Cooper safety VoCALL CFVCM User Manual & Log Book

Fire telephone & disabled refuge network system

Advertisement

Quick Links

VoCALL -
CFVCM/CFVCWM & CFVCX8
Fire Telephone & Disabled Refuge Network System
User Manual & Log Book

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VoCALL CFVCM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Cooper safety VoCALL CFVCM

  • Page 1 VoCALL - CFVCM/CFVCWM & CFVCX8 Fire Telephone & Disabled Refuge Network System User Manual & Log Book...
  • Page 2: Product Overview

    VoCALL Fire Telephone & Disabled Refuge Network System Introduction A VoCALL Emergency Voice Communications System (EVCS) is a fixed, secure, bi-directional, full duplex voice communication system to assist fire fighters in an emergency in high rise buildings or large sites where Radio communication may not work, and covers the operation of both fire telephones and disabled refuge systems.
  • Page 3: Important Safety Information

    VoCALL Fire Telephone & Disabled Refuge Network System Important Safety Information This equipment must only be installed and maintained by suitably skilled and competent person. This equipment is defined as Class 1 in EN60950 (Low Voltage Directive) and must be EARTHED. CAUTION INDOOR USE ONLY WARNING...
  • Page 4: Powering Up The System

    VoCALL Fire Telephone & Disabled Refuge System VoCALL Fire Telephone & Disabled Refuge Network System Powering up the System Carefully check the network wiring then apply AC power to each network exchange unit in turn DO NOT commission on batteries as the power supply has a large reservoir capacitor which will rupture the battery fuse if the AC is not present when powering up the system.
  • Page 5: Operation

    VoCALL Fire Telephone & Disabled Refuge System VoCALL Fire Telephone & Disabled Refuge Network System Operation All conversations on the VoCALL network system are under the command of the network master handset, if multiple network master handsets exist, the first operated one takes command of the system. Pt9 envisages the majority of calls to be made by lifting the handset of an outstation (Type A) or pressing the call button (Type B).
  • Page 6 VoCALL Fire Telephone & Disabled Refuge Network System Indications and Controls The faults on a VoCALL EVCS system are displayed in two locations, on the exchange with the fault, and at the CFVCM/CFVCWM master handset(s). Master Handset Indication The network master handset has the following indications:- CFVCM CFVCWM Health Indicators (Green)
  • Page 7: Led State

    VoCALL Fire Telephone & Disabled Refuge Network System Exchange Indications The network exchange unit has the following indications:- Meaning Fault This is a common fault LED and indicates that a current fault exists on this exchange unit, this can be a line fault, processor failure, power supply fault or network connection fault.
  • Page 8: Maintenance

    VoCALL Fire Telephone & Disabled Refuge Network System Maintenance It is a requirement of BS5839pt9 that a maintenance agreement be in place for the EVCS, the maintenance schedule should be as follows. Weekly: Lift a different handset on the system each week and make a call to the control, repeat each week until all points are tested, record results in the site log.
  • Page 9 VoCALL Fire Telephone & Disabled Refuge Network System VoCALL Fire Telephone & Disabled Refuge System - Log Book Site Name: Address: Contractor: Commissioned:...
  • Page 10 VoCALL Fire Telephone & Disabled Refuge Network System Certificate of Commissioning for an Emergency Voice Communication System (EVCS) to BS5839 pt 9 (2011) Site Name: Address: Customer Address: Areas Covered: System Design: In accordance with section 1 of BS 5839 : Part 9 : 2011 sub clause 6 the system design is has in accordance with the recommendations of this code except for the following: Installation: In accordance with section 3 of BS 5839 : Part 9 : 2011, the wiring has been inspected and tested and been...
  • Page 11 VoCALL Fire Telephone & Disabled Refuge Network System Site Specific Information Equipment Locations: Master Handset: Phone Locations: Exchange Number _______ Location _______________________ Cable ID Line Area Served...
  • Page 12 VoCALL Fire Telephone & Disabled Refuge Network System Site Specific Information Equipment Locations: Master Handset: Phone Locations: Exchange Number _______ Location _______________________ Cable ID Line Area Served...
  • Page 13 VoCALL Fire Telephone & Disabled Refuge Network System Site Specific Information Equipment Locations: Master Handset: Phone Locations: Exchange Number _______ Location _______________________ Cable ID Line Area Served...
  • Page 14 VoCALL Fire Telephone & Disabled Refuge Network System Date Event or Work Done Engineer Company Signature...
  • Page 15 VoCALL Fire Telephone & Disabled Refuge Network System Date Event or Work Done Engineer Company Signature...
  • Page 16 VoCALL Fire Telephone & Disabled Refuge Network System Date Event or Work Done Engineer Company Signature...
  • Page 17 VoCALL Fire Telephone & Disabled Refuge Network System Date Event or Work Done Engineer Company Signature...
  • Page 18 VoCALL Fire Telephone & Disabled Refuge Network System Date Event or Work Done Engineer Company Signature...
  • Page 19 VoCALL Fire Telephone & Disabled Refuge Network System Date Event or Work Done Engineer Company Signature...
  • Page 20 Cooper Safety Fire Systems Sales Service Cooper Lighting and Safety Ltd T: +44 (0)1302 303 999 T: +44 (0)1302 303 352 Wheatley Hall Road F: +44 (0)1302 303 333 F: +44 (0)1302 303 332 Doncaster E: sales@cooperfire.com E: service@cooperfire.com South Yorkshire...