Cleaning, Maintenance and
Functional Test Procedures
MAN3069-2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 204-0025 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Ampac 204-0025

  • Page 1 Ampac Detectors Cleaning, Maintenance and Functional Test Procedures MAN3069-2...
  • Page 2: Table Of Contents

    Table Of Contents Page No Non Disclosure Agreement ................. 1 Functional test Procedures for Ampac Smoke and Heat Detectors ..2 2.1. Testing Ampac smoke detectors ................2 2.2. Testing rate of Rise Detectors (<90ºC) ..............3 2.3. Testing Multisensor Detector ................4 2.4.
  • Page 3: Non Disclosure Agreement

    Ampac; is approved for release by written authorisation of Ampac; or is not designated by Ampac in writing or by appropriate stamp or legend to be of a secret, confidential or proprietary nature. This Agreement will be binding upon and inure to the benefit of the parties hereto, and their respective successors and assigns.
  • Page 4: Functional Test Procedures For Ampac Smoke And Heat Detectors

    Testing Ampac smoke detectors 2.1.1 Smoke detectors are tested with aerosol test gas, part number 204-0014, which may only be used in conjunction with the Ampac smoke detector test applicator part number 204- 0004. 2.1.2 The Ampac ‘Testifire’ unit, part numbers 204-0025, 204-0028 and 204-0029, used in conjunction with the relevant smoke capsule may also be used.
  • Page 5: Testing Rate Of Rise Detectors (<90ºc)

    2.2. Testing rate of Rise Detectors (<90ºC) 2.2.1 Rate of rise heat detectors with fixed tempeatures up to 90° C are tested with the Ampac Cordless Heat Detector Tester, part number 204-0017. 2.2.2 Heat detectors with classifications above 90° C (i.e. Series 65 CS/Series 60 Range 2/XP95 High Temperature Heat Detectors) may require the use of the Ampac mains powered heat detector tester, part numbers 204-0005 (240V).
  • Page 6: Testing Multisensor Detector

    Ampac smoke detector test applicator part number 204- 0004. 2.3.2 If the Multisensor is in ‘heat only’ mode (Mode 5) then it should be tested using the Ampac cordless heat detector tester, part number 204-0017.
  • Page 7: Testing Discovery Co Detector

    2.4. Testing Discovery CO Detector 2.4.1 Use Ampac CO test gas part number 204-0020, which may be used in conjunction with the Ampac smoke detector test pole part number 204-0004. 2.4.2 The Ampac ‘Testifire’ unit part number 204-0025, 204-0028 and 204-0029, used in conjunction with the relevant CO capsule may also be used.
  • Page 8 *Note 2: Discovery detectors may take up to 40 seconds to activate. *Note 3: Discovery CO detectors may take over 60 seconds to activate dependent on setting. Testifire (Smoke, Heat and CO) 204-0025, 204-0028 and 204-0029 204-0014 Aerosol test Gas (Solo A3)
  • Page 9: Cleaning Instructions For Optical Smoke And Multisensor Detectors

    The case can be cleaned with a dampened cloth with a solution of washing up liquid. Image A - cleaning a detector with a air pressure canister UNCONTROLLED DOCUMENT NOTE: Due to Ampac’s commitment to continuous improvement specifications may change without notice. MAN3069-2 Page 7...