Function Expansion Unit FE260
Operating Manual and Installation Instructions
Operating Manual:
HW version:
FE260
73017824
from V21 / V11
(AC / DC version)
Issue:
5.4.2006 (c)
Edition:
01

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FE260 and is the answer not in the manual?

Questions and answers

Summary of Contents for Elster Instromet FE260

  • Page 1 FE260 Function Expansion Unit FE260 Operating Manual and Installation Instructions Operating Manual: 73017824 Issue: 5.4.2006 (c) Edition: HW version: from V21 / V11 (AC / DC version)
  • Page 2 Function Expansion Unit FE260 All rights reserved. Copyright © 2006 Elster-Instromet GmbH, D-55252 Mainz-Kastel All the figures and descriptions in this operating and instruction manual have been compiled only after careful checking. Despite this however, the possibility of errors cannot be completely eliminated.
  • Page 3: Table Of Contents

    4.3.2 Problems during data transfer and solutions ............21 4.4 Local interfaces (optical interface and RS-232) ........... 23 4.4.1 Reading out and parameterising the volume corrector ........24 4.4.2 Parameterisation of the modem integrated into the FE260......... 24 4.4.3 Test mode......................24 A Approvals ........................25 A-1 EC Declaration of Conformance..............
  • Page 4: I Safety Information

    Function Expansion Unit FE260 Safety information Before mounting, installing or putting the FE260 into operation, this operating manual must be carefully read to avoid damage, hazards and problems. Mounting and installation should only be carried out by specialist personnel. The "...
  • Page 5: Items Supplied And Accessories

    Operating Manual II-2 Ordering information and accessories FE260 Order no. • Function Expansion Unit FE260, complete (incl. accessories)....83 480 540 Accessories • Operating manual, English..............73 017 824 • Operating manual, German..............73 017 464 Options • Standard modem 14,400 baud..............73 016 757 incl.
  • Page 6: Brief Description

    Function Expansion Unit FE260 1 Brief description The Function Expansion Unit FE260 is used for expanding the functions of a volume corrector in the LIS-200 range, such as for example the EK260 from software version 2.02. In the current level of expansion it fulfils the following tasks: Intrinsically safe power supply for the volume corrector.
  • Page 7 (4 x) (4 x) Electrical Intrinsically isolation safe circuits Fig. 2: Block diagram of FE260, "DC" version. Two signalling lamps fitted to the cover indicate the following states: “Power”: The device is ready for operation. • “Online”: Data transmission is running via the installed or connected modem. Data •...
  • Page 8: Mounting

    Function Expansion Unit FE260 2 Mounting The holes for wall mounting become accessible after opening the housing cover of the FE260. The dimensions, drilling template and diameter of the mounting holes can be taken from Fig. 3 and Fig. 4.
  • Page 9 As “associated electrical equipment”, the FE260 cannot be installed in Zone 1. (See [DIN] EN 60079-10 and [DIN) EN 60079-14.) For versions of the FE260 with a GSM modem, the supplied antenna must be mounted, e.g. on the wall. A mounting bracket is provided in the supplied items for this.
  • Page 10: Installation

    3.1.2 "DC" version (for direct voltage of 10 to 30 V) The "DC" version of the FE260 is suitable for a direct-voltage power supply in the range from 10 to 30 V. It can be operated, for example, with nominal voltages of 12 V or 24 V.
  • Page 11: Screening And Earthing

    A1 to A4 have a screen which must be earthed at both ends to prevent interference due to high frequency electromagnetic fields.. The screen must be connected all round, complete and flat. The FE260, similar to the volume corrector (e.g. EK260) to be connected, has special metallic EMC cable glands for this.
  • Page 12: Cables And Cable Lengths

    , offer the possibility of operating Output 2 as a high frequency output at up to 500 Hz. The connection “DA2” on the FE260 is specially rated for this. Consequently, the above mentioned degradation of the signal (see *3) is substantially less here.
  • Page 13: Terminal Layout

    Cable 2 On the EK260 the terminals “R+”, “R-“, “T+” and “T-“ are also labelled with “CS”, “RD”, “RS” and “TD”. When connecting the FE260, these designations have no significance. The terminals “Ri” and “Gnd” on the EK260 remain unconnected.
  • Page 14: Digital Outputs A1 To A4

    “Technical Data”. 3.5 Modem On request, the FE260 can be fitted with an integral modem or a connection for a separate modem in order to read out the data from the connected volume corrector by remote data transmission.
  • Page 15: Integral Gsm Modem

    Only use the top centre plastic gland for the antenna cable so that the point of connection does not form a short circuit to the earthed housing. Then the antenna cable is connected to the modem within the FE260 using the short cable.
  • Page 16: Connection Of A Separate Modem

    For the connection of a CL modem: refer to Chapter 3.5.4, page 17. If the FE260 is implemented with a connection for a separate modem, you can connect a commercially available modem to it to read out the volume corrector by remote data transmission.
  • Page 17: Connection Of A Cl Modem

    CL modem and also on the connected devices: The sum of the voltage (in volts) required by the connected devices must not be greater than the driver rating of the CL modem. The CL interface of the FE260 requires 3 V. Wiring diagram:...
  • Page 18: Initial Operation

    • Once all cables are connected and the housing firmly closed, switch on the FE260 power supply (mains voltage for the "AC" versions). • Check the “Power” signal lamp on the cover of the FE260. A continuous green signal indicates that the FE260 power supply is functioning correctly.
  • Page 19: Digital Outputs

    • Position "non-inv." The signals are not inverted (standard setting). • Position "inv." The signals are inverted. "Inverted" signifies that the FE260 output is switched through (conducts) when the volume corrector output blocks and vice versa. Elster-Instromet GmbH...
  • Page 20: Modem

    FE260 with the option "Local interfaces" or "CL interface"). *2) 19200 Bd is standard. With longer lengths of cable between the FE260 and the volume corrector (refer to Chapter 0, page 12) and when using the option "Local interfaces" or "CL interface", the baud rate may be set to a maximum of 9600 Bd.
  • Page 21: Cl Modem

    These volume correctors can be operated without restriction. If other bus devices are connected to the CL modem as well as the FE260, you must assign an unambiguous bus address to the volume corrector. This address is used by the calling software to select a device.
  • Page 22 → The modem must be suitably parameterised for the parameter "Md.S2" in the volume corrector: With "Md.S2 = 5" the modem accepts calls automatically, with "Md.S2 = 3" it does not. If the FE260 is fitted with the option "Local interfaces" or "CL interface", the modem must accept the calls automatically.
  • Page 23: Local Interfaces (Optical Interface And Rs-232)

    (No call acceptance by the volume corrector, setting Md.S2 = 5). • When using an FE260 with optical interface, operation occurs with a baud rate of 9600 Bd. On the volume corrector, apart from the displayed baud rate "Bd.S2", the so- called "Identification baud rate"...
  • Page 24: Reading Out And Parameterising The Volume Corrector

    4.4.2 Parameterisation of the modem integrated into the FE260 When the switch S2 is set to "Modem par.", the modem integrated into the FE260 can be parameterised with the aid of a PC or laptop. The serial interface of the PC or laptop is in this respect connected to the optical interface or to the DSUB-9 connector.
  • Page 25: A Approvals

    Function Expansion Unit FE260 Approvals A-1 EC Declaration of Conformance Elster-Instromet GmbH...
  • Page 26: Approval As Associated Operating Equipment

    Function Expansion Unit FE260 A-2 Approval as associated operating equipment Elster-Instromet GmbH...
  • Page 27 Function Expansion Unit FE260 Elster-Instromet GmbH...
  • Page 28 Function Expansion Unit FE260 Elster-Instromet GmbH...
  • Page 29 Function Expansion Unit FE260 Elster-Instromet GmbH...
  • Page 30: Declaration Of Conformance For Use In Areas Subject To Explosion Hazards, Zone 2

    Function Expansion Unit FE260 A-3 Declaration of conformance for use in areas subject to explosion hazards, Zone 2 Elster-Instromet GmbH...
  • Page 31: B Technical Data

    Function Expansion Unit FE260 Technical data B-1 General data (mechanical and ambient conditions) Housing/structure ....Wall-mounted housing, Aluminium cast alloy G AI SI 12 / DIN 1775 Dimensions (W x H x T) ..approx. 290 x 175 x 102 mm with cable entry glands and hinges Cable union glands ....
  • Page 32: Intrinsically Safe Power Supply For The Volume Corrector

    Function Expansion Unit FE260 B-3 Intrinsically safe power supply for the volume corrector Also suitable for supplying the EK260 volume corrector. Designation ......“U” Cable connection ....Screw terminals, blue Cable cross-sectional area ... 0.5...1.5 mm² Fit wire-end sleeves to flexible stranded wires...
  • Page 33: Serial Data Interface To The Volume Corrector

    500 Hz max. for cable length up to 10 m * and 40 to 50 mA switching current ** * With a cable length of more than 10 m between the FE260 and the volume corrector (intrinsically safe electrical circuit) the maximum frequency cannot be guaranteed. (See B-4 and Chapter 0).