1. Overview This manual is for both the AL205R and AL205B modems. The AL205R (repeater) is a component of an ALERT2 system consisting of LoggerNet ALERT2 Admin, AL205B (base), and AL200 (encoder) or AL205E (encoder). The AL205R can be configured to support repeating of ALERT2 messages and as a backup base and decoder of received ALERT2 messages.
USB flash drive is also used to install a firmware update. GPS antenna must be connected for proper time sync. GPS is required for the AL205R. NTP can be used instead of GPS in a AL205B, but time will be less accurate due to NTP jitter.
AL205R/AL205B suitable for use with a small (5 W or 10 W) solar panel. The AL205R/AL205B can monitor the input voltage level and include it in its regular status reports. 1.3 Status LEDs The following table describes the LED functions.
ASCII format (N, P, S, C messages); ships with at least 8 GB USD card LEDs: Power, Bit Sync, Frame Sync, GPS On, Clock Sync, Tx Radio Power, Transmit, Serial 1, Serial 2, Serial 3 AL205R / AL205B ALERT2 Repeater / Base...
A2Control are provided on the product webpages (www.campbellsci.com/al205r or www.campbellsci.com/al205b). 1. Connect your computer to the console port on the AL205R/AL205B using a USB cable. 2. Apply power to the AL205R/AL205B. 3. Launch A2Control. The following warning is displayed if the versions do not match.
Page 8
When A2Control begins communicating with the AL205R/AL205B, it will display the firmware type and version, and, if the AL205R/AL205B is connected to the network, the device IP address. NOTE: A2Control also can connect to the AL205R/AL205B remotely using TCP/IP by choosing network connection in the serial port drop down menu instead of a port number.
Page 9
Range is 0 to length of the frame minus the slot length. Default is 0. TDMA Slot Offset Settings AL205R / AL205B ALERT2 Repeater / Base...
Page 10
Configure serial ports for API or Concentration input, Input/Output Port ASCII/Binary/No output. Mode Settings 6. When changes are complete, click Write To Device to save them. Settings may also be loaded or saved to a local file. AL205R / AL205B ALERT2 Repeater / Base...
The AL205R/AL205B receives and decodes ALERT2 data when powered. When the AL205R/AL205B finds a valid Bit Sync pattern in the incoming audio, it turns on the Bit Sync LED and begins listening for a valid Frame Sync pattern (which should immediately follow the Bit Sync).
FIGURE 3-1. Messages displayed on A2Control 3.3 Pass reject list The AL205R repeater firmware supports up to two different pass or reject lists for determining the messages to repeat. Before a message is repeated, it is checked against all active address lists.
2. Connect the AL205R/AL205B to power. 3. Insert the USB thumb drive into the USB port of the AL205R/AL205B. 4. Wait more than two minutes for the AL205R/AL205B to recognize the USB thumb drive and start the firmware update. The Bit Sync LED flashes rapidly while the system logs are copied from the AL205R/AL205B (see Downloading ALERT2 data (p.
Update the AL205R/AL205B remotely over a TCP/IP networks using the SFTP protocol. Campbell Scientific recommends using FileZilla as an SFTP client (https://filezilla-project.org). Remote access to the AL205R/AL205B is disabled by default. To enable it, launch A2Control software, click the gear icon, click the IP Settings tab, and set the Network Password.
USB flash drive. The AL205R/AL205B copies ALERT2 output files to that folder if it fined it. The AL205R/AL205B must be powered for at least two minutes for it to register the USB flash drive.
5.3 LoggerNet ALERT2 Administration Utility LoggerNet can access the AL205R/AL205B ALERT2 and ALERT concentration data by using the LoggerNet ALERT2 Administration Utility in LoggerNet Admin. Usually, the AL205R/AL205B connects to the computer using TCP/IP and the LoggerNet call-back functionality, but the AL205R/AL205B can connect directly to a computer serial port.
Page 17
In the TCP Callback Port field, enter an open TCP/IP port number. TIP: Remote access to this port may require opening a port in the server firewall. Contact your IT administrator for help. AL205R / AL205B ALERT2 Repeater / Base...
Page 18
6. If using a serial port, do the following: a. Type a base name and select Serial Port for the Link Type. Click OK. b. Select the Serial Port to which the AL205R/AL205B is connected and select 115,200 for the Baud Rate.
Page 19
Click the Applybutton. ALERT2 administrator is now ready to receive data from the serial port of the AL205R/AL205B. 7. Start A2Control and connect to your AL205R/AL205B (see Configuration (p. 5)). 8. Click the gear icon to access the configuration settings.
Page 20
10. If using a serial port, do the following: a. Click the Serial Port Settings tab. b. For the serial port that the AL205R/AL205B is connected, set the Output Mode to ASCII and the Baud Rate to 115200. AL205R / AL205B ALERT2 Repeater / Base...
Click Write To Device to write the new setting to the AL205R/AL205B. 11. Return to ALERT2 Administrator and setup new ALERT2 stations and Sensor reports (see ALERT2 Administrator Help for more information). 6. Port descriptions The AL205R/AL205B has three serial ports with configurable functionality. The serial ports operate at RS-232 line levels.
Page 22
Serial port settings can be configured using the ALERT2 IND API or by using the AL205R/AL205B configuration menu. The AL205R/AL205B implements version 1.0 of the ALERT2 IND API. Default serial port settings are the following: Table 6-2: Default serial port settings...
Page 23
Table 6-4: TX pinout (from left, facing the AL205R/AL205B) Pin number Label Pin function RF data (output from the AL205R/AL205B) Ground Push to talk 12 V power (provided by the AL205R/AL205B) Channel select AL205R / AL205B ALERT2 Repeater / Base...
Page 24
See Product Details on the Ordering Information pages at www.campbellsci.com. Other manufacturer's products, that are resold by Campbell Scientific, are warranted only to the limits extended by the original manufacturer.
Page 25
Campbell Scientific office serves your country. To obtain a Returned Materials Authorization or Repair Reference number, contact your CAMPBELL SCIENTIFIC regional office. Please write the issued number clearly on the outside of the shipping container and ship as directed.
Page 26
Do not recharge, disassemble, heat above 100 °C (212 °F), solder directly to the cell, incinerate, or expose contents to water. Dispose of spent batteries properly. WHILE EVERY ATTEMPT IS MADE TO EMBODY THE HIGHEST DEGREE OF SAFETY IN ALL CAMPBELL SCIENTIFIC PRODUCTS, THE CUSTOMER ASSUMES ALL RISK FROM ANY INJURY RESULTING FROM IMPROPER INSTALLATION, USE, OR MAINTENANCE OF TRIPODS, TOWERS, OR...
Page 27
Campbell Scientific regional offices Australia France Thailand Location: Garbutt, QLD Australia Location: Vincennes, France Location: Bangkok, Thailand Phone: 61.7.4401.7700 Phone: 0033.0.1.56.45.15.20 Phone: 66.2.719.3399 Email: info@campbellsci.com.au Email: info@campbellsci.fr Email: info@campbellsci.asia Website: www.campbellsci.com.au Website: www.campbellsci.fr Website: www.campbellsci.asia Brazil Germany Location: São Paulo, SP Brazil...