CENTRONIK MODULATING DUTY
USERS MANUAL
V A L V E
C O N T R O L

Advertisement

loading

Summary of Contents for Centork Centronik

  • Page 1 CENTRONIK MODULATING DUTY USERS MANUAL V A L V E C O N T R O L...
  • Page 3: Table Of Contents

    The actuator is an electrical device, therefore you should take into account the EN 60204, Directive 73/23/ECC safety standars. The centork electric actuators must be handled with care and caution. Centronik Motor...
  • Page 4: Electric Actuators Modulating Duty

    In the LOCAL mode, the Centronik modulating duty only follows the front panel pushbuttons operation, the same as in the Centronik On/Off Duty. In the REMOTE mode, the operation is made via the remote inputs received through the users connector, or via RS-485 serial line.
  • Page 5 "Up" pushbutton This is the pushbutton used to move up through the menu in programming mode. Indicator display This is the display used to communicate with the CENTRONIK. The displaying corresponds to 99% and to 100%. Centronik modulating duty users manual...
  • Page 6: Electric Connection

    Fasten the 4 screws crosswise. Tighten cable glands to ensure enclosure IP67 (IP68 on request). ¹ The cable glands are not supplied with the Standard version. Page 4 Centronik modulating duty users manual...
  • Page 7: Switches Configuration

    CENTORK actuators are provided with thermoswitches mounted in the windings of the motor. The protection of the motor is only achieved with a proper connection for these thermostats. Centork guarantee for the motor is not valid if this connection is not properly done.
  • Page 8: Modulating Parameters Setting Procedure

    4 - 20 mA. - SW6 : This is the switch used to indicate to the CENTRONIK unit the way the TPS card will be adjusted (4-20 mA or 0-20 mA). It´s important to configure it properly, otherwise, the CENTRONIK will not operate correctly.
  • Page 9 If at the second try the correct password is not introduced, the CENTRONIK leaves programming mode and the state of the valve is displayed again.
  • Page 10 For remote outputs repeat the procedure previously described. The factory default values for exits are As standard. the CENTRONIK is supplied without relays. The output characteristic is 24 V /100 mA(max.load capacity). If relays are supplied, the outputs are potential free contacts.
  • Page 11 In this submenu, the operation of the actuator when receiving the ESD emergency signal, is configured. When the signal is received, the CENTRONIK will ignore all the securities except the security selection made by the user, the motor thermoswitches or the torque micro switches.
  • Page 12 The ESD signal will only be received in the remote mode. The CENTRONIK will then cancel any operation that it could be doing. It is activated with a logic level “0”; in this case this is done by joining the input ESD with the pin number 19.
  • Page 13 All these data can be obtained through the serial line. For more information refer to "Centronik operation. Serial line" brochure. 5.16. Change of password. Each time we go through this section, the CENTRONIK switches on L1, L2, L3, L4 and L5 in red colour. will be displayed, press choose between .
  • Page 14: Modulating Duty Centronik Operation

    "Centronik operation. Serial line" brochure. The CENTRONIK software has a "movement detection" funtion. If during the next 6 seconds after the last order no shaft movement is detected the unit will stop the operation. After correcting the problem, the STOP pushbutton be pressed to reset the unit.
  • Page 15 Yeserías, 41- E 28005 MADRID Tfno.: 34 91 474 62 22 - Fax : 34 91 474 12 93 E-mail sales@centralair.es http://www.centork.com AUTOMAIR NORTE LDA. Rua Marqués de Soveral, 2-A - P1700 LISBOA - Tfno.: 351 (01) 848 93 96 - Fax : 351 (01) 848 92 02...