Carrier CPHEATER001A00 Installation Instructions Manual page 12

Electric cooling and heat pump units

Advertisement

Table 6B — Standard Efficiency Electric Cooling Unit Electric Heater Packages — 208/240 V, 3-Phase, 60 Hz
ELECTRIC HEAT/
CONNECTION
UNIT
SINGLE-POINT
SIZE
WIRING KIT
CPHEATER
030
007A00
008A00
007A00
036
008A00
009A00
007A00
042
008A00
009A00
007A00
048
008A00
009A00
007A00
060
008A00
009A00
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
MCA
— Minimum Circuit Amps
NEC
— National Electrical Code (U.S.A. Standard)
Table 6C — Standard Efficiency Electric Cooling Unit Electric Heater Packages — 480 V, 3-Phase, 60 Hz
ELECTRIC HEAT/
CONNECTION
UNIT
SINGLE-POINT
SIZE
WIRING KIT
CPHEATER
010A00
036
011A00
012A00
010A00
042
011A00
012A00
010A00
048
011A00
012A00
010A00
060
011A00
012A00
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
MCA
— Minimum Circuit Amps
NEC
— National Electrical Code (U.S.A. Standard)
ELECTRIC HEAT
(kW)
DIAGRAM
(Fig. No.)
208 V
240 V
30
7.5
10.0
30
11.3
15.0
30
7.5
10.0
30
11.3
15.0
30
13.1
17.5
30
7.5
10.0
30
11.3
15.0
30
13.1
17.5
30
7.5
10.0
30
11.3
15.0
30
13.1
17.5
30
7.5
10.0
30
11.3
15.0
30
13.1
17.5
ELECTRIC HEAT
(kW)
DIAGRAM
(Fig. No.)
480 V
32
10.0
32
15.0
32
17.5
32
10.0
32
15.0
32
17.5
32
10.0
32
15.0
32
17.5
32
10.0
32
15.0
32
17.5
HEATER
UNIT ONLY
FLA
Max
208 V 240 V MCA
Fuse
HACR
15.5
25
20.9
24.1
31.3
36.1
18.8
30
20.9
24.1
31.3
36.1
36.5
41.0
22.9
35
20.9
24.1
31.3
36.1
36.5
41.0
25.9
40
20.9
24.1
31.3
36.1
36.5
41.0
33.0
50
20.9
24.1
31.3
36.1
36.5
41.0
NOTE: In compliance with NEC requirements for multimotor and com-
bination load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
UNIT ONLY
HEATER
FLA
Max
MCA
Fuse/HACR
9.2
10
12.2
18.1
21.1
10.8
15
12.2
18.1
21.1
13.7
20
12.2
18.1
21.1
16.8
25
12.2
18.1
21.1
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.
2. This unit must be supplied from a 480 v, 3-phase power supply
with a maximum voltage to ground of 300 v.
12
MIN CIRCUIT AMPACITY
FOR WIRE SIZING
OR HACR BRKR
208 V
240 V
208 V
28.6
32.6
41.6
47.7
29.6
33.6
42.6
48.7
49.1
54.8
31.1
35.1
44.1
50.2
50.6
56.3
32.3
36.3
45.4
51.4
51.8
57.5
34.6
38.6
47.6
53.7
54.1
59.8
MIN CIRCUIT AMPACITY
FOR WIRE SIZING
OR HACR BRKR
480 V
17.0
24.3
28.1
17.8
25.1
28.8
18.1
25.5
29.2
19.3
26.6
30.3
MAX FUSE
240 V
30
35
45
50
30
35
45
50
50
60
35
40
45
60
60
60
40
40
50
60
60
60
50
50
50
60
60
60
MAX FUSE
480 V
20
25
30
20
30
30
20
30
30
25
30
35

Advertisement

loading

This manual is also suitable for:

Cpheater020a00