Download Print this page
FFE Talentum UV/IR Test Unit Procedure

FFE Talentum UV/IR Test Unit Procedure

Advertisement

Quick Links

Talentum UV/IR Test Unit Procedure
Introduction
This note explains:
The purpose of the modification provided by the Talentum UV/IR Adaptor
The procedure for modifying the Talentum Test Unit to incorporate the Talentum UV/IR Adaptor
How to test a Detector using the Test Unit
Test Unit with Talentum UV/IR Adaptor
The Talentum Test Unit is designed to assist with performing a "flame" test without the need of a live
flame.
We have developed the Talentum UV/IR Adapter to optimise the output of the Test Unit for testing
Talentum UV/IR flame detectors only.
We strongly recommend that Test Units are modified with the adapter whenever used to test
UV/IR flame detectors, because without the modification the torch is less likely to identify a
performance issue with the flame detector.
Flame detectors for which this Test Unit is suitable:
16591 UV/IR2 Flame Detector
16521 UV/IR2 Flame Detector - Flameproof (Exd)
16531 UV/IR2 Flame Detector - Stainless Steel
16561 UV/IR2 Flame Detector - Stainless Steel, Flameproof (Exd)
The adapter works by changing the filter arrangement on the Test Unit so that it is optimised for testing
UV/IR flame detectors. Modifying the Test Unit with the adapter changes the output IR and UV
spectrum, so it closely matches a yellow flame. This subjects the Talentum detector to a test more suited
to identifying a performance issue. The output of the torch without this modification matches a blue
flame.
Health and Safety
In accordance with the Talentum User Guide, users should conduct regular maintenance and testing of
Talentum fire detection products according to the risk and environment in which the product(s) are
located. The frequency of such maintenance and test schedule should be revisited at regular intervals
to ensure that it remains appropriate.
The Talentum Test Unit is designed to assist with performing a "flame" test without the need of a live
flame. Adding our Talentum UV/IR Adapter ensures the output of the Test Unit is optimised for testing
UV/IR flame detectors.
Please note that the Test Unit does not have an (Ex) approval for hazardous areas. A permit is required
to test a detector in such areas. Alternatively, the detector should be removed and placed within a safe
location to perform the test.
Testing of a flame detector should only be conducted where it is safe to do so and by personnel with
appropriate training and equipment.
0044-112-01

Advertisement

loading

Summary of Contents for FFE Talentum UV/IR Test Unit

  • Page 1 Talentum UV/IR Test Unit Procedure Introduction This note explains: The purpose of the modification provided by the Talentum UV/IR Adaptor • The procedure for modifying the Talentum Test Unit to incorporate the Talentum UV/IR Adaptor • How to test a Detector using the Test Unit •...
  • Page 2 Talentum UV/IR Test Unit Procedure How to modify the Test Unit 1) Remove the four screws that hold on the plate and filter that cover the bulb of the Test Unit using a 2.5mm allen/hex key; 2) Remove the black cover and the blue filter behind it from the front of the torch including the four screws and washers and put them aside.
  • Page 3 Talentum UV/IR Test Unit Procedure How to test a Detector using the Test Unit To power up the unit, remove the Clip-on the base of the Test Unit, operate the power switch to ‘ON’ and the supply LED will illuminate ‘green’ if the battery has sufficient charge or flash if the battery is low.
  • Page 4 The flame detector is expected to alarm within 30 seconds. If a device is found to be insensitive to this flame sensor test, please contact your FFE account manager for support.

This manual is also suitable for:

Talentum ir test unit