Ampac; is approved for release by written authorisation of Ampac; or is not designated by Ampac in writing or by appropriate stamp or legend to be of a secret, confidential or proprietary nature. This Agreement will be binding upon and inure to the benefit of the parties hereto, and their respective successors and assigns.
Testing Ampac smoke detectors 2.1.1 Smoke detectors are tested with aerosol test gas, part number 204-0014, which may only be used in conjunction with the Ampac smoke detector test applicator part number 204- 0004. 2.1.2 The Ampac ‘Testifire’ unit, part numbers 204-0025, 204-0028 and 204-0029, used in conjunction with the relevant smoke capsule may also be used.
2.2. Testing rate of Rise Detectors (<90ºC) 2.2.1 Rate of rise heat detectors with fixed tempeatures up to 90° C are tested with the Ampac Cordless Heat Detector Tester, part number 204-0017. 2.2.2 Heat detectors with classifications above 90° C (i.e. Series 65 CS/Series 60 Range 2/XP95 High Temperature Heat Detectors) may require the use of the Ampac mains powered heat detector tester, part numbers 204-0005 (240V).
Ampac smoke detector test applicator part number 204- 0004. 2.3.2 If the Multisensor is in ‘heat only’ mode (Mode 5) then it should be tested using the Ampac cordless heat detector tester, part number 204-0017.
2.4. Testing Discovery CO Detector 2.4.1 Use Ampac CO test gas part number 204-0020, which may be used in conjunction with the Ampac smoke detector test pole part number 204-0004. 2.4.2 The Ampac ‘Testifire’ unit part number 204-0025, 204-0028 and 204-0029, used in conjunction with the relevant CO capsule may also be used.
Page 8
*Note 2: Discovery detectors may take up to 40 seconds to activate. *Note 3: Discovery CO detectors may take over 60 seconds to activate dependent on setting. Testifire (Smoke, Heat and CO) 204-0025, 204-0028 and 204-0029 204-0014 Aerosol test Gas (Solo A3)
The case can be cleaned with a dampened cloth with a solution of washing up liquid. Image A - cleaning a detector with a air pressure canister UNCONTROLLED DOCUMENT NOTE: Due to Ampac’s commitment to continuous improvement specifications may change without notice. MAN3069-2 Page 7...