Instead of sending and receiving information to and from frequency converters through I/O, you can connect them to a fieldbus. Vacon NX frequency converters can be connected to the RS-485 bus using a fieldbus board. The con- verter can then be controlled, monitored and programmed from the host system.
4 • vacon technical data RS-485 OPTION BOARD TECHNICAL DATA General Connections Interface OPTC2: Pluggable connector (5.08mm) OPTC8: 9-pin DSUB connector (female) Data transfer RS-485, half-duplex method Transfer cable Twisted pair (1 pair and shield) Electrical isolation 500 VDC Communications Modbus RTU As described in document “Modicon Modbus Protocol...
• 5 RS-485 FIELDBUS BOARD LAYOUT AND CONNECTIONS Vacon RS-485 Fieldbus Board is connected to the fieldbus through either a 5-pin pluggable bus con- nector (board OPTC2) or a 9-pin female sub-D-connector (board OPTC8). The communication with the control board of the frequency converter takes place through the stan- dard Vacon Interface Board Connector.
Insert the data cables of both cables into terminals #3 (Line B) and #4 (Line A). Strip the cable at such a distance from the terminal that you can fix it to the frame with the grounding clamp. See 24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com...
0.5 cm to fit in the terminals. See Figure 6. Note: Do this for both bus cables. 1 2 3 4 5 Shield Figure 6. Fix both the cables on the frame with the clamp. See Figure 7. Figure 7. 24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com...
10 • vacon layout and connections Grounding jumper X1 3.3.3 The Grounding jumper X1 on the OPTC8 is used for grounding selection. If position ON is selected it means that the D-sub connector PIN1 is connected directly to ground. Selection of position OFF means that PIN1 is connected to ground via an RC-filter.
• 11 Bus terminal resistors If Vacon is the last device of the fieldbus line the bus termination must be set. Use jumper X4 (ON po- sition) or external termination resistors (e.g. in DSUB-9 connector). See Figure 9. Figure 9. Using jumper X4 to set the bus termination.
12 • vacon layout and connections Bus Biasing Bus biasing is required to ensure faultless communication between devices at RS-485 bus. Bus bias- ing makes sure that the bus state is at proper potential when no device is transmitting. Without bias- ing, faulty messages can be detected when the bus is in idle state.
Module is activated and receiving messages from the bus (once/sec) Blinking Module is in FAULT state slow • No messages from Master within the watchdog time (once/5 secs) • Bus broken, cable loose or Master off line 24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com...
14 • vacon installation INSTALLATION OF VACON NX RS-485 BOARD Vacon NX frequency converter Remove the cable cover. Open the cover of the control unit. Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205...
Page 15
Make sure that the grounding plate (see below) fits tightly in the clamp. Make a sufficiently wide opening for your cable by cutting the grid as wide as necessary. Close the cover of the control unit and the cable cover. 24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com...
See Vacon NX User’s Manual, Chapter 7.3.3.1. Fieldbus board parameters The Vacon RS-485 board is commissioned with the control keypad by giving values to appropriate pa- rameters in menu M7 (for locating the expander board menu see Vacon NX User's Manual, Chapter...
Page 17
To see the present status of the RS-485 fieldbus, enter the page from (G7.5.2). See Figure 12 and Table 6 below. READY READY I/Oterm I/Oterm Monitor Comm. status 0.841 Good messages Error messages Figure 12. Communication status 24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com...
Page 18
18 • vacon modbus Good messages 0…999 Number of messages received without communication errors Error messages 0…64 Number of messages received with CRC or parity errors Table 6. RS-485 message indications Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205...
Examples are to read the ON / OFF states of a group of discrete coils or inputs; to read the data contents of a group of registers; to 24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com...
Page 20
20 • vacon modbus read the diagnostic status of the slave; to write to designated coils or registers; or to allow loading, recording, or verifying the program within the slave. When the slave responds to the master, it uses the function code field to indicate either a normal (er- ror-free) response or that some kind of error occurred (called an exception response).
CRC LO 47 hex 6.1.1.3 Preset Single Register The query message specifies the register reference to be preset. Registers are addressed starting with zero, i.e. register 1 is addressed as 0. 24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com...
Page 22
22 • vacon modbus Example of a request to preset register 42001 to 00001hex in Slave device 1: ADDRESS 01 hex Slave address 1 hex (= 1) FUNCTION 06 hex Function 04 hex (= 4) DATA Starting ddress HI 07 hex...
Modbus registers 6.2.1 The Vacon variables and fault codes as well as the parameters can be read and written from Modbus. The parameter addresses are determined in the application. Every parameter and actual value have been given an ID number in the application. The ID numbering of the parameter as well as the pa- rameter ranges and steps can be found in the application manual in question.
6.2.3.1 Control word In Vacon applications, the three first bits of the control word are used to control the frequency con- verter. However, you can customise the content of the control word for your own applications because the control word is sent to the frequency converter as such.
Page 28
28 • vacon modbus 6.2.4.1 Status word UVFS TCSPDL Status word Status Information about the status of the device and messages is indicated in the . The word is composed of 16 bits that have the following meanings: Description Value = 0...
Page 29
Process data out 1 to 8 Process Data Out values 1 to 8 can be used in application for various purposes. Update rate is 10ms for all values. See APPENDIX 1 for usage of these values. 24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com...
30 • vacon modbus Parameters 6.2.5 The parameter addresses are determined in the application. Every parameter has been given an ID number in the application. The ID numbering of the parameter as well as the parameter ranges and steps can be found in the application manual in question. The parameter value shall be given without decimals.
• 33 Start-up test Frequency converter application Choose Fieldbus (Bus/Comm) as the active control place (see Vacon NX User's Manual, Chapter 7.3.3). Master software 1. Set FB Control Word (MBaddr 42001) value to 1hex. 2. Frequency converter status is RUN.
34 • vacon metasys n2 METASYS N2 Metasys N2 Protocol Introduction The N2 communications protocol is used by Johnson Controls and others to connect terminal unit controllers to supervisory controllers. It is open to any manufacturer and based upon a simple ASCII protocol widely used in the process control industry.
All Internal Integer (ADI) points have the follwoing features: • Do not support Change of State (COS) reporting. • Can be overridden and the ”Override Active” bit will be set. However, the Internal value is un- changed (Read Only). 24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com...
P2.7.22 fault 2=Fault,stop acc. to 2.4.7 3=Fault,stop by coasting 0=No response Response to slot 1=Warning P2.7.23 fault 2=Fault,stop acc. to 2.4.7 3=Fault,stop by coasting Table 25. Frequency converter responses to faults 24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com...
Page 40
40 • vacon metasys n2 APPENDIX 1 Process Data OUT (Slave to Master) The Fieldbus Master can read the frequency converter’s actual values using process data variables. Basic, Standard, Local/Remote Control, Multi-Step Speed Control, PID control and Pump and fan con-...
Page 41
Reference for PID 0.01% controller 2005 Process Data IN2 Actual Value 1 to PID 0.01% controller 2006 Process Data IN3 Actual Value 2 to PID 0.01% controller 2007–2011 PD4–PD8 Not Used Table 29 24-hour support +358 (0)40 8371 150 • Email: vacon@vacon.com...