IQUID RYSTAL ISPLAY LED I ........................11 NDICATORS ................12 ONTROL USHBUTTONS AND WITCH 4.3.1 Test Key (ZXr-A Only)....................12 ..........................13 UZZER LCD M ..................... 13 PECIAL ESSAGES SPECIFICATIONS ........................14 Table of Figures 1 - B ..............5...
• These instructions cover the operation and installation of the ZXr-A / ZXr-P Repeaters. Refer to the Fire Alarm Control Panel (FACP) Manuals for instructions on powering up, operating and programming the system.
The ZXr-P Passive Repeater will only show (repeat) the operational state of the FACP. • The ZXr-A Active Repeater will show (repeat) the operational state of the FACP and can control the FACP using the SOUND ALARMS, SILENCE / RESOUND, MUTE BUZZER, ACCEPT and SYSTEM RESET functions.
ZXr-A / ZXr-P Repeaters MORLEY-IAS Mounting the Repeater to the Wall • The ZXr repeater should be wall mounted in a position that allows clear visibility of displays and easy access to operating controls. The height above floor level should be chosen such that the LCD is just above normal eye level (approximately 1.5 metres).
Ensure correct orientation. This label is not used on the ZXr-P. • At position C, insert the MORLEY-IAS logo legend label. Ensure correct orientation. Figure 4 – Label Insert Locations Page 6 of 16 Document No.
Only terminate the repeater power cables at the FACP or external source after ALL pre- commissioning checks have been performed. Only connect power cables when the system power is OFF. • The ZXr-A / ZXr-P Repeaters must be RIBBON CABLE supplied with DC Power from an approved (INTERNAL)
MORLEY-IAS ZXr-A / ZXr-P Repeaters 3.3.2 RS485 Communications Before commencing installation of the RS485 communications wiring, check to which type of panel the repeater is to be connected. If the repeater is to be connected to a ZX Series FACP, peel off and affix the supplied re-legend label over the text on the Termination PCB (see opposite).
ZXr-A / ZXr-P Repeaters MORLEY-IAS 3.4 Address Setting • Set the repeater address in binary using the address switch on the repeater chassis assembly PCB. (See Figure 9 above). • The address can be set in the range 1 – 126.
MORLEY-IAS ZXr-A / ZXr-P Repeaters 3.5 Commissioning 3.6 Preliminary Checks • Carry out the following preliminary checks for EVERY repeater being commissioned prior to power up the system. Check that all cables brought into the repeater have been terminated correctly. All power and signal cabling and wiring must conform to the appropriate local regulation.
Fire Alarm Control Panel (FACP) and the installation. • In addition, the ZXr-A is equipped with a key operated switch and five CONTROL keys and a TEST key. • The operation of the Repeater is as follows: 4.1 Liquid Crystal Display...
MORLEY-IAS ZXr-A / ZXr-P Repeaters 4.3 Control Pushbuttons and Key Switch • The ZXr-A Repeater is equipped with five control keys for SOUND ALARMS, SILENCE / RESOUND, MUTE BUZZER, ACCEPT and System Sound Alarms SYSTEM RESET and a TEST key.
ZXr-A / ZXr-P Repeaters MORLEY-IAS • Examples of LCD during display test: |||||||||||||||||||||||||||||||||||||||| |||||||||||||||||||||||||||||||||||||||| ▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐ ▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐▐ ████████████████████████████████████████ ████████████████████████████████████████ • Example of LCD Test Display when Control Key pressed: ▐▐▐▐▐▐▐▐MMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMM MMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMMM 4.4 Buzzer • The internal buzzer will sound to indicate alarm or fault conditions as follows: FIRE ALARM –...