EC Titanium
Input Power & Control Connections
Status LEDs
A1: Red = Trip
A2 A1
Green = Healthy
A2: Yellow = Alarm
Control Terminals
Terminals 1 to 11
Factory defaults settings:
1. Connect a START/STOP switch to Terminal 1
&
2
Close the contact START (enable) the drive
Open the contact STOP (disable) the drive
1
2
Command Input
2. Connect 10k potentiometer on terminals 5, 6, & 7
Vary the speed from 0 to max speed
5
6
7
Speed Reference
RJ45 Port
Remote Keypad & PC Interface
Quick Startup Guide
When delivered, the EC Titanium™ is pre-programmed to run from remote inputs wired to the terminal
strip. This default digital input configuration provides a general purpose I/O setup with a hard wired start /
stop enable, forward / reverse input and a selection between an analog speed reference or preset speed
input.
Parameter 1103 = 0 defines control from the terminal strip (for Keypad Control 1103 =1) and Parameter
9902 = 0 sets up the configuration for the inputs and outputs as shown below.
Step 1
Connect a control switch between the control terminals 1 and 2 and ensure that the contact
is open (drive disabled). Connect a potentiometer (1kΩ min to 10 kΩ max) between terminals
5 and 7 with the wiper to terminal 6 of the control terminal. With the potentiometer set to
zero, switch on the supply to the drive.
Step 2
The status LED is slow flashing green and a connected EC100L Keypad will display STOP.
Close the control switch, terminals 1-2, the drive is now 'enabled' and the output frequency
speed are controlled by the potentiometer. The status LED will change to constant on green.
Step 3
The display shows zero speed in Hertz as
If the display is not showing
potentiometer, the motor will accelerate to the speed set by the potentiometer up to the
value set in parameter 2008 (maximum frequency limit.)
Step 4
Stop the motor, disable the drive by opening the control switch (terminal 1-2).
Terminal Mode (1103=0)
Digital Input Function (9902=0)
Active input across terminal 1 & 2 will cause
the drive to run.
When terminal 3 is open the drive will
operate in the forward direction.
Closing input 3 reverses the commanded
direction.
Closing terminal 4 will force operation at
preset speed 1 (parameter 1202) or function
as a jog command.
Speed Reference Input
Potentiometer
1-10K Ohm Potentiometer
Recommended (2 Watt Min.)
Analog Input
Analog Input Format (parameter 1300)
selects Voltage or Current Source.
Voltage 0-10 or 10-0 Vdc
Current 0-20, 4-20 or 20-4 mA
Quick Start Guide
TM
Motor Connection:
U V W
Factory wired do not disconnect
with the potentiometer turned to minimum.
H 0.0.
H, change it with the navigate key. Adjust the speed using the
2-Wire Forward Reverse
Stop - Run
Forward - Reverse
Analog - Preset 1
Connection Example
0-10V
4-20mA
Common
Remote Keypad ECS100L
Supply Voltage:
- Single phase 115 or 230V
- Three phase 230, 415, 460V
- 50 / 60Hz
- Use inputs L (L1) & N (L2)
for single phase
AC Supply Voltage
L1 L2 L3
Earth
Fuse or MCB
check drive rating
for cable sizing
NOTE: For keypad control set parameter 1103=1 and 9902 to
Keypad Operation
Setting parameter 1103 to a value of 1 enables keypad mode with
forward direction only, while a value of 2 enables keypad mode with
forward and reverse rotation.
Set parameter 1100 to 1 or 3 to enable the drive to start from the set
keypad reference speed.
While the drive is stopped, press the STOP key. The value of the
digital potentiometer will be displayed, indicating the target speed.
Use the UP and DOWN keys to select the required target speed.
Press the STOP key to return to the real time display showing
STOP
speed. To reverse direction, press the START key again.
Keypad Display Screens
Prior to operation the keypad will show
key allows setting the preset speed on the display (H x.x) While
in operation the following displays can be accessed by briefly
pressing the Navigate Key.
1
+24V User Input
2
Digital Input 1
3
Digital Inpu 2
4
Digital Input 3
5
+10 Volts
6
Analog Input
7
0 Volts
5
+10V O/P
6
Analog Input
7
0V
6
Analog Input
7
0V
Used to display real-time information,
NAVIGATE
to access and exit parameter edit
mode and to store parameter changes.
Increase speed in real-time mode or
UP
scroll through values in parameter edit
mode.
Decrease speed in real-time mode or
DOWN
scroll through values in parameter edit
mode.
In normal application, when in Keypad
mode, this button is used to stop a
STOP
running drive. If in trip mode, the key is
used to reset the drive.
When in keypad mode, the button is
START
used to start a stopped drive or to
reverse the direction of rotation.
the desired I/O configuration.
or the START key to start the drive ramping up to the target
 

Drive power applied and
STOP
no Enable or Run signal
Drive Running
Output
H 0
0
.
.
Frequency (Hz)
Motor Current
A 0
0
.
.
(Amps)
Motor Power
P 0
0
.
.
(kW)
Drive Running, Speed Reference = 0
Enable / disable switch open drive will
decelerate to stop and display shows
STOP
A zero reference and enable/disable closed
Stnd by
the display with show H 0.0 (0.0Hz)
>60 seconds at zero speed drive standby
Stnd by
mode
reference
STOP
, pressing the STOP
 
Press Navigate to
select display
Press again to cycle
display
waiting for a speed