Air Quality; Address Configuration; Communications Configuration - Veris Industries GWNP Series Installation Manual

Bacnet and modbus protocol communication wall mounted platform for gas sensors
Table of Contents

Advertisement

Installation Guide

Air Quality

Configuration
Z207135-0C
Page 5 of 10
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
The GWNP includes two sets of DIP switches, as shown in the Product Diagram section. The DIP switch labeled
"ADDRESS" is for addressing. The DIP switch labeled "CONFIG" is for communications configuration.

Address Configuration

Each device on a single network must have a unique address. Set the DIP switch labeled "ADDRESS" to assign a
unique address before the device is connected to the network. If an address is selected that conflicts with another
device, neither device will be able to communicate.
Address the GWNP as any whole number between and including 1 to 127. Note that zero is not a valid address
for Modbus; zero is a valid address for BACnet. Positions 1 through 7 of the "ADDRESS" DIP switch designate the
address. Position 8 toggles between the Modbus and BACnet communication protocols, as shown in the diagram
below.
LSB
1
2
To set an address using the DIP switch, simply add the values of any switches that are in the ON position.
For example, an address of 73 is set as shown in the diagram below.
LSB
1
2
Position number 1 has an ON value of 1, position number 4 has an ON value of 8 and position number 7 has an ON
value of 64 (1 + 8 + 64 = 73).

Communications Configuration

See the Product Diagram section for the location of the DIP switch labeled "CONFIG". The following parameters are
configurable:
• Parity (Modbus only): None, Odd, None1 (one stop bit), Even
• Baud rate: 8600, 19200, 38400, 57600 (Modbus), 76800 (BACnet)
• Autobaud: On, Off
Note: Autobaud may not be able to automatically determine the baud rate in some situations. In this case, set
Autobaud to OFF and use the manual baud setting.
None
off
off
off
Odd
on
off
on
None1
off
on
off
Even
on
on
on
Parity
(Modbus Only)
©2016 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Binary Address
4
8
16
32
64
Modbus/BACnet
Toggle
Decimal Values
On = Modbus
Off = BACnet
4
8
16
32
64
On
Yes
Off
No
Autobaud
off
9600
off
19200
on
38400
on
57600 (Modbus)
76800 (BACnet)
Baud
MSB
73
=
MSB
TM
0916