controlair 400 Installation, Operation And Maintenance Instructions

controlair 400 Installation, Operation And Maintenance Instructions

General service pressure regulator

Advertisement

INTRODUCTION

The Type-400 General Service Pressure Regulator is an air or gas service unit designed for instrumentation and general purpose use.
This unit is reliable and has excellent stability and repeatability. In addition, all units are irridite coated and finished with baked epoxy
paint for corrosion resistant construction necessary for harsh industrial environments. Maximum allowable inlet pressure is 250 psi.
Operating temperatures are 0 to 160
pressure protection. Note: Non-relieving version does not provide internal relief. To avoid exceeding outlet pressure limits in service, a
pressure-relieving or pressure-limiting device should be provided.

SPECIFICATIONS

Port Size
Output Ranges
Maximum Supply Pressure
Mounting
Flow Capacity
Exhaust Capacity
Sensitivity
Air Consumption
Effect of Supply Pressure Variation
Temperature Limits
Weight

INSTALLATION

Clean all pipelines to remove dirt and scale before installation. Apply a minimum amount of pipe compound to the male threads of the
fitting only. Install the regulator as close as possible to the instrument or tool it is to service. Start with the third thread back and
work away from the end of the fitting to avoid contaminating the regulator. Install the regulator in the air line. The words "IN" and "OUT"
are cast into the body to indicate the direction of flow. Tighten all connections securely. If a lubricator is to be used in the system, install
it downstream.
Only qualified personnel should install or service a regulator. Regulators should be installed, operated, and maintained in
WARNING:
accordance with international and applicable codes and regulations, and ControlAir instructions. If the regulator vents fluid or a leak
develops in the system, it indicates that service is required. Failure to take the regulator out of service immediately may create a
hazardous condition. Personal injury, equipment damage, or leakage due to escaping fluid or bursting of pressure-containing parts may
result if this regulator is over pressured or is installed where service conditions could exceed the limits given in the Specifications section,
or where conditions exceed any rating of the adjacent piping or piping connections. To avoid such injury or damage, provide pressure-
relieving or pressure-limiting devices (as required by the appropriate code, regulation, or standard) to prevent service conditions from
exceeding limits. Additionally, physical damage to the regulator could result in personal injury and property damage due to escaping fluid.
To avoid such injury and damage, install the regulator in a safe location. The internal relief valve in the Type-400 regulators does not
provide full overpressure protection. The internal relief valve is designed for minor seat leakage only.

OPERATION

Prior to turning on supply air, back out adjusting screw until there is no compression on the range spring. After turning supply pressure
on, turn the adjusting screw clockwise until the desired output pressure is reached.
To avoid personal injury resulting from sudden release of pressure, isolate the regulator from all pressure before attempting
WARNING:
disassembly.
0
F. The Type-330 has low capacity internal relief which provides very limited down-stream over
1/4" NPT
0-10 psig (0-0.7 BAR), 0-30 psig (0-2 BAR), 0-60 psig (0-4 BAR), 0-120 psig (0-8 BAR)
250 psig (17 BAR)
Pipe, bracket or panel
20 scfm (660 Nl/min) at 100 psig (7 BAR) supply with 20 psig(1.4 BAR) output
0.1 scfm (3 Nl/min) with downstream pressure 5 psig (0.3 BAR) above set point
1" (2.5 cm) of water
Less than 5 scfh (2.5 Nl/min)
Less than 0.2 psig (0.01 BAR) for 25 psig (1.7 BAR) change
0
0
-20
F to 160
F (-29
0.84 lb (0.38 kg)
www.controlair.com 
General Service Pressure Regulator
0
0
C to 71
C)
Installation, Operation, and
Maintenance Instructions
TYPE 400

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 400 and is the answer not in the manual?

Questions and answers

Summary of Contents for controlair 400

  • Page 1 Additionally, physical damage to the regulator could result in personal injury and property damage due to escaping fluid. To avoid such injury and damage, install the regulator in a safe location. The internal relief valve in the Type-400 regulators does not provide full overpressure protection.
  • Page 2 ControlAir LLC recommended usages. ControlAir LLC’s liability is limited to repair of, refund of purchase price paid for, or replacement in kind of, at ControlAir LLC’s sole option, any products proved defective. ControlAir LLC reserves the right to discontinue manufacture of any product or change product materials, design or specifications without notice.

Table of Contents