4. System Requirements ......................7 5. Product Description ......................8 6. Installation and Connection ....................9 ® 6.1 Connecting the ADL-MXmini ..................10 6.1.1 Connecting the Power Supply for external Sensors ..........11 6.1.2 Connecting to Sensors and other Devices/Transducer .........12 6.1.3 Power Connection ....................13 6.1.4 Connecting to your PC ..................13...
Page 4
Meier-NT GmbH. The creation of a backup copy of software for private use, if it is both feasible and recommended by us, is excluded from that rule. Contraventions will be prosecuted and oblige to pay compensation for damages.
▪ The activation is prohibited unless the national electromagnetic compatibility- regulations are met. Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0 Director Dipl. Ing.(FH) Heiko Meier · HRB 25917 District Court Chemnitz...
Page 6
▪ Compliance with the limits required by national regulations is the responsibility of the manufacturers. European countries: EU-Directive 2004/108/EG (EMC -Directive). • Technical data, connection and installation requirements can be found in the product documentation and must be followed strictly. Attention! „Attention“...
Software: Web browser capable of displaying Flash-graphics. Depending on the browser, an update might be necessary. Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0 Director Dipl. Ing.(FH) Heiko Meier · HRB 25917 District Court Chemnitz...
Plugging in or removing of cable and SIM card is only allowed when the device is turned off. Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0 Director Dipl. Ing.(FH) Heiko Meier · HRB 25917 District Court Chemnitz...
Connection to a PC gets established via Ethernet cable (crossover cable) or via integration into a network. ® After being connected to power supply the boot screen will be shown on the ADL-MXmini and after further 20 seconds the device is ready for use.
The power supply for the ADL-MXmini must be adjusted to the appropriate level. The maximum load for the output is 500mA. Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0 Director Dipl. Ing.(FH) Heiko Meier · HRB 25917 District Court Chemnitz...
6.1.2 Connecting to Sensors and other Devices/Transducer ® The connection of sensors with the ADL-MXmini (RS485 P1 / RS485 P2 / RS485 P3 /SDI12 / RS232(V.24) or Ethernet) depends on the sensor type. It might be necessary to adapt the interface parameters and the address.
Subnet mask 255.255.0.0 This emergency address is always active, regardless of which IP settings have been made. Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0 Director Dipl. Ing.(FH) Heiko Meier · HRB 25917 District Court Chemnitz...
Page 14
Integration into a local network via LAN: ® In case your network includes a DHCP server, the ADL-MXmini will automatically obtain an IP address. If your network does not include a DHCP server, the address must be determined statically. (See „ Direct Linking by use of a crossover cable “).
7.1.2 Menu Structure The measured data on display changes every four seconds or can be changed with the help of the keys. Menu Current Data Settings Login To get to the menu item “Settings”, the key has to be pressed. The arrow keys can be used to navigate through menu items.
Page 17
By pressing the “OK” button you arrow keys and again the can proceed to the next step. Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0 Director Dipl. Ing.(FH) Heiko Meier · HRB 25917 District Court Chemnitz...
Page 18
Menu item Language ® Change the language of the ADL-MXmini Menu item Device ® Shows the version number, the serial number and available memory of the ADL-MXmini Menu item Factory reset ® Reset all settings of the ADL-MXmini Menu item Log Out...
7.2 Web Interface ® In order to have access to the web interface of the ADL-MXmini and PC and have to be connected via crossover cable, network or modem. The current IP address of the ADL- can be checked under the menu item ”Network“ on the GLCD. In delivery condition ®...
7.2.1.1 Start Screen ® On the start screen basic information about the ADL-MXmini is on display, among them are the location, serial number, firmware version and available memory. 7.2.1.2 Analysis Online Values On this page the measured data of the connected devices is on display. In case no data is...
Page 21
After entering all the required information press „Save“ and the diagram will be displayed. The axes of the diagram are autoscaled. Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0 Director Dipl. Ing.(FH) Heiko Meier · HRB 25917 District Court Chemnitz...
7.2.1.3 Login ® In order to make changes to the configuration or the sensors of the ADL-MXmini password must be entered first. The standard password is: 000000. This password can be changed in “System Settings“.
7.2.2.1 System Station Description In the station description information about the station can be entered and displayed. the coordinate values follow the Gauss-Krüger-format. A necessary translation can for example be done on the following webpage: http://geo.hlipp.de/latlong.php. System Settings Date, time, language and password for the data logger can be changed here. To change the password the old password must be entered once and the new password must be entered twice.
Page 26
Provider settings for RAS connection For dial-in via RAS connection to the ADL-MXmini you must setup username and password. By default the following settings are used:...
Page 27
The configuration of the data logger regarding data transmission to an FTP server or the web portal of Meier-NT can be done on this page. If “User (ftp)“ is selected as target, the data of your own FTP server have to be entered here. If the data shall be sent via the integrated GSM Modem, “Use modem“...
Page 28
Notifications On this page the notification functions of the data logger can be configurated. First enter and then select the email address or telephone number of the receiver. This feature is still in development and will be able for use in a later firmware version.
Page 29
Internet, an update can be brought in manually. At first an update has to be either downloaded from the Meier- NT Homepage or requested via mail at info@meier-nt.de. After a connection to the ®...
7.2.2.2 Devices Device Search Configuration Device Search Bevor the search can be started, you have to select which device is connected to which interface. The search for connected devices can be started with the button “Scan for inverters“. During the process a bar indicates the progress, and a list with already found devices is on display.
In this menu you can setup digital in- and outputs as well as the internal supply voltage measurement of the ADL-MXmini. The connections DIO1 – DIO8 are useable as in- and outputs. Therefore you must enable and setup this function at the appropriate connection.
Page 33
Additionally the measured value can be translated with the help of a formula. Further information can be found in the chapter “Formulas and Arithmetical Variables”. Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0 Director Dipl. Ing.(FH) Heiko Meier · HRB 25917 District Court Chemnitz...
7.3.5 Formulas and Arithmetical Variables A formula can be defined for every channel of a group and device, which either directly translates the recorded value or sets a switching condition for an output. The same scheme can be used in order to express a formula in arithmetic variables. Arithmetical Variables are used for calculating and linking of values.
Page 35
The input value for °C is the sensor value, which is available in “v1”. The complete formula to be entered therefore reads as: v1*1.8+32 Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0 Director Dipl. Ing.(FH) Heiko Meier · HRB 25917 District Court Chemnitz...
Page 36
Attention!!! Mind the notes from chapter “7.3.4.1 Basic Advices for entering Formulas”. 7.3.5.1 Basic Advices for entering Formulas: • Use a dot “.” and not a comma as decimal separator. • v0 references the own value • v1 to vx reference assigned values of other channels or variables •...
Page 37
(nan=stay on last value) k: input type (0=digital input, 1=pulse counter) Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0 Director Dipl. Ing.(FH) Heiko Meier · HRB 25917 District Court Chemnitz...
Annex Connection Diagram Clima Sensor US - ADL-MXmini Sensor cable: 16-pole sensor cable with connection box Power supply Clima Sensor US: ® The ADL-MXmini can provide power supply for the sensor only on a limited basis (The maximum load for the output (Vout) is 500mA) therefore heating cannot be activated. In case the sensor`s heating is required, the power supply has to be gained from an independent source.
Page 41
00001 station altitude station altitude is checked against GPS altitude 09998 independent message deactivated 00000 output Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0 Director Dipl. Ing.(FH) Heiko Meier · HRB 25917 District Court Chemnitz...
5-pole, free conductor end on straight M12 socket, A-coded. Power supply Field Extension: The power supply for the Field Extension can be provided via the ADL-MXmini. The power consumption of the Field Extension and the sensors connected to it should be checked in...
The power supply for the humidity and air temperature sensor can be provided via the ADL- MXmini. The maximum load for the output (Vout) is 500mA. Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0 Director Dipl. Ing.(FH) Heiko Meier · HRB 25917 District Court Chemnitz...
Page 44
Connection Diagram Tensiometer T8 - ADL-MXmini Sensor cable: sensor/actuator cable, M 12, 8-pole, free conductor end. Power supply Tensiometer T8: The power supply for the Tensiometer T8 can be provided via the ADL-MXmini. The maximum load for the output (Vout) is 500mA.
The power supply for the humidity and air temperature sensor DKrF400 can be provided via the ADL-MXmini. The maximum load for the output (Vout) is 500mA. Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0 Director Dipl. Ing.(FH) Heiko Meier · HRB 25917 District Court Chemnitz...
Connection Diagram M-70xx measuring module - ADL-MXmini Sensor cable: Power supply M-70xx module: The power supply for the M-70xx module can be provided via the ADL-MXmini. The maximum load for the output (Vout) is 500mA.
Sensor cable: Power supply pressure-level sensor Keller 36XW: The power supply for the Keller 36XW can be provided via the ADL-MXmini. The maximum load for the output (Vout) is 500mA. Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0...
Connection Diagram Precipitation Sensor Pluvio 2 - ADL-MXmini Sensor cable: Power supply Pluvio2: The power supply for the Pluvio 2 cannot be provided via the ADL-MXmini. The maximum load for the output (Vout) is 500mA.
Sensor cable: Power supply precipitation sensor: The power supply for the precipitation sensor can be provided via the ADL-MXmini. The maximum load for the output (Vout) is 500mA. Meier-NT GmbH · Rittergutsweg 5 · 08297 Zwönitz · Tel. 037754 304 0...
Connection Diagram WXT510/520 - ADL-MXmini Sensor cable: sensor cable, 8-pole, with M 12 socket. Power supply WXT510/520: ® The ADL-MXmini can provide power supply for the sensor only on a limited basis (The maximum load for the output (Vout) is 500mA) therefore heating cannot be activated. In case the sensor`s heating is required, the power supply has to be gained from an independent source.
Need help?
Do you have a question about the ADL-MXmini and is the answer not in the manual?
Questions and answers