DESCRIPTION:
Sensor designed to work with any power pack, to automatically control
lighting in standard and cold weather applications. This sensor utilizes
an industry leading 8-element Infrared Detector for superior minor
motion detection while combining with a lens that provides major
motion detection up to 2000 sq. ft. at a standard 9 ft. mounting height.
The sensor operates in climates down to -40° Fahrenheit or Celsius. Dual
Form C Relays are present on the sensor to allow for integration to
NexLight's 2-wire system and HVAC/BMS Systems. The sensor turns the
lights on and keeps them on while occupancy is detected and will turn
There is a daylight sensor built into the sensor to allow for ambient light
override functionality. If the ambient light level in the room is at a
this setting is used, the controlled lighting load will only turn on if the
ambient light present is less than the desired setting.
INSTALLATION:
See the back of this installation manual for installation instructions. The
sensor is fully operational after 30 seconds of powering up the device.
OPERATION OF SENSOR
Motion detection by the HDIR sensor will turn ON the lights as well as
keep them ON. When motion is not detected, the lights will turn OFF
after the delayed-OFF time.
Delayed-OFF Time: The sensor is designed to turn the lights OFF if no
black twist knob designated for timer inside the control console. Depen-
dent upon environmental conditions and occupancy patterns, the
adapting patterns will modify the delayed-OFF time to match the
parameters of each installation.
Walk-Through Mode: The walk-through feature is useful when a room is
momentarily occupied, such as a storage room. When a person enters
the room, the lights will turn on and stay on for 2.5 minutes. After 2.5
Scenario A: If motion is detected within 10 seconds of the lights shutting
Scenario B: If no motion is detected within 10 seconds of the lights
it sees detection the lights will turn on for 2.5 minutes.
Daylight Sensor: To enable daylight sensor operation, set Dip Switch 1
in Bank B to OFF. This puts the sensor in a stand-by mode when the
natural light level exceeds the selected Foot Candles (FC) level inhibiting
the lights from turning ON.
LED Operation: The Sensor has two LED indicators that, when enabled,
has been detected by Infrared Technology.
DETECTION AREA
TOP VIEW
30
25
Field of view intersection with floor (Top view in feet 9 foot mounting height)
DETECTION AND ACTIVATION:
When a person enters a room, the sensor detects major body motion
and turns the light on. The light is kept on even as smaller body
movement is detected. This sensor's detection sequence logic (DSL)
minimizes false triggering by continuously analyzes the motion
detection signal and adjusts internal operation to maximize the
and electrical noise.
OPERATION MODE ADJUSTMENT
Settings
Switch
Function
Off
Bank A
A1
Not Used
A2
Not Used
A3
Not Used
A4
Walk-Thru / Normal
Walk-Thru Enabled
Bank B
B1
Daylight Sensor
Enabled
B2
LED Indicator
Enabled
B3
Test Mode
Off-On-Off (Toggle Enter/Exit)
B4
Not Used
TESTING THE SENSOR
Test Mode: This mode is used to set the Delayed-OFF Time to 5 seconds for
while in test mode.
1. Ensure Power is On
2. Remove the cover from the Operation Control Console
defaulted to the OFF position.
4. To enter Test Mode, move the switch from OFF to ON and then back to
OFF. IF B3 is already in the ON position, test mode can be entered by just
moving it back to the OFF position.
Notes for Test Mode:
1. The Delayed-OFF Time will remain in the 5 second test mode for 15
minutes. It will then automatically reset to the Delayed -OFF Time setting
test mode.
2. To manually take the sensor out of the test mode, move switch B3 from
OFF to ON and back to OFF again.
SIDE VIEW
(ft)
20
15
10
5
0
5
10
15
20
25
30
SETTINGS:
All aspects of sensor operation can be adjusted here
Infrared Adjustment- For maximum range, set fully clockwise (CW). If
On
reduced range is required, then turn counterclockwise (CCW) and test
Delayed-OFF Time Adjustment: Each time motion is detected, the load
remains activated for a pre-set time, which is set by the Delayed-OFF
Normal Occupancy
Time Adjustment, The fully CCW setting (30 seconds) can be used for
testing. The fully clockwise setting is 30 Minutes. If motion is detected
Disabled
during the ON time, then the load remains activated until the full ON
Disabled
time has passed since the latest motion detection.
Daylight Sensor Adjustment: This level needs to be set in a room where
natural light is at the desired level for the lighting load to not be turned
on. The sensor will still see motion (indicated by the red LEDS)
1.
3.
5.
30sec
0
9
21
14
0
14
A
B
(Fig. Operation control console)
Set the daylight sensor knob to fully counter clockwise (lowest level)
Turn the daylight sensor knob clockwise until the light turns on.
This will be the setting
Infra re d R a nge
Range setting
Full CCW = min.(OFF)
Full CW = max.
Factory Default
Daylight Sensor
Delayed-OFF time
Full CCW = min.(30 sec.)
Full CCW = Lights stay OFF
Full CW = Lights always turn ON (NO daylight override)
Full CW = max.(30 min.)
5min 10min 20min 30min
20 FC 40 FC
80 FC 160 FC 320 FC
Factory Default
Factory Default
21

Advertisement

loading

Summary of Contents for PerfectSense PS-PCL24-R

  • Page 1 DETECTION AREA TOP VIEW SIDE VIEW DESCRIPTION: Sensor designed to work with any power pack, to automatically control lighting in standard and cold weather applications. This sensor utilizes (ft) an industry leading 8-element Infrared Detector for superior minor motion detection while combining with a lens that provides major Field of view intersection with floor (Top view in feet 9 foot mounting height) motion detection up to 2000 sq.
  • Page 2 WARNINGS AND CAUTIONS: Included Parts List: INSTALLATION INSTRUCTIONS • To be installed and/or used in accordance with appropriate Sensor (1) Base mounting ring (1) electrical codes and regulations. Wall Anchors (3) Spring mounting clip (2) • If you are unsure about any part of these instructions, PIR detection Mask (1) 7/8”...