Testing of automation with optical device

Advertisement

22.
Perform various gate manoeuvres and check that the opening and
closing are correctly performed without the inversion of the movement.
23.
Perform further manoeuvres and activate the optical presence
detector, as illustrated in point 17, during the closing manoeuvre (if "FT A"
function) or the opening manoeuvre (if "FT B" function) or both (if "FT C"
function) and ensure that a short inversion occurs and the movement
stops.
24.
Perform additional manoeuvres and during the closure activate the
sensitive edge as indicated in point 18 and check that the foreseen action
is performed such as the inversion of the movement.
25.
The control of the FT210B optical presence sensor (type D),
according to the EN 12445 standard, is performed with the
700x300x200mm test parallelepiped with 3 black faces and 3 polished
white or mirrored faces as indicated in figure 5 and according to chapter 7
of the EN 12445:2000 standard.
26.
The control of the PSPE pressure sensitive device of the FT210B
according to the EN 12445 standard, is performed by measuring the force
at the points foreseen in chapter 5 of the EN 12445 standard, if the
hazardous situations, which have been caused by the movement of the
leaf, have been safeguarded through the limitation of the impact force
(type C).
27.
After verifying all the above points, remove the damper filter from the
glass panel on the RX receiver as shown in figure 6.
28.
Make sure that all casings of the various devices are closed when
testing is complete
Document produced by Nice S.p.a. for installers – All rights reserved