Download Print this page

Advertisement

Quick Links

This service bulletin provides a troubleshooting table for the Comark IOX and DCX series of
UHF television transmitter. The information contained in this table is the compilation of inputs
from Comark customer service representatives, field service engineers, design engineers, and
customers. If you would like to make an addition or correction to this table, please send your
information to the Comark Customer Service department via e-mail to
csfeedback@comarktv.com
Symptom
"Soft Start" failure prevents
application of high voltage.
Beam voltage OK when HV is
isolated, but sags significantly
(>5kV) when IOT is
connected. Possible positive
grid current alarms or severe
distortion of transmitted
waveform.
Beam voltage is 2/3 of
nominal value e.g. 22kV
instead of 33kV.
Beam voltage is unstable, bi-
stable (jumping between two
values).
Beam will not come on due to
cabinet interlock alarm, yet all
safety devices connected to
cabinet interlock line are in
proper positions.
High voltage is stable in beam
mode but drops out with
cabinet interlock alarm after
REV H - 10 January 2007
Technical Service Bulletin 030328
IOX / DCX Troubleshooting Table
Problem / Solution
480VAC Three Phase Power
Missing phase in 480V feed to beam supply primary. Trace three-phase voltages back from
beam supply disconnect with voltmeter to find where missing leg disappears.
Possible partial failure of CB3 motorized breaker. Check for presence of three-phase 480V
at output terminals of CB3 when closed. Replace CB3 as necessary.
Possible failure of HV rotary switch or outdoor disconnect. Check for 480V at output
terminals of suspected device. Replace faulty components as necessary.
To prevent damage to CB3 breaker, HV rotary switch, step-start contactors, and other 480V
devices, check tightness of terminal connections at regular intervals as part of a
preventative maintenance program.
Missing phase in 480V feed to beam supply primary. Trace three-phase voltages back from
beam supply disconnect with voltmeter to find where missing leg disappears.
Possible partial failure of CB3 motorized breaker. Check for presence of three-phase 480V
at output terminals of CB3 when closed. Replace CB3 as necessary.
Possible failure of HV rotary switch or outdoor disconnect. Check for 480V at output
terminals of suspected device. Replace faulty components as necessary.
Missing phase in 480V feed to beam supply primary. Trace three-phase voltages back from
beam supply disconnect with voltmeter to find where missing leg disappears.
Possible partial failure of CB3 motorized breaker. Check for presence of three-phase 480V
at output terminals of CB3 when closed. Replace CB3 as necessary.
Possible failure of HV rotary switch or outdoor disconnect. Check for 480V at output
terminals of suspected device. Replace faulty components as necessary.
Possible high voltage breakdown of 60 ohm filter resistors in HV beam supply. Extinguish
high voltage and inspect beam supply resistors. Replace resistors as necessary.
Possible over-temperature condition in step-start resistors. Step start resistor temperature
sensor is also part of cabinet interlock line. Condition typically occurs after frequent HV on-
off cycles in a short period of time. Allow step start resistors to cool down for ten minutes.
Interlock will clear itself as resistors cool.
Step-start overheating may also be due to open phase leg on K32 step start contactor.
Remove 480V and connect voltmeter across contactor terminals for one phase. Reapply
480V and read voltage drop across contactor while engaged. Repeat measurement for all
three phases. Look for non-zero voltage drop on one phase leg. Replace K32 as necessary.
Note: other devices in cabinet interlock line are HVPS door, HVPS ground hook, HVPS oil
level switch, HV key interlock system.
Possible over-temperature condition in step start resistors due to high resistance condition
in one or more legs of K32 step start contactor. Step start resistor temperature sensor is
also part of cabinet interlock line. Remove 480V and connect voltmeter across contactor
Technical Service Bulletin 030328
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the IOX Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Comark IOX Series

  • Page 1 Technical Service Bulletin 030328 IOX / DCX Troubleshooting Table This service bulletin provides a troubleshooting table for the Comark IOX and DCX series of UHF television transmitter. The information contained in this table is the compilation of inputs from Comark customer service representatives, field service engineers, design engineers, and customers.
  • Page 2: Control System

    Control System HPA control panel buttons Contact Comark for a replacement unit PN 452103-02. Be prepared to provide panel serial intermittent or insensitive. number, revision level of panel and HPA brain (CPU) board. (CPU code and Front Panel Buttons must be pressed very code.)
  • Page 3 A permanent solution may be had by upgrading to a commands from exciter 452117-01 HPA CPU card with code version 3.10 or later. Contact Comark for further cabinet or remote control. details.
  • Page 4 HPA alarms on remote I/O may be on input IN11 with system fault reset on input IN12. Documentation incorrectly block. shows IN12 as system/HPA fault reset and IN11 as unused. Contact Comark if doubts remain. Incandescent bulbs in system Replace incandescent bulbs with LED replacements. Suitable replacements are as follows: controller frequently burn out.
  • Page 5 Technical Service Bulletin 030328 of high voltage, does not fire event serves as a good confirmation that arc is internal to IOT. in HV ISOLATED mode. Note: an ion current reading of as low as 5uA may cause an immediate crowbar upon Arc known to be internal to application of high voltage.
  • Page 6 Possible use of incorrect fuses or magnetic breakers in building AC distribution system. Comark specifies BUSS FRS-R type fuses for main Tx feed and each HPA branch feed to prevent spurious AC trips during crowbars. Contact Comark or original installation AC distribution diagram for more details.
  • Page 7 Trace logic signal through HV and LV PCBs. Any interruption of the NOT TRIGGERED trip. signal will cause this condition. Check for presence of U5 retrofit daughter board in U5 socket on HV board. Obtain Comark Service Bulletin 020709 describing retrofit. Consult Service Bulletin 46744354-194 for further details.
  • Page 8 IOT tuning very sensitive to Input drive cable or coupling loop loose inside input cavity. Repair may be possible on-site mechanical shock, especially with partial cavity disassembly. Contact Comark or tube manufacturer. input return loss. Transmitter metering circuits Possible RF leak from IOT due to poorly seated cavities and / or missing finger stock. Check sensitive to opening and IOT cavities for proper mechanical seating.
  • Page 9 Technical Service Bulletin 030328 Rippling of IOT swept VSWR at IOT output or on RF sample cable to analyzer. Add 6dB attenuator pads on each response (greater than +/- end of sample cable. Check VSWR performance of RF dummy loads. Note changes in 0.5dB).
  • Page 10: Reverse Power

    Contact tube manufacturer for further instructions and to line up replacement IOT. If positive grid current is instantaneous upon application of high voltage: possible grid neutralization problems with Comark IOT. Consult manufacturer instructions for proper REV H - 10 January 2007...
  • Page 11 Type #46745360 FBI supply (millennium): replace faulty supply. Always check filament current or filament voltage voltage (E2V, L3) or current (Comark, CPI) calibrations upon installation of a new FBI otherwise erratic, unstable. supply. Consult Service Bulletin 030524 for more details.
  • Page 12 If cables are OK and FBI supply is receiving power, replace FO transmitter card (405307-01) for type 405343-01 (non-millennium) FBI supply. Replace entire FBI supply for type 46745360 (millennium) FBI supply. If problem persists, contact Comark for possible HPA controller backplane replacement.
  • Page 13 Technical Service Bulletin 030328 Serious damage to transmitter may result. HPA flow meter indicates full Flow meter mechanically stuck due to dried / crusted glycol. Disassemble switch and clean liquid cooling flow to tube with denatured alcohol. Check proper operation of flow meter and flow meter interlock at even with valve closed.
  • Page 14 -50dB and SNR less than 35dB as viewed on appropriate test equipment or Comark Scout software. Signal quality may also be measured by looping exciter output back to DAP feedback input (Loop J23 back to J16 (or J50 w/ OLDC) on ADAPT backplane and pad accordingly to obtain max I and max Q levels = 24000).
  • Page 15 –50dB and SNR less than 35dB as viewed on appropriate test equipment or Comark Scout software. Signal quality may also be measured by looping exciter output back to DAP feedback input (Loop J23 back to J16 (or J50 w/ OLDC) on ADAPT backplane and pad accordingly to obtain max I and max Q levels = 24000).
  • Page 16 The LO frequency is programmed at the factory, but may be changed in the field with special software permissions. Contact Comark for more details. This problem is most likely to surface after the replacement of an LO module.
  • Page 17 Release Version in ADAPT Control software to check exciter software revision level. If software revision is 3.4.6 or lower, contact Comark for upgrade to newer software level. Possible incorrect remote control set up. Use voltmeter to check status of remote control lines in TB1 in system cabinet.
  • Page 18 The LO frequency is programmed at the factory, but may be changed in the field with special software permissions. Contact Comark for more details. This problem is most likely to surface after the replacement of a DAP module.
  • Page 19 Applies principally to type 604540-01 filters (406/586). An improved replacement filter 608335-01 with higher Q factor is now available to provide improved aural metering stability and freedom from tuning drift. Contact Comark for further details. Prominent smeared corner on...
  • Page 20 Check integrity of video bypass capacitor. Location of video bypass cap varies waveform monitor while according to tube make and model. Contact Comark or tube manufacturer for more details. viewing field rate. Possible partial power supply failure in exciter or other low power RF stage. Check signal quality at driver output sample and exciter output sample to determine origin of vertical interval sag.
  • Page 21 Disconnect IF alarm open collector line. Allow traditional P switching chassis to sense and switch IF oscillators. At Comark, we are constantly striving to improve the satisfaction of both our new and existing customers. Please do not hesitate to contact Comark Customer Service with any questions you may have concerning the contents of this service bulletin.

This manual is also suitable for:

Dcx series