Download Print this page

IFAM FAT 2002 Operating Instructions

Fire brigade indicator panel

Advertisement

Quick Links

Ingenieurbüro für Applikation von Mikrocomputern GmbH , Dalbergsweg 1 , D - 99084 Erfurt
( +49-361 / 6 59 11-0
Fire Brigade Indicator Panel (FAT)
Displays and Operating Controls of the FAT
Keys :
Indication level
Alarm / Fault /
Disabled
Message down
Message up
Buzzer OFF / Test
Alarms are immediately indicated on the LCD. Faults and disabled devices are signalled by a flashing common
message LED and have to be called up with keys. The level shown on the LCD is specified by the relevant common
LED display which lights up continuously.
Common LED displays (operating status)
LED
Colour
Power
green
Alarm
red
Fault
yellow
Disabled
yellow
FAT-Operating-Instruction_GB.doc Rev 1.5 Ja 20.01.2006
Fax. +49-361 / 6 46 21 39
Operating Instructions
Fire Brigade Indicator Panel
First
23/03
message
MCP
First floor
127/08
Last
Det. Attic left
message
Indication level
Further messages
Buzzer OFF
Test
Function
ON:
Ready for operation
Flashing: Operating voltage ON, no communication
OFF :
No operating voltage, FAT in programming mode
ON :
Fire alarm(s) present and shown on LCD
Flashing: Fire alarm(s) present but not shown on LCD
OFF :
No fire alarm, FAT in programming mode
ON :
Fault message present and shown on LCD
Flashing: Fault message present but not shown on LCD
OFF :
No fault message, FAT in programming mode
ON :
Disabled device message present and shown on LCD
Flashing: Disabled device message present but not shown on LCD
OFF :
No disabled device message, FAT in programming mode
ifam@ifam -erfurt.de
www.ifam-erfurt.de
Fire
Fire
Common displays
Power
Fire-Alarm
Fault
Disabled
I
LCD plain-text indication :
Line 1-2: first / further message
Line 3-4: last message
The LED of the indicated level
lights up continuously.
Common LED displays :
Power LED :
ON : ready for operation
Flashing: internal fault
Message level LEDs
Alarm / Fault / Disabled :
ON:
Message(s) of level
shown on LCD
Flashing: Message(s) present,
to be called up with keys
F A M
1 / 2

Advertisement

loading

Summary of Contents for IFAM FAT 2002

  • Page 1 Ingenieurbüro für Applikation von Mikrocomputern GmbH , Dalbergsweg 1 , D - 99084 Erfurt F A M ( +49-361 / 6 59 11-0 Fax. +49-361 / 6 46 21 39 ifam@ifam -erfurt.de www.ifam-erfurt.de Fire Brigade Indicator Panel (FAT) Operating Instructions...
  • Page 2 F A M ( +49-361 / 6 59 11-0 Fax. +49-361 / 6 46 21 39 ifam@ifam -erfurt.de www.ifam-erfurt.de Alphanumeric display A message on the alphanumeric display always comprises 2 lines and starts in the first line with zone and detector numbers, which are separated by a slash.