INSTRUCTION MANUAL
VALVE POSITIONER
(for Modbus; built-in SSR)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Valve positioner (body + base socket) .................................(1)
Terminating resistor (110 Ω, 0.25 W) .................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• This equipment is suitable for Pollution Degree 2, Instal-
lation Category II (transient voltage 2500V) and Meas-
urement Category II (control output, transient voltage
2500V). Reinforced insulation (Modbus or control out-
put or feedback resistance to power: 300V and Modbus
or feedback resistance to control output: 250V) is main-
tained. Prior to installation, check that the insulation
class of this unit satisfies the system requirements.
• The equipment must be mounted inside a suitable fire
enclosure.
• Altitude up to 2000 meters.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements. Failure to observe these re-
quirements may invalidate the CE conformance.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODEL
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V, 50/60 Hz,
approx, 1.5VA at 100V AC
approx, 4VA at 200V AC
approx, 6VA at 264V AC
100 – 240V DC rating: 85 – 264V, approx, 1W
■ GENERAL PRECAUTIONS
• Before you remove the unit from its base socket or mount
it, turn off the power supply and power to a motor for
safety.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +60°C
(23 to 140°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
MEXM
EM-4610 Rev.1 P. 1 / 5

Advertisement

loading

Summary of Contents for M-system MEXM

  • Page 1 • Locate the power input rating marked on the product and confirm its operational range as indicated below: Thank you for choosing M-System. Before use, please check 100 – 240V AC rating: 85 – 264V, 50/60 Hz, contents of the package you received as outlined below.
  • Page 2: Component Identification

    0 – 3; 4 – 9 are unused. 0: 38.4 kbps (factory setting) 1: 19.2 kbps 2: 9600 bps 3: 4800 bps EM-4610 Rev.1 P. 2 / 5 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 3: Terminal Connections

    Tx–/Rx+ Rx– Connect terminating resistor between DA and DB of both ends of the unit. Connect the attached terminating resistor to the MEXM. Master unit is connectable also at both ends or other points. EM-4610 Rev.1 P. 3 / 5 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 4: Manual Operation

    Modbus, be sure to turn off the manual operation deadband range. switch. Also turning both (open and close) switches on, both will be out of function. EM-4610 Rev.1 P. 4 / 5 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 5: Modbus Settings

    “0.” “0” is read when there is no other assignation; it is not writable. LIGHTNING SURGE PROTECTION M-System offers a series of lightning surge protector for protection against induced lightning surges. Please contact M-System to choose appropriate models.