Summary of Contents for Eurotherm Chessell 394

  • Page 1 ε EUROTHERM CHESSELL Model 394 Chart recorder Installation and operation manual...
  • Page 2 Declaration of Conformity Manufacturer's name: Eurotherm Recorders Incorporated Manufacturer's address One Pheasant Run, Newtown Industrial Commons, Newtown, PA 18940 USA. Product type: Industrial chart recorder Model: (Status level B2 or higher) Safety specification: EN61010-1: 1993 / A2:1995 EMC emissions specification: EN50081-2 (Group1;...
  • Page 3: Table Of Contents

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Circular Chart Recorder Installation and Operation Manual Overall contents list Section Page SECTION i PREAMBLE ............i - 1 SAFETY NOTES ................ i - 3 SECTION 1 INSTALLATION..........1 - 1 1.1 UNPACKING THE RECORDER ..........1 - 2 1.2 INSTALLATION ..............
  • Page 4 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL List of contents (Cont.) Section Page SECTION 5 REFERENCE ............5 - 1 5.1 COSHH ................5 - 3 5.2 ERROR MESSAGES ............5 - 5 5.3 LIST OF EFFECTIVE PAGES ..........5 - 6 5.4 GLOSSARY OF TERMS ............
  • Page 5 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL STATIC ELECTRICITY High voltages (tens of kilo-volts) can be generated on the human skin through a number of mechanisms, such as fric- tion between different materials (e.g. nylon and skin), and separation of similar materials (e.g. masking tape, nylon sheet).
  • Page 6: Safety Notes

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Safety Notes 1. Before any other connection is made, the protective earth ground terminal shall be connected to a protective con- ductor. The supply voltage (mains) wiring must be terminated in such a way that, should it slip in the cable clamp, the Earth ground wire would be the last wire to become disconnected.
  • Page 7 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Section 1 INSTALLATION LIST OF CONTENTS Section Page 1.1 UNPACKING THE RECORDER ..........1 - 2 1.2 INSTALLATION ..............1 - 2 1 - 2 1.2.1 Mechanical installation ............1 - 2 PANEL MOUNTING ............1 - 2 PIPE MOUNTING .............
  • Page 8: Section 1 Installation

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Section 1 Installation 1.1 UNPACKING THE RECORDER The recorder is despatched in a special pack designed to give adequate protection during transit. Should the outer box show signs of damage, it should be opened immediately and the recorder examined. If there is evidence of damage, the instrument should not be operated and the local representative contacted for instructions.
  • Page 9 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 345 mm 22.5 12.5 mm Note: Bezel and panel cutout are offset from one another horizontally Top view Max. panel thickness = 25.4 mm Door opens 100˚ Lift latch to operate Front view Right side 148 mm 380 mm...
  • Page 10 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 1.2.2 ELECRICAL INSTALLATION (Cont.) TR A N SMI TTE R POW ER SU P PLY N º 2 TR A N SMI TTE R POW ER SU P PLY N º 1 Pr in t Ar m Ch ar t Dis pl ay...
  • Page 11 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 1.2.2 ELECTRICAL INSTALLATION (Cont.) SUPPLY VOLTAGE (MAINS) WIRING Leave the earth ground lead longer than the others, so it would be the last to become disconnected should the cable be pulled out of the connector. Green Black White...
  • Page 12 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL SIGNAL WIRING V+ V- V+ V- V+ V- Shun t ass embl y Attenu ator ass embl y – – – DC V DC V (-10V <Vin<10V) DC mA DC mV (– 10 0 to +100 V) The rm oc ou ple s V+ V- V+ V-...
  • Page 13: Changing The Chart

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 1.3 CHANGING THE CHART Op:Display Open the recorder door (fig 1.3a) and operate the cancel (x) key to call the Op: Display page, then use the page key to call the Op:Chart Op: Chart page ↵...
  • Page 14: Changing The Cartridge

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 1.4 CHANGING THE CARTRIDGE Note: Care should be taken to avoid cartridge ink contact with skin or clothing Before changing the cartridge, switch the chart drive off as described in section 1.3 above. Then use the page key twice, then the Enter key, to park the printhead.
  • Page 15 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Section 2 BASIC OPERATION Section Page 2.1 POWER UP ............... 2 - 2 2.2 BACKGROUND DISPLAY ............ 2 - 2 2.3 ALARM INDICATION ............2 - 3 2.4 KEY/DISPLAY FUNCTIONS ..........2 - 3 2 - 3 2.4.1 Keys ..................
  • Page 16: Section 2 Basic Operation

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Section 2 BASIC OPERATION This section is designed to help you as a new user to understand the display and key operations. After the display and key descriptions, an example configuration is given to show you how to set up an input channel to a known set of parameters, so you can start recording your own traces with the minimum of effort.
  • Page 17: Alarm Indication

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 2.3 ALARM INDICATION Each of the six input channels has its own LED indicator on the display. A further alarm icon situated to the left of the display line indicates whenever there is an active alarm. The symbols flash until the alarm is acknowledged or are steadily illuminated if the alarms are still active but have been acknowledged.
  • Page 18 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 2.4.1 KEYS (Cont.) Scroll up / down keys This key is used a. To scroll through text characters when entering text strings. b. To enter numeric values. c. To scroll through all menu items associated with a parameter (e.g. thermocouple types). Cancel This is used a.
  • Page 19: Configuration Example

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 2.5 CONFIGURATION EXAMPLE This section gives you a step-by-step guide to the basic configuration of a single channel (Nº2) to an imaginary set of input conditions. If you are new to recorders, it is recommended that you first follow this example, and then modify it to suit your own particular requirements.
  • Page 20 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 2.5.2 Entering Configuration (Cont.) Password 00000 The password is set to '10' at the factory. The pass- word can be edited in Instrument Configration. Password 00000 To enter '10', press the cursor key three times, then the Password 00000 up arrow and 'enter' keys.
  • Page 21 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 2.5.3 CHANNEL CONFIGURATION (Cont.) Temperature units I/P Units ˚C Operate the page key to call the input units page Lin Type Type B Units are ˚C as required. Other units (˚F, K or R could be scrolled to using the arrow keys) Lin Type Type C Operate the Page up key to call the linearisation type...
  • Page 22 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 2.5.3 CHANNEL CONFIGURATION (Cont.) Input Break Response Use the Page up key twice to call the Break Response Damping None page. This page allows us to set Drive high, such that if the wiring to the thermocouple breaks, the pen will move to the outer edge of the chart and trace at Brk Rsp None Full Scale, thus making it obvious that there is a...
  • Page 23 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 2.5.3 CHANNEL CONFIGURATION (Cont.) Type Absolute High Alarm Threshold (Setpoint) Threshold 0.00 Operate the Page up key to call the Threshold page. Use the up arrow and cursor keys to set the threshold to 780.00, using the technique described for input Threshold 780.00 range (section 2.5.3 above).
  • Page 24 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 2.5.3 CHANNEL CONFIGURATION (Cont.) Channel : Trace Checking that the trace is ON Use the Enter key to call the trace on/off page Trace Off If the trace is off, use either arrow key to scroll to 'On'.
  • Page 25 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Section 3 OPERATOR MENUS Section Page 3.1 INTRODUCTION ..............3 - 3 3.2 TOP LEVEL OPERATOR MENUS ........... 3 - 3 3.3 CHART SUBMENU ............. 3 - 3 3 - 4 3.3.1 Chart on/off ................. 3 - 4 CHART ALIGN ..............
  • Page 26 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL This page is deliberately left blank Section 3 HA250385 Page 3 - 2 Issue 2 Mar 98...
  • Page 27: Section 3 Operator Menus

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL SECTION 3 OPERATOR MENUS 3.1 INTRODUCTION This section describes the operator menu structure of the basic recorder. For details of Options such as relays, analog retransmission, derived variables (math), memory card or serial communications; see the Multipoint Circular Chart Options Manual.
  • Page 28 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 3.3 CHART SUBMENU (Cont.) Op:Chart ↵ for Fast Chart Off ↵ for Chart Off Please wait Speed is HHH hour ↵ for Chart On Please wait ↵ to Send Log 1 ↵ to Send Log 2 ↵...
  • Page 29: Alarm Summary Page

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 3.3.2 Logs When delivered form the factory, Log groups 1 and 2 contain all the recorder's input channels. During 'Group con- figuration' (section 4.6) these items can be deleted individually, and if the relevant options are present, derived variables, totalisers and counters can be added.
  • Page 30: Alarm Setup Page

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 3.4.1 Display interpretation The alarms appear in channel order, and are flashing if not acknowledged. Each alarm is presented as a channel number (full size), followed by a subscript alarm number (1 to 4) . 3.5 ALARM SETUP PAGE This page allows the operator to view the alarm type, threshold settings etc.
  • Page 31: System Error

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 3.7.1 Back-up battery The system date and time are maintained under power-off conditions, by a re-chargeable Nickel-metal hydride battery. When fully charged, the battery will maintain the time and date for approximately one month. As despatched from the factory, the battery is discharged.
  • Page 32: Calibrate Chart

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Figure 3.9 Entry to configuration 3.10 CALIBRATE CHART This page allows the printhead zero and span positions to be set to chart zero and span. On initiation, the printhead traces lines on the chart where it thinks zero and span are. If incorrect, the positions can be adjusted using the up arrow key to move the trace slightly to the right, or the down arrow to move it to the left.
  • Page 33: Operator Menus Summary

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 3.11 OPERATOR MENUS SUMMARY Background Process Variable (PV) display 1 568 .3 7 De g C Use 'Cancel' key to enter Operator menus Op :Dis pl ay Use 'Enter' key to retur n to PV display Op :C ha rt Op :C al ib ra te cha rt...
  • Page 34 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL OPERATOR MENUS cont. Use ' Page' keys t o move from page to page. Use ' Enter' k ey t o enter 'P age', to c onfirm c hanges or to return t o PV dis play. Use Up and Down arrows to sc roll through underlined items in page.
  • Page 35 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Section 4 CONFIGURATION LIST OF CONTENTS Section Page 4.1 INTRODUCTION ..............4 - 3 4 - 3 4.1.1 Password ................4 - 3 4.1.2 Text entry ................4 - 3 CHARACTER SET ............. 4 - 5 4.1.3 Options ................
  • Page 36 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Section 4 List of Contents (Continued) Section Page 4 - 15 4.5.2 Alarm configuration ............... 4 - 15 SETPOINT CONFIGURATION ........... 4 - 17 ALARM PARAMETERS ............4 - 18 ALARM JOBS ..............4 - 18 4.5.3 Trace configuration ..............
  • Page 37: Section 4 Configuration

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Section 4 Configuration Note: In order to help new users, a brief configuration guide appears as section 2 of this manual. This guide gives step-by-step instructions to show the example configuration of a single input channel to. Note: A configuration tool to run on a PC, is available from the manufacturer to speed configuration, and text entry in particular.
  • Page 38 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.1 INTRODUCTION (Cont.) Table 4.1 Configuration parameter locator Parameter etc. to be edited Configuration page name Where to look Adaptive recording Chart Section 4.4.5 Adjust input Adjust Section 4.14 Alarm Jobs Channel: Alarm: Jobs Section 4.5.2 Alarm Parameters Channel : Alarm : Setpoint...
  • Page 39: Logs 1 And 2 ........................................................................ 4.1.5 Jobs

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.1.3 Options In order to simplify this manual, option descriptions for relays, analog retransmission, derived variables (math), memory card and serial communications are included in the Options Manual supplied, if appropriate, with your recorder.
  • Page 40 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.1.5 JOBS (Cont.) No Action Chart online N = Channel number (use up/down arrow keys) While Active Chart Span B Ch N While Inactive Chart Span B for All While UnAck'ed Disable all alarms Ack All Alarms Log 1 to chart On Going Active...
  • Page 41: Configuration Techniques

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.2 CONFIGURATION TECHNIQUES Configuration menus are treated in the same way as operator menus, with the page and enter keys being used to se- lect a parameter, and the arrow keys being used to edit it. To return to a higher menu level the cancel (x) key is used. Figure 4.2 below shows the alarm setpoint sub-menus in an attempt to illustrate these techniques.
  • Page 42: Instrument Configuration

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.3 INSTRUMENT CONFIGURATION Instrument configuration allows: 1. The setting of a new password 2. The setting of a different language for subsequent displays and chart printing 3. Configuration of remote cold junction input Conf:Instrument Use Cursor and arrow keys to enter new Set Password: 00010...
  • Page 43: Chart Configuration

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.4 CHART CONFIGURATION Chart configuration allows the following to be set up: 1. Chart speed. 2. Log interval for logging Log 1 Process Variables automatically on the chart. 3. Time/date/scale/chart speed etc. data. 4.
  • Page 44: Log Intervals A And B

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.4.3 Stop After One Revolution When selected, this feature causes the chart to complete one turn from the point at which it was last placed online and then stop. The tracing will stop, the "Chart online" event source will become inactive and any demand annotation will print at maximum speed.
  • Page 45: Channel Configuration

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.5 CHANNEL CONFIGURATION Conf: Channel 1 Channel : Range Channel : Alarm 1 Channel : Trace Scrolls through T/C, mA (always use mV I/P type I/P type mA type with current shunt input), V, mA, RTD, Ohms, Dig, Comms (if fitted), Cont1 (if fitted), Cont2 (if fitted), Test.
  • Page 46: Range Configuration

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Channel configuration is in three parts: Range, Alarms and Trace. 4.5.1 Range configuration This sub section allows the setting up of the following: Input type, range and units Linearisation type Scaling Value format (decimal point position) Input damping Input break response Channel tag (identifier or descriptor)
  • Page 47: Cjc Type

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.5.1 RANGE CONFIGURATION (Cont.) CJC type For thermocouple inputs only, allows Off, Internal, External or Remote to be selected as cold junction type. Internal uses the recorder's internal temperature sensor to apply cold junction compensation. External is used where the cold junction of one or more thermocouples is maintained at a known temperature.
  • Page 48: Open / Closed

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.5.1 RANGE CONFIGURATION (Cont.) Open / Closed For Input Type digital (not available on Channel 1), the PV display consists of a text string or an open/closed representation. The strings to appear under open (logic low) and closed (logic high) conditions can be scrolled through using the up/down arrow keys.
  • Page 49: Alarm Configuration

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.5.2 Alarm configuration Up to four alarms can be configured for each channel. For absolute and deviation alarms, a hysteresis value can be entered to prevent spurious triggering should the process value 'hover' around the alarm threshold. For all types of alarm, a dwell (or waiting) period can be configured, and if the alarm clears within this period, the alarm is ignored.
  • Page 50 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.5.2 ALARM CONFIGURATION (Cont.) Latest part of chart For clarity, the following alarm diagrams are shown Absolute Low Absolute High with straight rather than curved value lines. PV values setpoint setpoint increase from the right (inner) to left (outer) portion of the chart.
  • Page 51: Alarm Parameters

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.5.2 ALARM CONFIGURATION (Cont.) Latest part of chart Rate of change - fall Rate-of-change alarms alarm active With rate-of-change alarms, a value, a time period Measured and an averaging period have to be configured. In value the accompanying sketch, the Value is 200 litres and the Time Period is one minute.
  • Page 52: Alarm Jobs

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Alarm jobs As shown in figure 4.5.2a on page 4-15, the jobs page is reached by operating the page key from the Alarm : Setpoint page. Two jobs can be set up for each alarm, and the actions they can carry out are as shown in the Jobs description in section 4.1.5 4.5.3 Trace configuration This section of configuration allows you to:...
  • Page 53 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.5.3 TRACE CONFIGURATION (Cont.) Use ar ro w keys t o s el ect ch an nel Co nf :C ha nn el 1 Ch an ne l : Ra ng e Ch an ne l : Al ar m 1 Ch an ne l : Tr ac e Scro ll thr oug h O ff, On Tr ac e Of f...
  • Page 54: Group Configuration

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.6 GROUP CONFIGURATION This allows contents and format of four* groups to be set up: Log1, Log2, DV*, and display. * Note: DV appears only if the maths option is fitted. Conf:Group Display Conf:Group Log 1 01 02 03 04 05 06 01 02 03 04 05 06...
  • Page 55: Dv Group

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.6 GROUP CONFIGURATION (Cont.) 4.6.2 DV Group Allows a number of items to be grouped together for action by a Derived Variable (e.g Group Average). See the Op- tions manual for full details. This group can contain all values available to the display and the two logs, but cannot be printed to the chart.
  • Page 56: Format

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.8 CLOCK CONFIGURATION (Cont.) FORMAT Use the up arrow key to scroll through Day/Month/Year and Month/Day/Year as date formats. It should be noted that if a valid date has not been set up, date format change will not work. 4.9 MESSAGE CONFIGURATION This part of the configuration allows up to 20 messages to be entered, for display and/or to be printed on the chart as the result of operator or Job action.
  • Page 57: Internal Events

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.9.1 EMBEDDED SEQUENCES (Cont.) EXAMPLES An alarm going active on channel 3 has 'Print Message 1 on going active' as one of its jobs. If Message 1 were set up to be: <TIME><.TA><-PV> then the current time and the tag and process value of chan- nel 3 would be printed on the chart.
  • Page 58 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.10 EVENT CONFIGURATION (Cont.) Use arrow keys to select event Conf:Events 1 number See section 4.1.5 for a list of jobs. Event : Source Event : Job 1 Event Disabled Event Enabled S1 Only S1 Or S2 S1 And S2 S1:System error...
  • Page 59: Configuration Transfer

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.11 CONFIGURATION TRANSFER This facility allows the transfer between recorders, or between the recorder and a host computer (running PC configuration software) using a jack socket located towards the right of the bulkhead behind the cassette. Only the Baud rate is configurable at the recorder, so if you are transferring to and from a host computer, the other settings you need are: Eight data bits, One stop bit and No parity.
  • Page 60: Not Used

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.12 NOT USED 4.13 OPERATOR ACCESS For the sake of security, it is possible to enable/disable certain of the operator functions. These functions are listed below, together with their 'default permissions' (i.e. how they are despatched from the factory). Switch the chart drive on and off: default = Yes Initiate Log: default = Yes Adjust alarm thresholds: default = No...
  • Page 61: Adjust

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.14 ADJUST 4.14.1 Input adjust NOTE, input boards are perminantly calibrated and require no periodic calibration. This feature allows input channels to be adjusted to make allowance for non-standard inputs. The technique used is to apply a known input at the low end of the input range for each channel in question. Once the reading displayed by the recorder has stabilized, the 'correct' value is entered.
  • Page 62: Chart Adjust

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.14.2 Chart adjust This feature is the same as the Operator Calibrate Chart feature described in section 3.10 4.15 DEFAULT CONFIGURATION This section allows the user to return to the factory set configuration. After confirmation has been received, the re- corder re-initialises and returns to the background display (section 2.1).
  • Page 63 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL This page is deliberately blank HA250385 Section 4 Issue 2 Mar 98 Page 4 - 29...
  • Page 64: Configuration Menus Summary

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 4.16 CONFIGURATION MENUS SUMMARY T op leve l O pera t or SEE PAGE 4-32 FOR menu DESCRIPTION OF OP:Configuration Set : KEY FUNCTION Chart spe eds A an d B Char t sp eed unit s Log i nt er val Password _____ Ent er p asswor d...
  • Page 65 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Use 'Page' keys to move from page to page. Use 'Enter' key to enter 'Page', to confirm changes or to return to PV display. Use Up and Down arrows to scroll through underlined items in page. Use 'Cancel' key to ignore changes, to return to a higher level, or to enter operator menus from PV display.
  • Page 66 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL This page is deliberately blank Section 4 HA250385 Page 4 - 32 Issue 2 Mar 98...
  • Page 67 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Section 5 REFERENCE List of contents Section Page 5.1 COSHH ................5 - 3 5 - 3 5.1.1 Printheads ................5 - 4 5.1.2 Batteries ................5.2 ERROR MESSAGES ............5 - 5 5 - 5 5.2.1 Invalid configuration ..............
  • Page 68 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL This page is deliberately blank Section 5 HA250385 Page 5 - 2 Issue 2 Mar 98...
  • Page 69: Coshh

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 5.1 COSHH 5.1.1 Printheads WATER BASED INKS NOT CONTAINING FORMAMIDE Product: LA248163 Part numbers: LA249556 LA250280 HAZARDOUS INGREDIENTS Name % Range Toxicological data Acid dye Not available Not established 1 to 4 PHYSICAL DATA 1.05 to 1.1 Specific gravity Boiling point...
  • Page 70 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 5.1.2 Batteries Product: Rechargeable batteries Part numbers: PA250331 HAZARDOUS INGREDIENTS Name % Range Toxicological data Mischmetal alloy available Nickel Hydroxide Highly toxic if ingested available Potassiun hydroxide Highly toxic, Highly corrosive. available PHYSICAL DATA Not applicable Specific gravity Boiling point...
  • Page 71: Error Messages

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 5.2 ERROR MESSAGES 5.2.1 Invalid configuration This message can appear under a number of circumstances, but is normally the result of the operation of the 'Enter' key before configuration is complete. For example if you have set input type to T/C, but operate the Enter key before you set a suitable Linearization type, the message will appear, and the attempted 'Enter'will be ignored.
  • Page 72 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 5.3 LIST OF EFFECTIVE PAGES This manual consists of the following pages at their stated issue number Section i Section 4 (Cont.) Page i - 1 ........Issue 4 Feb 99 Page 4 - 10 ........Issue 4 Feb 99 Page i - 2 ........
  • Page 73: Glossary Of Terms

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL 5.4 GLOSSARY OF TERMS The following glossary is general to all the manufacturer’s products and may thus contain terms which are not appli- cable to your particular unit. In particular, many of the terms are relevant only to configurable recorders. Alarm A function which is triggered when an input signal or a signal derived from it reaches a certain value (absolute or deviation alarms) or changes faster than a specified rate (rate-of-...
  • Page 74 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Derived channel A ‘pseudo’ channel which contains the results of maths pack operations so they can be traced on the chart, logged, used in other calculations etc. Derived Variable (DV) The result of one or more input channel or derived channel being acted upon by a math- ematical function (e.g.
  • Page 75 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Maths functions (Cont.) Constant Square root Log base 10 Latching maximum Switch Copy Channel average Rate of change Continuous maximum High select Group average Sample and hold Polynomial Low select Subtract Rolling average Channel minimum Relative humidity Trace generator...
  • Page 76 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Span Span has two common meanings: the highest (or outer) grid of the chart, or the value given by (maximum value - minimum value). The two meanings are identical where the mini- mum value is zero. Trace The line produced on the chart or display screen showing the value of the process variable being measured.
  • Page 77: Annex A Technical Specification

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Annex A TECHNICAL SPECIFICATION Section Page A1 TECHNICAL SPECIFICATION (RECORDER) ......A - 2 A2 TECHNICAL SPECIFICATION (INPUT BOARD) ......A - 3 A3 TECHNICAL SPECIFICATION (RELAY BOARD) ......A - 4 INSTALLATION CATEGORY AND POLLUTION DEGREE This product has been designed to conform to BS EN61010 installation category II and pollution degree 2.
  • Page 78: A1 Technical Specification (Recorder)

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL A1 TECHNICAL SPECIFICATION (Recorder) Board types (I/O) Universal input board, 6-Changeover relay output board, 4-Channel analog output (retransmision) board Options (See options manual) Host Communications Memory Card Transmitter Power Supply Controllers (see also separate controller manual) Also Case Heater (not described) Environmental Performance Temperature limits...
  • Page 79: A2 Technical Specification (Input Board)

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL A2 TECHNICAL SPECIFICATION (Input board) General Termination Terminal block Maximum number of inputs Six. ±38mV, ±150mV, ±1V, ±10V Input ranges Input types DC Volts, dc millivolts, dc milliamps (with external shunt), thermocouple, 2 / 3-wire resistance temperature detector (RTD), Ohms, Contact closure (not channel 1) (Minimum contact closure = 500msec) Input type mix Freely configurable...
  • Page 80: A3 Technical Specification (Relay Board)

    MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL A2 TECHNICAL SPECIFICATION (Input board) (Cont.) Thermocouple data Temperature scale ITS90 1.7nA on ±38mV range, 8nA on all other ranges Bias current Cold junction types Off, internal, external, remote CJ error 1˚C max; instrument at 25 ˚C CJ rejection ratio 50:1 minimum Remote CJ...
  • Page 81 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Index C (Cont.) Absolute alarms ............. 4 - 16 Character set ............4 - 3 Adaptive recording ..........4 - 10 Chart Adjust Adjust ..............3 - 8 Chart ..............3 - 8 Align with time datum ..........
  • Page 82 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL Embedded sequences ........... 4 - 22 Open/closed text ............ 4 - 14 Entering Operation Introduction. See Section 2 Configuration menus ........... 2 - 5 Numeric values ............ 2 - 6 Operator Text ..............4 - 3 Access to configuration ......
  • Page 83 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL (Cont.) Static electricity ............i - 4 System error ............3 - 7 Channel .............. 4 - 14 Instrument ............4 - 8 Test waveform selection ........4 - 14 Text entry ..............4 - 3 Time Inclusion in messages ........
  • Page 84 MULTIPOINT CIRCULAR-CHART RECORDER INSTALLATION AND OPERATION MANUAL This page is deliberately left blank Index HA250385 Page 4 Issue 2 Mar 98...
  • Page 85 Inter-Company sales and service locations Australia Great Britain Korea Eurotherm Pty. Limited. Eurotherm Recorders Limited, Eurotherm Korea Limited, Suite # 903 P.O. box 6764 Baulkham Hills BC, Dominion Way, Daejoo Building, Baulkham Hills, Worthing, 132-19, Chungdam-Dong, NSW 2153 West Sussex BN14 8QL Kangnam-Ku, Telephone: 01 903 205222 Seoul, 135-100...

Table of Contents