Download Print this page

Global GFE-CH Series Installation Wiring Diagram

Rate of rise with fixed temperature detector

Advertisement

Quick Links

TYPICAL WIRING DIAGRAM
Figure 1(a) shows the typical wiring diagram of the
2-wire heat detector when connected to a Fire alarm
control panel.
FIRST DETECTOR BASE
+
INITIATING
LOOP
-
-
+
5
2
EN54 LISTED
COMPATIBLE
CONTROL
6
1
3 4
PANEL
REMOTE
INDICATOR
CLASS A OPTIONAL WIRING
NOTE: IF REMOTE INDICATOR IS NOT USED. POLARITY TO DETECTOR MAY BE REVERSED.
Figure 1(b) shows the typical wiring diagram of the
4-wire heat detector (separate power & relay wiring).
WARNING
TO
PREVENT
DETECTOR
SUBSEQUENT
WARRANTY
DETECTOR MUST REMAIN COVERED UNTIL THE AREA
IS CLEAN AND DUST FREE.
INSTALLING THE BASE
1. To insure proper installation of the detector head to the
base, all the wires should be properly dressed at
installation:
(A) Position all the wires flat against terminals.
(B) Fasten the wires away from connector terminals.
2. If you use a jumper wire to connect the two poles of
terminals 2 and 5 when testing the detector loop
continuity, be sure to remove the jumper wire prior to
the installation of the detector head.
3. The end-of-line device shown in fig. 1(a) and 1(b)
should be compatible with the control unit. The
end-of-line supervisory relay used should be rated for
the DC power voltage used.
4. Open area detectors are intended for mounting on a
ceiling
or
a
wall
requirements.
5. The base of the detector can be mounted directly onto
an electrical junction box such as an octagonal (75mm,
90mm or 100mm), a round (75mm), or a square
(100mm) box without using any type of mechanical
adapter.
INSTALLING THE HEAD
1. Align the components as shown in Figure 2.
2. Mate the detector head onto the base and twist
clockwise to secure it.
EOL
LAST DETECTOR BASE
RESISTOR
-
+
2
5
6
1
3
4
CONTAMINATION
invalidation,
in
accordance
with
Local
GFE-CH Rate of Rise with Fixed Temperature Detector
Installation Wiring Diagram
3.
Do not install the detector head until the area is
thoroughly cleaned of construction debris, dusts, etc.
The maximum number of detectors that can be
connected to the same detection zone is typically
30.(see panel installation instructions)
RECTANGULAR
OPENING HERE
LONG ALIGNMENT MARK
Fig. 2 Fitting detector head to base
ADJUSTING THE RELAY FOR NO/NC Operation
The normal condition for the relay is "normally open"
(NO).
1. To adjust the normal condition of the relay to
"normally closed" (NC), insert a screwdriver into the
rectangular hole located on the side between the front
cover and base and rotate to remove the front cover.
2. Refer to figure 3. There is a jumper head next to the
relay on the PCB. Remove the jumper head and reinsert
it in the NC position.
3. Carefully replace the front cover.
Relay contact rating:
1A@30VDC,
AND
0.5A@125VAC
THE
HEAT SENSOR
LED
TESTING
TESTING
All remote signaling systems, releasing devices and extinguishing
systems should be disconnected during the test period and reconnected
at the conclusion of testing.
2. After energizing the detector head for approximately
one minute, check to see the indicator red LED
flashing once every 4-6 seconds. If red LED fails to
flash, it indicates the non-functioning of the detector or
faulty wiring. Re-check the wiring or replace the
detector if necessary.
3. The detector to be tested should be subject to a flow of
warm air at a temperature of between 65°C and 80°C.
(This requirement can be met by some domestic hair
dryers).
Proceed as follows:
(1). Switch on the warm airflow and check that
HEAT SENSOR
LED
DETECTOR HEAD
BASE
SHORT ALIGNMENT MARK
.
RELAY
Fig. 3 Schematic of detector structure
When front cover is open.
Jumper for
relay
status

Advertisement

loading

Summary of Contents for Global GFE-CH Series

  • Page 1 GFE-CH Rate of Rise with Fixed Temperature Detector Installation Wiring Diagram Do not install the detector head until the area is TYPICAL WIRING DIAGRAM thoroughly cleaned of construction debris, dusts, etc. Figure 1(a) shows the typical wiring diagram of the The maximum number of detectors that can be 2-wire heat detector when connected to a Fire alarm connected to the same detection zone is typically...
  • Page 2 Global Fire Equipment Ltd. declares that this product is free from defects in material and workmanship. And it will repair or replace any product or part thereof which proves to be defective in workmanship or material for a period of 24 months from the date of purchase. Please visit the Global Fire Website for a full description of Global Fire Equipment’s LIMITED WARRANTY, which, among other things, limits the duration of warranties...

This manual is also suitable for:

Gfe-ch-2Gfe-ch-2-lGfe-ch-4-12Gfe-ch-4-24Gfe-ch-4-ar-12Gfe-ch-4-ar-24