User Manual PBLH™ Series PBLH-12R0/87WT PBLH-12R0/100WT PBLH-12R0/112WT PBLH-10R8/150WT 7520 Mission Valley Road ● San Diego, CA 92108-4400 ● USA ● Tel: 619.398.9700 ● Fax: 619.398.9777 ● www.tecategroup.com ...
If the unit is found to be defective or any parts are missing, please contact your supplier. Handling & Safety 2.2. Tecate ultracapacitor modules are designed to provide years of trouble-free operation. Proper handling is required to avoid damage to the module. The following handling precautions should be observed: ...
HIGH VOLTAGE HAZARD Never touch the power terminals as the module can be charged and cause fatal electrical shocks. Always check that the module is fully discharged before manipulating the module. Please refer to the step by step instructions below for the manual discharge procedure. A fully discharged module may have a “bounce back voltage”...
Mounting points: (4x) M4x8 T20 drive screws Maximum torque: 1.13 Nm Figure 2: PBLH™ Mounting Hole Locations Dimensional spacing of the mounting holes for the modules is shown in Figure 2. To properly install please do not exert any bending or twisting torque to the module enclosure. Ensure that the module’s mounting points are co-planar within ±1 mm.
Thermal Performance 3.3. It should be noted that these modules are not intended for high cycling applications. Should there be an interest in higher cycling applications, please consult Tecate Engineering. Figure 4: Possible Parallel Connection Figure 3: Possible Series Connection ...
The maximum recommended operating voltage for a series string is 48VDC. For series strings higher than 48VDC please check with Tecate Engineering at: UCEngineering@tecategroup.com. When several modules are connected in series for operating at higher system voltages, care must be taken to ensure proper creepage and clearance distances in compliance with appropriate national and local safety standards for electrical equipment.
6.4. Check electrical connections for proper torque 6.4.1 Reason – avoid false signals, shock hazards, and high-resistance connections 6.4.2 Frequency 6.4.2.1 High Vibration Environments (6 months) 6.4.2.2 Low Vibration Environments (12 months) 7. Storage: The discharged module can be stored in the original package in a dry place. Discharge a used module prior to storage or shipment.