1105BJ Amsterdam The Netherlands https://tkhsecurity.com/ Tel.: +31-20-4620700 This manual represents the knowledge at the above-mentioned time. TKH security works non-stop to improve her products. For the most recent technical information please contact your consultant or dealer. Table of content Publication 1 This document ..........................
This document This document contains all the information which is needed when installing the Sirius iX30. The details and recommendations will be described in the chapters below.
General The Sirius iX30 card reader is a versatile card reader which support multiple card technologies and communication protocols used in access control solutions. In addition, the Sirius iX30 is able to support different technologies simultaneously. 2.1 Wiring This document assumes standard T-568-B color coding of the cables.
801-6110 2.3.2 Celrubber Celrubber is strongly recommended if the Sirius iX30 (with or without spacer) is mounted directly to an outside surface. It offers both more protection and a smoother mounting in the event of an uneven surface. Celrubber Part number...
Installation To ensure proper functioning of the equipment, the environment of the Sirius iX30 must be compliant with certain conditions. Caution: The Sirius iX30 operates between a temperature and humidity of -30°C and + 65°C and 20 ~ 90% RH non-condensing.
Keep a minimum distance of 20cm between Sirius iX30 card readers. • The Sirius iX30 should preferably not be installed directly on metal. In the event that this is necessary, please use a spacer (see chapter 3.3.1) to achieve better performance.
Default LED settings 4.1.1 801-5301 TKH coded The Sirius iX30 TKH coded can both read TKH coded Mifare classic cards and TKH coded Mifare DESFire cards simultaneously and works by default at the following devices. Protocol Hardware device (door controller)
6 digits card number e.g.: 789012 Result as output: 123456789012 4.1.2 801-5302 CSN The Sirius iX30 reads both 4 byte and 7 byte CSN simultaneously and works by default at the following devices: Protocol Hardware device (door controller) RS485 Orion (stacked)
Upload the file per line Detailed information can be found in the manual: TKH_Security_HardwareControllApplet. Configuration card: A customer specific card which can be ordered by TKH Security which writes down the configuration into the card reader. • Connect the card reader •...
4.3 Interfaces The following interfaces are by default available on the Sirius iX30. Label Interface Description Light guide Multicolor RGB LED to display current status Buzzer Multitone buzzer for audio feedback DIP switch 3pin DIP switch for RS485 purpose 9 Pin connector...
Clock/data- Wiegand, open collector Clock/data- Wiegand, open collector *The Sirius iX30 accepts a power between 5.0 and 16.0 VDC. A higher input voltage results in lower power consumption and ensuring cost-efficient wiring with a smaller conductor diameter. When using an external power supply, it must comply with SELV guidelines.
4.4.1 RS485 Directly Recommended cable type between the a Orion or Polyx and the Sirius iX30 card reader is: • CAT 5 UTP four twisted pairs of 24AWG copper conductors • CAT 6 UTP four twisted pairs of 24AWG copper conductor A direct connection (without using an Adapterboard) between the Sirius card reader and a door controller based on RS485™...
Page 14
Connect GND of the Adapterboard to the local earth. • Connect the shield of the ground cable to the GND connection of the Adapterboard possible connection of the Sirius iX30 on the Adapterboard. Do not place any jumpers! For more information. See the Adapterboard-IM manual.
4.4.3 Clock/data- Wiegand Recommended cable type between the Orion or Orbit and Sirius iX30 card reader: • CKY 3x2x0,14mm² • CKY 4x2x0,14mm² • CAT5 UTP four twisted pairs of 24AWG copper conductors • CAT6 UTP four twisted pairs of 24AWG copper conductors...
Technical specifications Power supply voltage 5- 16VDC (max: 1,4W) Measure housing 142 x 45 x 22 mm 98+ (…) x 38 mm Environment IP rating IK rating operating temp. -35 … 65ºC operating 5 … 95% relative humidity, non-condensing humid. storage temp.
Need help?
Do you have a question about the iX30 and is the answer not in the manual?
Questions and answers