GV D1092S Instruction & Safety Manual

GV D1092S Instruction & Safety Manual

Sil 3 relay output module

Advertisement

Quick Links

D1092S - D1092D
INSTRUCTION & SAFETY MANUAL
SIL 3 Relay Output Module
DIN-Rail Models D1092S, D1092D
D1092 - SIL 3 Relay Output Module
ISM0091-11

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the D1092S and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for GV D1092S

  • Page 1 D1092S - D1092D INSTRUCTION & SAFETY MANUAL SIL 3 Relay Output Module DIN-Rail Models D1092S, D1092D D1092 - SIL 3 Relay Output Module ISM0091-11...
  • Page 2 Function: 1 or 2 totally independent and isolated relay for safety related circuits, provides isolation between input and output. D1092S: SIL 3 Safety Function for NE load (de-energized in safe state) is available at Terminal Blocks 1-2; in this case, the safety function is met when the relay is de-energized (open contact).
  • Page 3 Ordering information Model: D1092 1 channel DIN-Rail accessories: DIN rail stopper MOR016 2 channels Front Panel and Features  SIL 3 according to IEC 61508:2010 Ed. 2 for Tproof = 14 / 20 years (≤10% / >10 % of total SIF) with NE Load. ...
  • Page 4 L o a M O D E L D 1 0 9 2 L o a In 2 Out 2-B ND Load MODEL D1092S Out 1-A NE Load In 1 Out 1-B ND Load Relay contact shown in de-energized position To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram.
  • Page 5 Description: Input Signal from PLC/DCS is normally High (24 Vdc) and is applied to pins 13-14 or 9 - 11 (D1092S or 1st ch. of D1092D) and pins 15-16 or 10 - 12 (2nd ch. of D1092D) in order to Normally Energize (NE) the internal relays.
  • Page 6 Description: Input Signal from PLC/DCS is normally Low (0 Vdc) and is applied to pins 13-14 or 9 - 11 (D1092S or 1st ch. of D1092D) and pins 15-16 or 10 - 12 (2nd ch. of D1092D) in order to Normally De-energize (ND) the internal relays.
  • Page 7 Operation D1092 relay modules are suitable for the switching of safety related circuits, providing isolation between the input and output contacts. D1092S provides 1 SPST contact for normally energized (NE) loads and 1 SPST contact for normally de-energized (ND) loads. D1092D provides 2 SPST contacts for normally energized (NE) loads and 2 SPST contacts for normally de-energized (ND) loads.
  • Page 8 “9” and “10” (for positive input duplication) and a wired jumper between terminals “11” and “12” (for negative input duplication). For Model D1092S, in case of NE loads, the terminals “1” and “2” are the two poles of relay output contact used to enable or disable the load circuit. Generally, the relay contact is used to break positive or negative supply line of load circuit.