Download Print this page

A. Mallios Pamal WP Quick Start Manual

Advertisement

Quick Links

TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES Ni-Cd
(
)
BATTERY PROTECTION
INDICATIONS CONTROLS
-
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used in places where
emergency luminaires are needed.
Each luminaire must be permanently connected
to mains power supply In normal operation the
led strip lights and the battery is charging. In
case of a mains power supply failure the
luminaire will light the led strip automatically in
emergency mode.
supply is restored the device turns to normal
operation.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel
only
.
2.
The device must be connected to the mains
power supply thru a fuse dependent by the total
amount of the line's power load
3.
It is sugested to check every month the
indication LED for battery charging, and by
pushing the TEST button (see the paragraph 8
on page 2), to check the emergency cirquit. The
lamp should light as long as the TEST button is
pressed
. In the opposite condition contact the
installer.
4.
It is sugested to check every 6 months the
minimum autononous duration by disconnecting
the mains power supply Count the time that the
led strip lights and in case of less time than the
minimum autonomous duration the battery must
be replaced. If the measured time is
4.8V/1.5Ah
.
When the
mains
power
.
.
Pamal WP
220-240V AC/50-60Hz
4 VA
From overcharge and full discharge
Charge indication LED TEST button
6 power LED's
EN 60598-1, EN 60598-2-22
Bayblent F 3010 transparent polycarbonate
R
355 x 145 x 73 mm
3 years
(1
considerably less than the minimum autonomous
duration
contact the installer.
led strip replacement, these must be replaced by
parts of the same type
5.
In case of inactive use for a period greater
than 2 months, disconnect the battery by pulling
out the battery's connector.
6. I s not allowed to discard batteries in to
t i
common trash bins, they must be discarded
only
in battery recycling points. Do not
incinerate.
INSTALLATION
To install the luminaire follow the installation
instructions in page 2.
NOTE:
LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
0: Non Maintained
A: Including test device
*90: 90min duration
180: 180min duration
5 VA
4.8V/3Ah
,
24h
180min
370lm
IP 65
o
0 to 40 C
Up to 95%
,
1020gr.
year for the battery
)
In case of battery or
.
6 VA
4.8V/4Ah(Ni-MH)

Advertisement

loading

Summary of Contents for A. Mallios Pamal WP

  • Page 1 TECHNICAL CHARACTERISTICS Pamal WP OPERATION VOLTAGE 220-240V AC/50-60Hz MAXIMUM POWER CONSUMPTION 4 VA 5 VA 6 VA BATTERIES Ni-Cd 4.8V/1.5Ah 4.8V/3Ah 4.8V/4Ah(Ni-MH) From overcharge and full discharge BATTERY PROTECTION Charge indication LED TEST button INDICATIONS CONTROLS CHARGING TIME 180min MINIMUM AUTONOMOUS DURATION ILLUMINATION SOURCE 6 power LED’s...
  • Page 2 INSTALLATION INSTRUCTIONS Remove the diffusor Place simultaneously 2 flat blade screwdrivers and pull up gently the reflector. Install the included plastic cover in to the unused hole and install the base plastic (with the included mounting screws and plugs). Instal the cable gland and pass the round cable thru. Place the battery’s connector to the corresponding connector on the P.C.B Connect the mains as shown in figure Install the included tie (if needed) to fasten securely the power cables.