit No. 0…99 0…99 Communications Baud Rate 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, or 57.6 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, or...
  • Page 340 5-112 Parameter Functions & Definitions Notes: Publication 900-UM007D-EN-E - January 2011...
  • Page 341 Chapter Troubleshooting & Error Indication Error Displays When an error occurs, the error contents are shown on the controller’s No. 1 or No. 2 display. This section describes how to check error codes on the display, and the actions to be taken to remedy the problems. s.err Input Error Meaning...
  • Page 342 Troubleshooting & Error Indication Operation at Error • After an error occurs, the error is displayed and the alarm output functions as if the Upper-Limit has been exceeded. • If you configure the Input Error Output parameter in the Advanced Setting function group to ON, the Alarm 1 output turns ON whenever an input error occurs.
  • Page 343 Troubleshooting & Error Indication Figure 6.1 Resistance Thermometer Input Resistance Thermometer Input (Except for models with a setting range of −199.9 to 500.0 °C) (Except for models with a setting range of −199.9 to 500.0 °C) Thermocouple Input Thermocouple Input (Except for models with a setting range of −199.9 to 400.0 °C) (Except for models with a setting range of −199.9 to 400.0 °C) Control range...
  • Page 344 Troubleshooting & Error Indication e111 Memory Error Meaning The controller’s internal memory operation is in error. Action First, turn the controller power OFF then back ON again. If the display remains the same, the Controller must be repaired. If the display is restored, then the probable cause is electrical noise affecting the control system.
  • Page 345 Troubleshooting & Error Indication Heater Burnout Alarm (HBA) Heater Short Alarm (HSA) lcr1 Heater Overcurrent lcr2 Meaning When a Heater Burnout (HBA), a Heater Short Alarm (HSA) or Heater Overcurrent occurs, the No. 1 display in the applicable function group flashes. Action When either HBA, HSA, or Heater Overcurrent is detected, the HA indicator lights and the No.
  • Page 346 Troubleshooting & Error Indication Timing Status Meaning Countermeasures Page During operation Overshooting ON/OFF control is Select PID control and execute either ST 3-30 Undershooting enabled (default: (self-tuning) or AT (Auto-Tuning). Hunting ON/OFF control When using self-tuning, turn ON the power selected).
  • Page 347 Troubleshooting & Error Indication Timing Status Meaning Countermeasures Page During operation Temperature error is Thermometer has burnt Check whether the thermometer has burnt out or — (Continued) large out or short-circuited. short-circuited Input error (S.err Thermometer lead Wire the lead wires and power lines in separate —...
  • Page 348 Troubleshooting & Error Indication Symptom: Cannot Communicate or a Communications Error Occurs Table 6.B Meaning Countermeasures The communications wiring is not correct Correct the Wiring The communications line has become disconnected Connect the communications line securely and tighten the screws. The communications cable is broken.
  • Page 349 Troubleshooting & Error Indication Table 6.B Meaning Countermeasures The host device sent another command The response must always be read after sending a command (except for before receiving a response from the Controller. broadcast commands). The host device sent the next command too After receiving a response, wait at least 2 ms before sending the next soon after receiving a response from the command.
  • Page 350 6-10 Troubleshooting & Error Indication Notes: Publication 900-UM007D-EN-E - January 2011...
  • Page 351 Appendix Specifications For the setting ranges for each sensor input, refer to page A-9. Table A.A Technical/Control Supply Voltage 100…240V AC, 50/60 Hz 24V AC, 50/60 Hz/24V DC Operating Voltage Range 85 to 110% of rated supply voltage Power Consumption 900-TC16 7.5 VA 5 VA/3 W...
  • Page 352 Table A.A (Continued) Technical/Control (Continued) 900-TC16 Output voltage 12V DC ±15% (PNP), max. load current 21 mA, with Control Output Voltage Output (Continued) over-current protection circuit 900-TC8 Series B: Output voltage 12V DC +15%/−20% (PNP), max. load current 40 mA, with over-current protection circuit Series B: Voltage Control Output 2: 12V DC +15%/−20% (PNP), max.
  • Page 353 Table A.A (Continued) Technical/Control (Continued) Indication Accuracy Thermocouple (±0.3% of indication value or ±1 °C, whichever is greater) ±1 digit max. (ambient temperature of 23°C) Platinum resistance thermometer: (±0.2% of indication value or ± 0.8 °C, whichever is greater) ±1 digit max. Analog input: ±0.2% FS ±1 digit max.
  • Page 354 Table A.A (Continued) General/Environmental (Continued) Ambient Humidity Relative humidity 25…85% (no condensation) Storage Temperature –25…+65°C (with no condensation or icing) Altitude 2,000 m or less Installation Environment Installation Category II, Pollution Class 2 (IEC 61010-1 compliant) Recommended Fuse T2A, 250V AC, time lag, low shut off capacity EN 61326 Radiated Interference Electromagnetic EN 55011 Group 1, class A...
  • Page 355 Heater Burnout Alarm (HBA), Heater Short Alarm (HSA), and Heater Overcurrent Alarm Table A.B Max. Heater Current 50 Amps AC ±5% FS ±1 digit max. Input Current Readout Accuracy HBA Setting Range 0.1…49.9 Amps (0.1 Amp units) 0.0 Amps: Heater Burnout Alarm output turns OFF. 50.0 Amps: Heater Burnout Alarm output turns ON.
  • Page 356 Table A.C Item Specifications Ambient Operating 10%…80% Humidity −20…60°C (with no condensation or icing) Storage Temperature Storage Humidity 10%…80% Altitude 2,000 m max. Weight Approx. 100 g Compatible Operating Environment A personal computer that includes the following specifications is required. •...
  • Page 357 Current Transformer (CT) Specifications Table A.E Item Specifications Model 900-CT1 900-CT2 Max. Continuous Current 50 A 120 A Dielectric Strength 1000V AC (1 minute) Vibration 50 Hz 98 m/S Approximate Weight 11.5 g 50 g The maximum continuous CT detection/display current of the Bulletin 900 controller is 50 A. Approximate External Dimensions Dimensions are in millimeters.
  • Page 358 Figure A.3 — Cat. No. 900-CT2 ∅ 2.36 Publication 900-UM007D-EN-E - January 2011...
  • Page 359 Sensor Input Setting and Indication Ranges Table A.F — List of Global Temperature (GT) Input Types Input Type Specifications Value Input Setting Range Input Indication Range −200…850 (°C)/−300…1,500 (°F) Resistance Pt100 -220…870 (°C)/-340…1540 (°F) Thermometer −199.9…500.0 (°C)/−199.9…900.0 (°F) -199.9…520 (°C)/-199.9…940 (°F) 0.0…100.0 (°C)/0.0…210.0 (°F) -20.0…120 (°C)/-40…250 (°F) −199.9…500.0 (°C)/−199.9…900.0 (°F)
  • Page 360 A-10 • The default is 5 (°C/°F) for Controllers with Thermocouple/Resistance Thermometer Universal Inputs and 0 for Controllers with Analog Inputs. • The applicable standards for each of the above input ranges are as follows: • K, J, T, E, N, R, S, B: JIS C1602-1995, IEC 584-1 •...
  • Page 361 Appendix Parameter Operations List Function Groups Global Temperature input:Controllers with Thermocouple/Resistance Thermometer (RTD) and Millivolt (0…50) Inputs Analog input:Controllers with Analog (e.g., 4…20 mA, 1…5V DC, etc.) Inputs Table B.A — Operation Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Value Process Value Temperature: According to indication...
  • Page 362 Table B.B — Adjustment Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Set Value l.adj Adjustment Level Display AT Execute/Cancel OFF, AT Cancel AT-2: 100% None at-2 AT Execute AT-1: 40% AT at-1 Execute cmwt off on Communications Writing OFF, ON None Heater Current 1 Value Monitor...
  • Page 363 Table B.B — Adjustment Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Value c-db Universal input: −199.9…999.9 °C or °F ➊ Dead Band Analog input: −19.99…99.99 0.00 Manual Reset Value of-r 0.0…100.0 50.0 °C or °F ➊ Hysteresis (heating) Universal input: 0.1…999.9 Analog input: 0.01…99.99 0.10...
  • Page 364 Table B.C — Initial Setting Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Set Value in-t 0:Pt100 None Input Type Global Temperature 1:Pt100 (GT) Input 2:Pt100 3:JPt100 4:JPt100 5: K 6: K 7: J 8: J 9: T 10: T 11: E 12: L...
  • Page 365 Table B.C — Initial Setting Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Set Value sl-l −200 SP Lower-Limit Input range Lower-Limit to SP Upper-Limit − 1 (temperature) Scaling Lower-Limit to SP Upper-Limit − 1 (analog) intl onof PID ON/OFF ON/OFF 2-PID ON/OFF...
  • Page 366 Table B.C — Initial Setting Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Set Value alt1 Alarm 1 Type 0:Alarm function OFF None 1:Upper- and Lower-Limit alarm 2:Upper-limit alarm 3:Lower-limit alarm 4:Upper- and Lower-Limit range alarm 5:Upper- and Lower-Limit alarm with standby sequence 6:Upper-limit alarm with standby sequence...
  • Page 367 Table B.C — Initial Setting Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Set Value alt2 Alarm 2 Type Same settings as the alarm 1 type. None NOTE: The 12: LBA (Loop Burnout Alarm) setting cannot be used. alh2 °C or °F ➊...
  • Page 368 Table B.C — Initial Setting Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Set Value Extraction of Square OFF, ON None Root Enable amov −1999…9,999 Move to Advanced None Setting function group ➊Set “None” as the unit for analog inputs ➋Initial Setting function group ➌PRST (Program Start) can be configured even when the Program Pattern parameter is configured to OFF, but the function will be disabled.
  • Page 369 Monitor Setting Item Function Group The contents displayed vary depending on the Monitor/Setting Value 1 to 5 (Advanced Setting function group). Table B.F — Advanced Setting Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Set Value Parameter Initialization init OFF, FACT None fact...
  • Page 370 B-10 Table B.F — Advanced Setting Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Set Value off on Cold Junction OFF, ON None Compensation Method rlrv off on MB Command Logic OFF, ON None Switching colr PV Color Change Orange, Red, Green None Red to Green: When ALM1 is lit...
  • Page 371 B-11 — Table B.F — Advanced Setting Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Set Value LBA Detection Time 0…9999 Second (0: LBA function disabled) lbal °C or °F ➊ LBA Level Universal input: 0.1…999.9 Analog input: 0.01…99.99 10.00 lbab °C or °F ➊...
  • Page 372 B-12 Table B.F — Advanced Setting Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Set Value pvrp PV Rate of Change 1...999 Sampling Calculation Period period csca off on Automatic Cooling OFF, ON None Coefficient Adjustment Heater Overcurrent Use 0cu off on OFF, ON None...
  • Page 373 B-13 Table B.F — Advanced Setting Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Set Value spdp PV/Display Screen None 0: PV/SP Selection 1: PV/SP/Multi-SP, PV/SP/MV 2: PV/SP/MV, PV/SP/Multi-SP 3: PV/SP/Multi-SP 4: PV/SP/MV 5: PV/SP/Multi-SP, PV/SP/ Soak Time Remain 6: PV/SP/MV, PV/SP/Soak Time Remain 7: PV/SP/Soak Time Remain...
  • Page 374 B-14 Table B.F — Advanced Setting Function Group Parameters Characters Setting (Monitor) Value Display Default Unit Set Value Control Output 2 ON/ 0..9999 100 times OFF Count Alarm Set Value ON/OFF Counter Reset None 0: Disable the counter reset function. 1: Reset the control output 1 ON/OFF counter.
  • Page 375 B-15 Table B.H Communications Function Group Parameters Characters Setting (monitor) value Display Default Unit Set value sbit Communications Stop 1, 2 Bits prty none Communications Parity None, Even, Odd Even None even sdwt Send Data Wait Time 0…99 Publication 900-UM007D-EN-E - January 2011...
  • Page 376 B-16 Setup Function Group This diagram shows all of the function groups. To move to the advanced setting function group and calibration function group, you must enter Diagrams passwords. Some parameters are not displayed depending on the protect function group configuration and the conditions of use. Figure B.1 —...
  • Page 377 B-17 Parameter Flow This section describes the parameters configured in each level. Pressing the Key at the last parameter in each level returns to the top parameter in that level. PF Key Power ON Starting in manual mode. PF Key (See note 2.) Starting in Press the O Key for at least 3 s.
  • Page 378 B-18 Monitor/Setting Item Level (900-TC8 and 900-TC16 only) Monitor/Setting Monitor/Setting Monitor/Setting Monitor/Setting Monitor/Setting Item Display 1 Item Display 3 Item Display 4 Item Display 5 Item Display 2 Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced setting function group). Press the O Key for at least 1 s.
  • Page 379 Note: Rockwell Automation cannot ensure the results of calibration by the user. Also, factory calibration data is overwritten with the user’s settings and the factory default calibration settings cannot be returned after user calibration.
  • Page 380 Calibration Figure C.1 — Controllers with Thermocouple/Resistance Thermometer Universal Inputs Advanced Setting Function Group Moves automatically according to input type. Thermocouple or Infrared Platinum Resistance Analog Input Temperature Sensor Thermometer 0: Pt100 1: Pt100 5: K 6: K 19: K140F/60C 23:0 to 2: Pt100 7: J...
  • Page 381 Calibration Controllers with Analog Inputs (900-TC8 & 900-TC16) Figure C.2 Advanced Setting Function Group Moves automatically according to input type. Current Input Current Input Voltage Input 0: 4 to 20 mA 2: 1 to 5 V 4: 0 to 10 V 1: 0 to 20 mA 3: 0 to 5 V a 20...
  • Page 382 If, however, they must be calibrated by the user, use the parameters for calibrating temperature input and analog input. Rockwell Automation, however, cannot ensure the results of calibration by the user. Also, the factory calibration data is overwritten with the latest user calibration results.
  • Page 383 Calibration Calibrating Thermocouples Calibrate according to the type of thermocouple, thermocouple 1 group (Input Types 5, 7, 11, 12, 15), and thermocouple 2 group (Input Types 6, 8, 9, 10, 13, 14, 16, 17, 18, 19, 20, 21, 22, 24, 25). When calibrating, do not cover the bottom of the controller.
  • Page 384 Calibration Set the cold junction compensator designed for compensation of internal thermocouples to 0 C. However, make sure that internal thermocouples are disabled (tips are open). In the above figure, STV refers to a standard DC current/voltage source. Use the compensating conductor designed for the selected thermocouple.
  • Page 385 Calibration Figure C.6 — Example, Zero Controller 900-TC8 900-TC16 900-TC32 20/5/12 – 19/4/11 Leave Open Zero Controller OUTPUT INPUT Compensating conductor of currently selected thermocouple. Use the K thermocouple compensating conductor for: • E, R, S, B, W, and PLII thermocouples and •...
  • Page 386 Calibration value is outside the specified range, the Number 2 display will flash and the count value will NOT be temporarily registered. 6. Press the M key to set the Bulletin 900 Controller to the state below. Set STV to –6 mV. Allow the count value on the No. 2 display to fully stabilize, then press the D key to temporarily register the calibration setup.
  • Page 387 Calibration 10. Change the wiring as follows Figure C.13 Open in Non-connected State – Short-Circuit Zero Controller OUTPUT INPUT Compensating conductor of currently selected thermocouple. Use the K thermocouple compensating conductor for: • E, R, S, B, W, and PLII thermocouples and •...
  • Page 388 C-10 Calibration 15. Press the M key. The No. 2 display changes to the state below. Note that the data to be temporarily registered is not displayed if it is not complete. Figure C.15 16. Press the U key. The No. 2 display changes to yes. Release the key and wait 2 seconds or press the M key.
  • Page 389 Calibration C-11 3. Turn the power ON. 4. Move to the Calibration function group. This starts the 30-minute aging timer. This timer provides an approximate timer for aging. After 30 minutes, the No. 2 display changes to 0. You can advance to the next step in this procedure even if 0 is not displayed.
  • Page 390 C-12 Calibration Figure C.20 10. The calibration mode is ended by turning the controller power OFF. Calibrating Platinum This example describes how to calibrate the Bulletin 900 Controller when it is connected to a platinum resistance thermometer. Resistance Thermometers Figure C.21 900-TC8 900-TC8 Input Power Supply...
  • Page 391 Calibration C-13 Figure C.22 5. Press the M key to display the count value for each Input Type. The No. 2 display at this time displays the currently entered count value in Hexadecimal. Set the 6-dial as follows: Input Type 0: 390 Input Type 1, 2, 3 or 4: 280 Figure C.23 Input Type...
  • Page 392 C-14 Calibration 10. When the M Key is pressed, the status changes as shown to the left. The data to be temporarily registered is not displayed if it is not complete. Press the U Key. The No. 2 display changes to yes. Release the key and wait two seconds or press the M Key.
  • Page 393 Calibration C-15 Figure C.27 5. When the M key is pressed, the status changes as shown in Figure C.28. The No. 2 display at this time shows the currently entered count value in hexadecimal. Set the STV to 20 mA. Allow the count value on the No.
  • Page 394 C-16 Calibration Calibrating an Analog Voltage (e.g., 1…5V DC) Input (900-TC8 & 900-TC16) In this example, calibration is shown for a Controller with an Analog Voltage Input (Input Type 2, 3, or 4). 1. Connect the power supply. 2. Connect an STV and DMM to the voltage input terminals, as shown in the following diagram.
  • Page 395 Calibration C-17 Figure C.33 Input Type 4: Input Type 2v10 2 or 3: c7c3 b104 6. When the M key is pressed, the status changes as shown in the figure below. Set the STV to 1V. Allow the count value on the No. 2 display to fully stabilize, then press the D key to temporarily register the calibration settings.
  • Page 396 C-18 Calibration Checking Indication After calibrating input, make sure to check indication accuracy to make sure that the Bulletin 900 Controller has been correctly calibrated. Accuracy Operate the Bulletin 900 Controller in the PV/SP monitor mode. Check the indication accuracy at the Upper- and Lower-Limits and mid-point.
  • Page 397 Calibration C-19 Operation: Make sure that the cold junction compensator is at 0 C, and configured STV output to the voltage equivalent to the starting power of the value to be checked. The cold junction compensator and compensation conductor are not required when an external cold junction compensation method is used.
  • Page 398 C-20 Calibration Analog Input (900-TC & 900-TC16) Preparation: The following figures show the required device connection: Figure C.38 — Controller with a Thermocouple/Resistance Thermometer Multi-input (Analog Input) 900-TC8 900-TC8 Input Power Supply − 900-TC16 900-TC16 Input Power Supply − Figure C.39 — Current Input for a Controller with an Analog Input 900-TC8 900-TC8 Input Power Supply...
  • Page 399 Appendix Glossary Adaptive Tuning: Used to continuously monitor and optimize PID constants while the controller operates. Three tuning algorithms are used to recalculate the PID constants within 500 ms after the process value stabilizes at set point: step-response method, disturbance tuning, and hunting tuning. Anti-Reset Wind-Up (ARW): A feature of PID controllers that prevents the integral (auto-reset) circuit from operating when the temperature is outside the proportional band.
  • Page 400 Glossary Contact Output: Relay control outputs are often available in these contact forms: Form A Contact (SPST-NO): Single-pole, single-throw relays use the normally open and common contacts to switch power. The contacts close when the relay coil is energized and open when power is removed from the coil.
  • Page 401 Glossary Deviation: A departure of a controlled variable from a command such as set point. Deviation Indication: A system of indication in which a departure of a detected value from the set point is indicated. DIN (Deutsches Institut für Normung): A German standards agency that sets world-recognized engineering and industrial standards.
  • Page 402 Glossary Fuzzy Logic: A rule-based control algorithm that enables control devices to make subjective judgments in a way similar to human decision-making. Within a process controller, fuzzy logic uses some basic information about the system, which is input by the user, to emulate the way an expert operator who was manually controlling the system would react to a process up set.
  • Page 403 Glossary Loop Break Alarm: This alarm indicates a problem in the control loop, e.g., a sensor has become disconnected or a problem has developed with the final control element. Manipulated Variable: The final output percentage (0 100%) that will be sent to a control element.
  • Page 404 Glossary Process Variable: The parameter that is controlled or measured, such as temperature, relative humidity, flow, and pressure. Proportional Band: The range of temperature in which a manipulated variable is proportionate to any deviation from the set point. Proportional Control Action (P): A control action in which the manipulated variable is proportionate to any deviation from the set point.
  • Page 405 Glossary Serial Communications: A method of transmitting information between devices by sending all bits serially over a communication channel. RS-232 is used for point-to-point connections of a single device, usually over a short distance. RS-485 communicates with multiple devices on a single, common cable over longer distances.
  • Page 406 Glossary Notes: Publication 900-UM007D-EN-E - January 2011...
  • Page 407 Index Numerics Communications function......3-8 setting level........3-6 2PID control parameter operation list .
  • Page 408 switching between auto and manual ....4-23, 4-53 manual control level ....... 3-5 HB Error (error display) .
  • Page 409 Precautions, Safety ....... . 1-3 password ........4-36 Program end .
  • Page 410 Back Cover Publication 900-UM007D-EN-E - January 20112 Supersedes Publication 900-UM007C-EN-D - October 2008 © 2011 Rockwell International Corporation. Printed in the U.S.A.

This manual is also suitable for:

Allen-bradley 900-tc16Allen-bradley 900-tc32

Table of Contents