B07S(E)415 / B07S(E)515 / B07PS415 / B07PS515 Instrunction Sheet
(1) Preface
Thank you for purchasing DELTA's DOP-B series. This instruction sheet will be helpful in the installation, wiring and inspection of
Delta HMI. Before using the product, please read this instruction sheet to ensure correct use. You should thoroughly understand all
safety precautions before proceeding with the installation, wiring and operation. Place this instruction sheet in a safe location for
future reference. Please observe the following precautions:
Install the product in a clean and dry location free from corrosive and inflammable gases or liquids.
Ensure that all wiring instructions and recommendations are followed.
Ensure that HMI is correctly connected to a ground. The grounding method must comply with the electrical standard of
the country (Please refer to NFPA 70: National Electrical Code, 2005 Ed.).
Do not disassemble HMI, modify or remove wiring when power is applied to HMI.
Do not touch the power supply during operation. Otherwise, it may cause electric shock.
If you have any questions during operation, please contact our local distributors or Delta sales representatives.
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most
updated version at
http://www.delta.com.tw/ia
(2) Safety Precautions
Carefully note and observe the following safety precautions when receiving, inspecting, installing, operating,
maintaining and troubleshooting. The following words, DANGER, WARNING and STOP are used to mark safety
precautions when using the Delta's HMI product. Failure to observe these precautions may void the warranty!
Installation
Comply with quick start for installation. Otherwise it may cause equipment damage.
Do not install the product in a location that is outside the stated specification for the HMI.
Failure to observe this caution may result in electric shock, fire, or explosion.
Do not install the product in a location where temperatures will exceed specification for
the HMI. Failure to observe this caution may result in abnormal operation or damage the
product.
Please note that this equipment has obtained EMC registration for commercial use. In the
event that it has been mistakenly sold or purchased, please exchange it for equipment
certified for home use.
Do not use this product as an alarm device for disaster early warning that may result in
personal injury, equipment damage, or system emergency stop.
Wiring
Connect the ground terminals to a class- 3 ground (Ground resistance should not exceed
100 ). Improper grounding may result in communication error, electric shock or fire.
Operation
The users should use Delta Screen Editor software to perform editing in Delta's HMI
product. To perform editing and confirming HMI programs without using Delta Screen
Editor software in Delta's HMI product may result in abnormal operation.
To prevent the personal injury and equipment damage, when designing HMI programs,
please ensure that a communication error occurred between Delta's HMI product and the
connecting controller or equipment will not result in system failure or malfunction.
Please be sure to backup the screen data and HMI programs in case they are lost,
accidentally deleted or worse.
Do not modify wiring during operation. Otherwise it may result in electric shock or
personal injury.
Never use a hard or pointed object to hit or strike the screen as doing this may damage the
screen and let the screen has not respond at all, and then cause HMI to work abnormally.
Maintenance and Inspection
Do not touch any internal or exposed parts of the HMI as electrical shock may result.
Do not remove operation panel while power is on. Otherwise electrical shock may result.
Wait at least 10 minutes after power has been removed before touching any HMI terminals
or performing any wiring and/or inspection as an electrical charge may still remain in the
HMI with hazardous voltages even after power has been removed.
Turn the power off before changing backup battery and check system settings after
finishing change. (all data will be cleared after changing battery).
Be sure the ventilation holes are not obstructed during operation. Otherwise malfunction
may result due to bad ventilation or overheating troubles.
Wiring Method
Do not use a voltage that will exceed specification for the HMI. Failure to observe this
caution may result in electric shock or fire.
Remove the terminal block from the HMI before wiring.
Insert only one wire into one terminal on the terminal block.
If the wiring is in error, perform the wiring again with proper tools. Never use force to
remove the terminals or wires. Otherwise, it may result in malfunction or damage.
For the power line that forced to take out, ensure to check wiring again and restart.
Communication Wiring
Comply with communication wiring specification for wiring.
Wiring length should comply with the stated specification for the HMI.
Proper grounding to avoid bad communication quality.
To avoid noise and interference, the communication cable, all power cables, and motor
power cable should be placed in separate conduits.
(3) Pin Definition of Serial Communication
DOP-B07S(E)415 DOP-B07PS415 Series
COM1 Port (Supports Flow Control)
Contact
COM Port
PIN
RS- 232
1
PIN1
2
RXD
3
TXD
4
5
GND
6
7
RTS
8
CTS
9
Note: Blank = No Connection.
COM2 Port (Supports Flow Control)
MODE1
MODE2
COM Port
PIN
RS- 232
RS- 422
1
TXD+
2
RXD
PIN1
3
TXD
4
RXD+
5
GND
GND
6
TXD-
7
RTS
8
CTS
9
RXD-
Note1: Blank = No Connection.
Note2: When COM2 port is used for RS- 232 flow control, i.e. RTS and CTS signals are used for flow control, COM3 port will
become incapable of being used.
Note3: When COM2 port is used for RS- 422 flow control, please refer to the following COM3 Port signals table for pin
assignments. The signals, RTS+ , CTS+ , RTS- and CTS- shown in brackets are the signals used for flow control.
COM3 Port
MODE1
MODE2
COM Port
PIN
RS- 232
RS- 422
1
TXD+ (RTS+ )
2
RXD
PIN1
3
TXD
4
RXD+ (CTS+ )
5
GND
GND
6
TXD- (RTS- )
7
8
9
RXD- (CTS- )
Note1: Blank = No Connection.
Note2: When COM2 port is used for RS- 422 flow control, please refer to the COM3 Port signals table above for pin assignments.
The signals, RTS+ , CTS+ , RTS- and CTS- shown in brackets are the signals used for flow control.
DOP-B07S(E)515 DOP-B07PS515 Series
COM1 Port (Supports Flow Control)
Contact
COM Port
PIN
RS- 232
1
2
RXD
PIN1
3
TXD
4
5
GND
6
7
RTS
8
CTS
9
Note: Blank = No Connection.
COM2 and COM3 Port
MODE1
MODE2
COM Port
PIN
COM2
COM3
COM2
RS- 232
RS- 485
RS- 485
1
D+
2
RXD
PIN1
3
TXD
4
D+
5
GND
GND
6
D-
7
8
9
D-
Note1: Blank = No Connection.
Note2: B05S111 / B07S(E)515/ B07PS515 series models do not support RS- 422 flow control function.
Note3: COM3 is the extension port (COM2 and COM3 share one physical port).
DOP- B07E415 / DOP- B07E515 Ethernet Interface (LAN)
Contact
Ethernet Interface (LAN)
PIN
Ethernet
1
TX+
2
TX-
3
RX+
4
5
6
RX-
7
8
Note: Blank = No Connection.
(4) Parts Names
DOP- B07S(E)415
MODE3
RS- 485
D+
GND
D-
A
C
MODE3
RS- 485
D+
D
GND
D-
1. The definition of the operation LED indicator (Blue) can be determined by the users freely.
DOP- B07S(E)415
MODE3
COM3
COM2
COM3
RS- 485
RS- 232
RS- 422
TXD+
RXD
TXD
A
D+
RXD+
GND
TXD-
B
D-
RXD-
C
D
E
DOP- B07PS415 (Front View)
B
A
: Power LED Indicator
Lights in green when HMI works normally.
: Operation LED Indicator (Blue)
(Note1)
The operation LED indicator blinks in blue when either the communication is carried out or
the data is accessing (please refer to the "Note1" below for explanation).
: Alarm LED Indicator (Red)
The alarm LED indicator blinks in red when one of the alarms is on.
Touch Screen / Display
NOTE
DOP- B07PS415 (Rear View)
D
C
A
B
Power Input Terminal
F
Ethernet Interface (LAN)
COM3
(It is provided with two LED indicators to
G
USB Host
indicate that HMI is in Read or Write status
during the communication process.)
COM2
(It is provided with two LED indicators to
H
Audio Output Interface
indicate that HMI is in Read or Write status
during the communication process.)
COM1
I
Memory Card Slot / Battery
USB Slave
-
-
C
I
H
G
F
E

Advertisement

loading

Summary of Contents for Delta DOP-B07 Series

  • Page 1 B07S(E)415 / B07S(E)515 / B07PS415 / B07PS515 Instrunction Sheet (1) Preface Thank you for purchasing DELTA’s DOP-B series. This instruction sheet will be helpful in the installation, wiring and inspection of Note: Blank = No Connection. Delta HMI. Before using the product, please read this instruction sheet to ensure correct use. You should thoroughly understand all safety precautions before proceeding with the installation, wiring and operation.
  • Page 2 1.5 ~2 times the value of the power consumption. Operation System The content of this quick start may be revised without prior notice. Please consult our distributors or download the most Delta Real Time OS updated version at http://www.delta.com.tw/ia/ 32-bit RISC Micro-controller...

This manual is also suitable for:

Dop-b07s415Dop-b07s515Dop-b07ps415Dop-b07ps515Dop-b07se415Dop-b07se515