INSTALLATION AND OPERATION MANUAL MODEL KBPW-240D KB Part No. 8401 (Black Case) • Part No. 8402 (White Case) NEMA 4X, IP-65 PWM DC Motor Speed Control For PM and Shunt Wound Motors Rated 7.5 Amps DC, 11.5 Amps AC @ 115/230 VAC STOP ™...
Electrical Hazard Warning Symbol: Failure to observe this warning could result in electrical shock or electrocution. Operational Hazard Warning Symbol: Failure to observe this warning could result in serious injury or death. SAFETY WARNING! Please read carefully This product should be installed and serviced by a qualified technician, electrician, or electrical maintenance person familiar with its operation and the hazards involved.
Optional accessories include On/Off AC Line Switch, FWD-BRK-REV Switch, Run-Stop-Jog Switch, Signal Isolator, and Anti-Plug Reversing Module. Quick-connect terminals are provid- ed for easy installation of all optional accessories. The control is available in black finish (P/N 8401) and FDA approved white finish (P/N 8402). STANDARD FEATURES •...
D. Motor Current – Jumper J2 is factory set for 7.5 Amp motors. For lower current motors, set jumper J2 to the corresponding motor current as described in Section IVB, on page 10. Note: The factory setting for Current Limit is 150% of the nominal current setting (example: if jumper J2 is set to “5A”...
FIGURE 1 – CONTROL LAYOUT (Illustrates Factory Setting of Jumpers and Approximate Trimpot Settings) To LED Board ACCEL DECEL START/STOP SWITCH KBPW-240D CON1 BLACK INH1 TCL NTCL INH2 WHITE START STOP RELAY VIOLET ORANGE WHITE MAIN SPEED POTENTIOMETER 180V WHT WHT CON2 ACCEL DECEL...
III. WIRING INSTRUCTIONS FIGURE 3 – POWER CONNECTION WARNING! Read Safety Warning, on page 1, before using this control. Disconnect the AC line before wiring. Note: To avoid erratic operation, do not bundle AC line and motor wires with wires from signal following, start/stop switch, inhibit, or any other signal wires.
Note: Do not connect motor armature FIGURE 4 – FULL VOLTAGE FIELD leads to F1 and F2 terminals. Do not use F1 and F2 terminals for PM motors. D. Full Voltage Field Connection (Shunt Wound Motors Only) – Wire the motor field leads to F1 (+) and F2 (-) terminals of TB2 as shown in Figure 4 &...
in the front cover. Connect the FIGURE 7A – REMOTE 3-WIRE START/STOP SWITCH WITH NORMALLY OPEN START CONTACT remote Start/Stop switch wires to AND NORMALLY OPEN STOP CONTACT START (momentary), COM (common), and STOP (constant) terminals as shown in Figure 7A. Start MOMENTARY START...
Note: If an isolated signal voltage is not available, an FIGURE 10 – INHIBIT CIRCUIT optional signal isolator can be installed (KBSI-240D, INHIBIT P/N 9431). Connect the isolated signal voltage to P2 (CLOSE TO STOP) (+) and P1 (-) terminals. Adjustment of the MIN trim- (OPEN TO RUN) pot may be necessary to achieve a 0 Volt DC output.
A. Motor Voltage Selection (J1) – Jumper FIGURE 14 – MOTOR VOLTAGE SELECTION J1 is factory set to “90V” position for 90 J1 Set for 90 Volt Motors Volt SCR rated motors (or 130 Volt PWM (Factory Setting) J1 Set for 180 Volt Motors rated motors).
C. Timed and Non-Timed Current Limit FIGURE 17 – CURRENT LIMIT MODE SELECTION Selection (J3) – Jumper J3 is factory set to “TCL” position for timed current limiting J3 Set for TCL Mode operation. See Figure 17. For non-timed (Timed Current Limit) J3 Set for NTCL Mode current limiting operation, set jumper J3 (Factory Setting)
E. Run Relay Output Mode Selection (J5) FIGURE 19 – DC TACH-GENERATOR WITH ADDITION OF R – Jumper J5 is factory set to “NO” position for normally open relay output at TB4. For normally closed relay output, set jumper J5 to “NC” position. See Figure 20. F.
potentiometer is fully counterclockwise. To start the control, momentarily set the Start/Stop switch to “START” position and release it. The STOP LED should no longer illuminate. The motor should begin to rotate, as the main speed potentiometer is rotated clockwise. Note: If the motor rotates in the incorrect direction, it will be necessary to disconnect the AC line, reverse the motor leads, and repeat the startup procedure.
E. Jog Speed (JOG) – Sets “jog” speed of the motor. The JOG FIGURE 27 – JOG TRIMPOT RANGE trimpot is factory set for 15% of motor base speed, as shown in Figure 27 . For a higher jog setting, rotate the trimpot clockwise.
B. Stop (STOP) – The STOP LED will illuminate yellow when the Start/Stop switch is set to “STOP” position. When AC line is applied, this LED will also be illuminated until the Start/Stop switch is set to “START” position. C. Overload (OL) – The OL LED will illuminate red when the control goes into current limit, indi- cating that the current limit set point has been reached (set by the CL trimpot and the posi- tion of jumper J2).
Page 20
XI. LIMITED WARRANTY For a period of 18 months from the date of original purchase, KB Electronics, Inc. will repair or replace, without charge, devices which our examination proves to be defective in material or workmanship. This warranty is valid if the unit has not been tampered with by unauthorized per- sons, misused, abused, or improperly installed and has been used in accordance with the instructions and/or ratings supplied.