IP POWER 9212 USER MANUAL USER MANUAL IP POWER 9212Delux Version: V1.00 2006.12 - 1 - VER. X.X,...
Page 3
IMPORTANT NOTICE 1. IP POWER 9212 Delux is deigned to be used in-door, we have no responsibility for the possible damage in out-door use especially in the rain.。. 2. Please use the power adaptor provided by the dealer, we have no responsibility for the possible damage in using other adaptors.
1. Introduction The IP Power 9212SDelux is a Network Controller & Sensor with 8 DI & 8 DO. A specific PC or software is not needed; you can easily control devices remotely and check the device status via the Internet anywhere in the world.
Industrial application field: bank, financial security system, jewels, casino, cash register in supermarket, park, traffic control, military equipment and airport. 2. Before you start 9212 package contents One set of IP POWER 9212 One network wire with RJ45 port One 1A, 110~220V adaptor TWO D-Sub 15 Pin cable...
9201 is the input /sensor module and 9202 is the output / control module 4. Hardware & Software installation Before you star to use IP Power 9212, please follow the steps below: Check the package to make sure the contents is complete.
Page 8
IP POWER 9212 USER MANUAL 9201Pro Hardware connection (recommend): 4-1. Dry & Wet Setting In 9212Delux, the DRY or WET contact of each input ( in 9201) can be switch. To setup the Dry or Wet contact of each input signal , please open 9201 case and adjust the two blue SWITCHs There is two blue switch in 9201.
Page 9
Then you can setup the Dry/Wet contact in left switch : As no contact with the Input , Switch set as ON : LED light ON & means the input is Dry contact , Switch set as OFF : LED light is OFF which means the input is Wet contact For example: the left switch setup input 1~4 is OFF &...
Page 10
IP POWER 9212 USER MANUAL 4-2 . Connection Illustration: For different request of normal state of electric equipment, 9201 offers four sets of voltage signal IN1-IN4 and four sets of shortcut circuit signals IN5-IN8. 9201 Pro provide 4set Source mode - Voltage Input – Out 1 ~ Out 4...
Page 11
3. Sink mode ( Resistance signal ) —IN5 & IN8: can be connected to magnetic reed switch as the follow figures It can be installed in the entrance guard or security equipment such as doors, windows, drawers and safe case.. Source mode ( Voltage input) : IN1-IN4 contacts are active signal sensor.
Page 12
Most of them are used in security equipment, living product and automatic mechanism. 9202 Pro Hardware connection (recommend) IP Power 9202 Pro offers 4 sets of NC(Normal Close ) – Out 1- Out 4 4 sets of NO (Normal Open ) –Out 5- Out 8. Maximum Rated Voltage: 240V/AC, 60V/DC...
Page 13
Step 2: Use a test pencil or screwdriver with voltage tester to identify the live wire between the two wires of electrical wire. Cut off the live wire and connect to the port of IP Power 9212. Use the test pencil or screwdriver with voltage tester again to make sure the connection is correct.
IP POWER 9212 USER MANUAL 3. You an control multi power by use the power extension cord NOTICE: Do not connect too much energy intensive electrical equipment such as air conditioner, electrical heater, microwave over or over in the same electrical outlet.
IPEDIT will searching all IP Products 9XXX series in the same local Ethernet, the default name of 9212Delux is IP Power, and display the information as select 1. Double click the IP address, it will be covered by dark stripe, its name, and IP will be displayed below.
Page 16
* Same SEGMENT : The first 3 number of IP address is same - XXX.XXX.XXX.abc. The part of XXX is same. Fro Example : IP address is 192.168.1.100 , then another IP address 192.168.1.123 is the IP in same segment . 4. The default username and password of IP Power 9212 are: Username: admin Password: 12345678 If forget the new password , you can key in superuser in username , and hardware reset the device to set the default setting Password : 12345678 。( for security concern) ).
Page 17
Internet online devices: By setting the server address in IP server of advanced setup page, user can easily to get the IP address of IP Power 9212Delux on internet by name searching. The default IP address of IP server is 220.135.169.136.
Web Control page. Username: admin / Password: 12345678 Sensor of IP Power 9212: Read IO Source mode (Voltage input): IN1-IN4 contacts are active signal sensor. If the voltage difference between the two contacts in one set within 0V~3V, 9212 shows ON. It the voltage difference within 4V~24V, 9212 shows OFF.
Page 19
(there may be some delay, it up to your network). Control of IP Power 9212: SET IO IP Power 9212 now can control 8 outputs at the same time. * Out1 & Out4 are normal close switches. When it is on, the corresponding LED lights up, the circuit between the two connects is turnoff.
Gateway, DNS. If you choose to use DHCP, please make sure that your network support DHCP service so the IP Power 9212 will search and gain an IP address automatically when it starts. You can also control the Beeper sound.
Page 21
IP address in order to let the other computers can visit the 9212 Delux. Now type the new IP address in the address field of IE, you can visit the 9212 Delux. You also can use the ipedit.exe to find the IP Power 9212 and modify its IP address.
Page 22
IP POWER 9212 USER MANUAL Advanced Setup: 2. IP Server: Register 9212Delux in our IP Server then user can easily get online IP address by “Name “search. Please refer page16 for this function. To use the internal control function which we are going to introduce in following page, please set all the pin on left switch to OFF and the light on DI will be all off.
Page 23
2. As LO in either one each channel, 9212 Delux will ask the setting IP (9060A) take pictures. You can also use the P5 area bottom of 9201 (of 9212Delux) to control the LO. As enable the function, as the DI status change, 9212A will take pictures.
Page 24
IP POWER 9212 USER MANUAL 4. As LO in either one DI, 9212Delux will send E-mail to advice the certain input status change. You can use the P5 area bottom of 9201 (of 9212Delux) to control the LO. 5. User can Auto control the DO of 9212Delux by DI status change One DI can control 1~ 8 DO.
In output area: * Enable: The DO light turn on * Disable: The DO light turns off. Note: Channel 1- 4 is NC, Channel 5- 8 is No, DO “ Light on” means status change. DDNS Setting: DDNS Server Settings: when your network connects to the Internet through ADSL, the IP address you gain is dynamic assigned by your ISP.
Page 26
8. PROXY PORT: Please fill in the proxy port here. E-Mail setting: receive IP address & inform as Sensor trigger IP Power can setup the e-mail address for receive change from sensor part. As setting up the receiver e-mail address, IP Power will send its IP Address to receiver.
Page 27
5.) Receiver: no longer than 50 English letters. Please use blank space to separate two Receiver’s e-mail address. After you have finished this setting, you will receive the email to inform you the IP address of the IP Power 9212 every time you enter the webpage.
IP POWER 9212 USER MANUAL Setting the password for IP Power 9212 Click the change password option at the left window and you can enter the change password page. Follow the instructions, fill in the old password and new password, then click the apply button to confirm.
If user wishes to control the power in one outlet of IP Power 9212, you can fill in the time in the power control column and choose on or off. Support parameter of operate schedule: * Disable / Just Once / every day * Work Day: every Monday to Friday.
Page 30
IP POWER 9212 USER MANUAL Note: 1. If the Network card is not onboard card, it needs to connect with your Main board by cable. Please refer your network card connection 2. You can get your MAC address in PC, please refer following pictures:...
If no firmware to update please do not go to this page. As received new firmware, user can gain more functions for IP Power 9212 through firmware update. Click the firmware update on the right side of the page; the following window will pop up.
1)If the Port is 80 then you can directly update。 2) If update fail ,you can manual reset the device and update again . 7. Setting the 9212 Delux through the Internet After you have setting the Ethernet and router, you can access the IP Sensor 9212 from the Internet.
8. Associated with other IP network product You can associate the IP Power 9212 with other IP network product of OUR in your home Ethernet, such as IP Kamera 9000 network camera, IP Video 9100 network video server and IP Sensor 9201, IP POWER 9202E to monitor the equipments or sensors installed in the doors or windows.
Example 1: control the power supply of 9212: http://admin:12345678@192.168.1.10 /Set.cmd?CMD=SetPower+ P60=1+P61=1+P62=1+P63=0 This command control IP Power 9212 IP address at 192.168.1.0, user name is admin and password is 12345678. This order will: turn on the power of outlet1 (p60); turn on the power of outlet2 (p61), turn on the power of outlet3 (p62);...
Page 35
out1 set parameter as 0 (output1 disconnect relay )or 1(output1 connect relay) out2-out4 same as out1 2. GetPower: to read I/O parameter - read parameter as follow out1 if parameter reply as 0 (output1 disconnect relay)or 1(output1 connect relay) out2-out4 same as out1 http:// /admin:1234567@ 192.168.1.100/Set.cmd?CMD=GetPower the above command control 9212 IP address as 192.168.1.10,...
Page 36
Example 1: control power on / off of 9212: http:// /admin:12345678@192.168.1.10/Set.cmd? CMD=SetSchedule+Power=1A+YY=2006+MM=02+DD=16+HH=06+MN=02+SS=16+PARA M=128+ONOFF=1 Above command control one IP Power 9212 IP address at 192.168.1.0, user name is admin and password is 12345678. This 9212 will connect relay1 (p60) on 2006/2/16 06:02 。 4. ReadPower Read P6 ( relay status) http://xxx/Set.cmd?cmd=getpower...
11. Webpage Customization Customer can use our Web page SDK to amend the word and background pictures for your 9212. If not familiar to write webpage, please do not do this amendment. Important Notice: 1. Each file does not over the original file size. 1.
Page 38
IP POWER 9212 USER MANUAL Step 3. Amend web page by HTML langrage (get from right click as in amend web page”): Step 4: Save file format as “UNIX”: Like choose “DOS to UNIX Step 5. After amend the other 9212 web page you plan to amend. Please open program “Make9212Html “...
Page 39
Step 6. There will be a new file “ Update_2006-01-11.bin” which is the BIN file include the amend web page. Please follow 9212-update procedure to update the firmware BIN file. Please note the Update procedure must be done in port 80. Note: program “Make9212Html.exe “...
Page 40
IP POWER 9212 USER MANUAL Set the “Bits per second” as 19200 at COM1 (Must at COM1) 4. Then power ON 9212 you will get message in Hyper Terminal. Please check the message and get your IP address. - 39 -...
Page 41
6. Use this IP address to update again. We supply original firmware V1.22 for update f 7. Log in this address to update again. 8. If still cannot finish update successful, please check if create BIN file too big. If need to ship BIN file, please use bin file V1.22.bin in SDK to update back to factory version.