Download Print this page

Greenheck Vari-Green Quick Start Manual page 2

Single/three phase motor

Advertisement

Quick Start Guide
Single/Three Phase Vari-Green
Step 6
Review the Installation, Operation and Maintenance
Manual for the fan for any specific installation
questions. The manual is shipped with the fan,
and can also be found at www.greenheck.com or
by scanning the QR code located within the drive
compartment.
Electrical Data
110 Volt Units, 99-126 V
Supply Voltage Range
230 Volt Units, 180-264 V
400 Volt Units, 342-528 V
5kA Without Fused Disconnect
Short Circuit Capacity
100kA With Fused Disconnect
Control Terminal Wiring
Maximum Size
0.05-0.5mm2 / 20-26 AWG
RL-1 Relay
Relay N.O. Contact
250VAC, 6A/30VDC, 5A
Motor Enclosure
Totally Enclosed Fan Cooled, IP54
Motor
®
WARNING
Do not remove the drive cover for wiring or
periodic inspections while power is applied or
the unit is in operation. Electric shock may occur
from the exposed terminals.
Wait at least 1 minute after disconnecting the
input power before performing any wiring tasks
and/or periodic inspections of the drive.
Operate the Vari-Green motor and control
devices with dry hands.
Do not use this device if power or motor cable is
damaged.
As this is a permanent magnet motor, this motor
will generate voltage when the shaft is rotated.
Shaft must be locked out for safe servicing.
CAUTION
Disconnect the input power if the Vari-Green
motor has been damaged. Failure to do so
may result in fire and/or secondary damage or
accidents.
Do not touch the Vari-Green motor immediately
after shutting down or disconnecting it. It can
remain hot for a few minutes. Bodily injuries such
as skin-burn or damage may occur.
Do not apply power to a damaged Vari-Green
motor or to a Vari-Green motor that is missing
parts.
Do not allow lint, paper, wood chips, dust,
metallic chips or other foreign material into the
drive as it may cause fire or accident.
Vari-Green Controls all use a 0-10 VDC control signal
to provide a speed reference to Vari-Green Motors.
See below for typical Vari-Green wiring. Reference
the individual controls Installation, Operation and
Maintenance Manual for programing, wiring and
troubleshooting of that control.
484390 • Single/Three Phase Vari-Green Motor, Rev. 2, November 2020 • Copyright © 2020 Greenheck Fan Corp.
Vari-Green Controls
+24V, 100mA
D1, ENABLE
GND
POWER
2D
V+
IN
D3/A2
+10VDC
A1
COMMON
CONTROL OUT
REF OUT
AO/DO OUTPUT
DIGITAL
COMMON
OUTPUT
MODBUS RTU–
OVERRIDE
REMOTE SET
MODBUS RTU+
POINT
CONSTANT PRESSURE / AIRFLOW
CONTROL – INTEGRAL TRANSDUCER

Advertisement

loading