Page 3
24 months is valid from the date of sale to the end buyer, but not more than 36 months after delivery from Smarteh. In case of claims within warranty time, which are based on material malfunctions the producer offers free replacement. The method of return of malfunctioned module, together with description, can be arranged with our authorized representative.
Additional equipment LOC-1 2 DESCRIPTION The LOC-1 is a 4 wire occupancy sensor used in combination with the input modules (e.g., LPC-2.I16, LPC-2.DI1, LPC-2.DI5, LPC-2.R01, LPC-2.R02) to detect moving person or object. LOC-1 uses PIR sensor for occupancy sensing and current protected bipolar transistor as a switching...
Additional equipment LOC-1 3 FEATURES Figure 1: LOC-1 Occupancy sensor Table 1: Features Wide power supply range: 5 .. 32 V DC/AC Output voltage free contact Mounting with integrated magnets or screws Convenient enclosure for multi mounting possibilities 2 diagnose LED...
Power Supply = 5 .. 32 V AC/DC Option 2: No moving person or object present: voltage drop on sensor > 4 V. Moving person or object present: voltage drop on sensor < 1 V. Smarteh input modules (e.g., LPC-2.I16, LPC-2.DI1, LPC-2.DI5, LPC-2.R01, LPC-2.R02).
Page 9
Additional equipment LOC-1 Figure 4: Connection scheme with pull-down resistor +U = 10 .. 32 V DC R = 3 .. 20 kΩ Power Supply = 5 .. 32 V AC/DC Option 1: No moving person or object present: voltage drop on sensor > 95 % Vcc.
Page 10
Additional equipment LOC-1 Figure 6: Connection scheme Table 2: Flying lead wires Yellow 5 .. 32 V AC/DC Power supply Brown Ground Green 5 .. 32 V DC (positive) NO voltage free contact White 0 V DC (negative) NO voltage free contact...
Mounting instructions: The occupancy sensor should be located on the position that provides maximum effect. 1. Mount LOC-1 sensor on the position with the magnets or screws . Magnets can be pushed to the other side of abutment surface if needed.
• Label 2 descriptions: 1. S/N: LOC1-S9-1600000003 is the serial number. LOC1 – short product name, • S9 – user code (test procedure, e.g. Smarteh person xxx), • 1600000003 – year and current stack code, • 16 – year, •...
Additional equipment LOC-1 5 TECHNICAL SPECIFICATIONS Table 4: Technical specifications Power supply 5 .. 32 V AC/DC Consumption max. 15 mA Voltage free contact power supply 5 .. 32 V DC Output type transistor (NO) Output current max. 15 mA, internally limited...
Additional equipment LOC-1 6 SPARE PARTS For ordering spare parts following Part Numbers should be used: LOC-1 Occupancy sensor, 2 m LOC-1 P/N: 204LOC16001001...
Additional equipment LOC-1 7 CHANGES The following table describes all the changes to the document. Date Description 30.09.16 The initial version, issued as LOC-1 User Manual.
Need help?
Do you have a question about the LOC-1 and is the answer not in the manual?
Questions and answers