Microengine XP-GT Series Programming Manual

Microengine XP-GT Series Programming Manual

Single door access control system
Table of Contents

Advertisement

 
MicroEngine
XP-GT/GTR Programming Manual
 
®
XP-GT/GTR
SINGLE DOOR ACCESS
CONTROL SYSTEM
PROGRAMMING MANUAL
Version 4.00
 
v4.00 
 

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the XP-GT Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Microengine XP-GT Series

  • Page 1   MicroEngine XP-GT/GTR Programming Manual   ® XP-GT/GTR SINGLE DOOR ACCESS CONTROL SYSTEM PROGRAMMING MANUAL Version 4.00   1  v4.00   ...
  • Page 2   MicroEngine XP-GT/GTR Programming Manual   ® MicroEngine XP-GT/GTR Controller Programming Manual Revision History Version Date Remarks 1.00 1/1/2007 First Release of Manual 2.00 8/3/2008 Updated arrangements and drawings 2.10 17/7/2008 Updated drawings and included the XP-GTR series to the manual. Also added a page to indicate scope of manual.
  • Page 3   MicroEngine XP-GT/GTR Programming Manual   ® Scope: This manual covers the following products XP-GT1200 XP-GT3200 XP-GT1200L XP-GT3200L XP-GTR1200 XP-GTR3000 XP-GTR1200L XP-GTR3000L XP-GT3500L XP-GT3500ABL XP-GTR1500L XP-GTR1500ABL   v4.00  3   ...
  • Page 4: Table Of Contents

      MicroEngine XP-GT/GTR Programming Manual   ® Table of Contents A. XP-GT/GTR Single Door Access Control System ............i. Powering Up ........................ii. Idle Mode ........................iii. Verification Mode ......................a. Token Mode ....................... b. Token+PIN Mode ......................c. Token+Fingerprint Mode ....................
  • Page 5   MicroEngine XP-GT/GTR Programming Manual   ® 3. Fingerprint Menu ...................... 3.1 Add Fingerprint ......................3.2 Delete Fingerprint ....................... 3.3 Clear Fingerprint ......................3.4 Template Enrolled ...................... 3.5 Set Security Level ...................... 4. Maintenance Menu ....................4.1 Change Master PIN ....................
  • Page 6: Xp-Gt/Gtr Single Door Access Control System

      MicroEngine XP-GT/GTR Programming Manual   ® A. XP-GT/GTR Single Door Access Control System i. Powering Up Before powering up the controller for the first time, check that all the connections to the hardware are connected properly according to the wiring diagram.
  • Page 7: Idle Mode

      MicroEngine XP-GT/GTR Programming Manual   ® ii. Idle Mode In Idle Mode, the screen below will be shown: Good Day Please Present Token 10:38:55 Tue,07/17 The controller will prompt different audio and visual indications to users under different circumstances. Table below shows normal response in Idle Mode:...
  • Page 8: Token+Pin Mode

    For maximum security, the controller can be programmed to accept ‘Card+Pin+Fingerprint’ before granting door access. Alternatively, the controller can also be programmed to accept ‘Fingerprint’ only or ‘Fingerprint+Pin’ verification mode according to the user’s requirements. NOTE:- Fingerprint functions are only available to all XP-GT series.   v4.00  8   ...
  • Page 9: Symbols

      MicroEngine XP-GT/GTR Programming Manual   ® iv. Symbols Listed below are the common symbols that are used in the operation: Symbol Name Description Anti PassBack Enabled Anti PassBack Mode enabled. Once enabled, a user will not be able to use the same...
  • Page 10: Programming Environment

    ® B. Programming Environment The MicroEngine XP-GT/GTR series controllers have an LCD display and a 4 x 4 keypad to allow users to program the functionalities of the controller. The programming environment on the controller is called the configuration menu.
  • Page 11   MicroEngine XP-GT/GTR Programming Manual   ® XP-GT/GTR (1500L, 3500L, 1500ABL, 3500ABL) Series To enter Configuration Menu for the first time, please follow the steps below: 1. Press '*' (asterisk). 2. Enter the 6-digits default Master PIN (“123456”). 3. Screen as below will be shown. Enter a new 6-digit Master Pin for enhanced security levels.
  • Page 12 - Local IP Address Fingerprint Menu - Local Port No. 2) Delete Fingerprint only available to all - Remote IP Address XP-GT series. - Remote Port No. 3) Clear Fingerprint - Subnet Mask - Gateway IP 4) Template Enrolled 5) Set Security Level...
  • Page 13: System Menu

      MicroEngine XP-GT/GTR Programming Manual   ® - Lock Release Time 1. System Menu - Door Open Time - Lock Release TZ - Exit Button TZ - Autopin Mode - Security Off 1) System Menu 1) Set Date & Time...
  • Page 14   MicroEngine XP-GT/GTR Programming Manual   ® The section with parenthesis, ( ), is the value selected for editing. Press if users wish to exit without saving changes. √ Enter the ‘YEAR’ settings, press to proceed to the next section.
  • Page 15: Door Parameter

      MicroEngine XP-GT/GTR Programming Manual   ® Set Date & Time Save Changes?   √ - OK X - Cancel NOTE:- If controller has established communication with the software, the date & time will automatically be synchronized with the PC’s date & time.
  • Page 16   MicroEngine XP-GT/GTR Programming Manual   ® List of programmable parameters include: Lock Release Time Description : Duration for the lock to be released every time a valid access is granted. Value : 00 - 99 seconds. Default value : 10 seconds.
  • Page 17   MicroEngine XP-GT/GTR Programming Manual   ® vii. Anti PassBack Description : Anti PassBack Mode enabled or disabled. Once enabled, users are prevented from using the same card to gain access through the same direction successively without first gaining access from the opposite direction.
  • Page 18   MicroEngine XP-GT/GTR Programming Manual   ® xiii. As Exit Reader Description : Built-in Reader enabled or disabled. Once enabled, controller’s built-in reader is used as exit reader while external reader is configured to be the entry reader. Value : ON, OFF.
  • Page 19   MicroEngine XP-GT/GTR Programming Manual   ® xix. Fire Release Description : Fire Release Enable selection. Once enabled, the controller will release the door lock when the fire alarm signal is detected. Value : NO, YES. Default value : NO.
  • Page 20: Time Set

      MicroEngine XP-GT/GTR Programming Manual   ® 1.3 Time Set Time Set is the time interval that activates an operation or function. Time Set consists of three time intervals that enable users to activate Time Zone controlled functions. The GT/GTR (1200, 3000, 3200, 1200L, 3000L, 3200L) series controllers have 50 Time Sets while the GT/GTR (1500L, 3500L, 1500ABL, 3500ABL) series controllers have an expanded 100 Time Sets.
  • Page 21   MicroEngine XP-GT/GTR Programming Manual   ® The Time Set above defines the time interval that the lock will be released. Please refer to the Time Set programming procedure that follows after EXAMPLE 2. EXAMPLE 2:- During normal office hours, users only need to use their cards to access the store room door.
  • Page 22: Time Zone

      MicroEngine XP-GT/GTR Programming Manual   ® Enter Time Set number that users want to set. Screen below will be shown: Time Set Setting TimeSet No 03 I1 (00): 00 ▸ 00 : 00 I2 00 : 00 ▸ 00 : 00 I3 00 : 00 ▸...
  • Page 23   MicroEngine XP-GT/GTR Programming Manual   ® Time Zone 00 has Time Set 00 (no time interval to activate functions). The functions assigned with this Time Zone will thus be disabled at all times including holidays. This Time Zone is also known as ‘No Access Time Zone’.
  • Page 24   MicroEngine XP-GT/GTR Programming Manual   ® (refer to EXAMPLE 2 for detailed information of Time Set 03) Users then need to assign Time Zone 3 to Hi Security TZ sub-menu in Section 1.2 Door Parameter menu. To program the Time Zone, please follow steps below: Enter Configuration Menu.
  • Page 25: Holiday Setting

      MicroEngine XP-GT/GTR Programming Manual   ® 1.5 Holiday Setting Holiday Setting is used to define dates that are declared as holidays. The controller has 30 sets (00-29) of Holiday settings. When a date falls in the holiday category, its original Time Set setting in the Time Zone will be overridden by the holiday’s Time Set setting in the same Time Zone.
  • Page 26: General Parameter

      MicroEngine XP-GT/GTR Programming Manual   ® NOTE:- These settings must be updated yearly for holidays that do not fall on the same date every year. 1.6 General Parameter This menu lets users set general parameters of the controller. The settings which can...
  • Page 27   MicroEngine XP-GT/GTR Programming Manual   ® NOTE:- Ensure that all controllers in the same RS485 connection network have DIFFERENT System Address settings to prevent communication errors. Advance Communication This parameter lets users specify the communication mode between the controller and the host of the system. Toggle between the option of 'NOR' and 'EHD'.
  • Page 28: Network Parameters

      MicroEngine XP-GT/GTR Programming Manual   ® NOTE:- 1) Sub-menu v., vi., and vii. are only available to GT/GTR (1500L, 3500L, 1500ABL, 3500ABL) series only. 2) By default, sub-menu v., vi., and vii. are set OFF so that users can enter Configuration Menu via Master Pin set in Section B (iii).
  • Page 29   MicroEngine XP-GT/GTR Programming Manual   ® Network Settings Enter Local IP Addr. (192).[168].[001].[023] √ - OK X - Cancel The screen below will be shown. Enter the Local Port No. for the √ controller and press to proceed to the next screen.
  • Page 30: Sounder Setting

      MicroEngine XP-GT/GTR Programming Manual   ® The screen below will be shown. Enter the Gateway IP for the network √ and press to proceed to the next screen. Network Settings Enter Gateway (192).[168].[001].[001] √ - OK X - Cancel The screen below will be shown to prompt users to save all changes.
  • Page 31: O/P Trigger Events

      MicroEngine XP-GT/GTR Programming Manual   ® Sounder Setting Day of Week : Sun Time 00 [99:99] Time 01 [99:99] Time 02 [99:99] √ - OK X - Cancel The screen below will then be shown to prompt users to save the √...
  • Page 32   MicroEngine XP-GT/GTR Programming Manual   ® Event Event Event Event Event Event Event Event Code Code Code Code Valid Entry Access Door Forced Open Output Isolated Tr M AntiPassBack Violation Card Locked Out Input On Tr N Unknown Card Number...
  • Page 33: Database Menu

      MicroEngine XP-GT/GTR Programming Manual   ® 2. Database Menu 1) Quick Add User 2) Database Menu 2) Add User 3) Delete User 4) Edit User Setting 5) Clear AntiPassBack 6) Clear CardLockOut 7) Clear All User 2.1 Quick Add User This menu allows users to quickly add a new user.
  • Page 34: Add User

      MicroEngine XP-GT/GTR Programming Manual   ® If the ID entered has not been added before, a success notification will be shown as below. Enter another User ID to quick add another user, or press to return to Database Menu.
  • Page 35   MicroEngine XP-GT/GTR Programming Manual   ® Screen as below will be shown. Enter the Time Zone No. to grant door access √ for this user and press to proceed to the next screen. Add User Enter TimeZone No. TimeZone :[00] √...
  • Page 36: Delete User

      MicroEngine XP-GT/GTR Programming Manual   ® The screen below will be shown. Select whether to allow the new user to √ access Configuration Menu and press to proceed to the next screen. Add User NOTE:- This sub-menu is only available to GT/GTR (1500L, 3500L, Allow Config.
  • Page 37: Edit User Settings

      MicroEngine XP-GT/GTR Programming Manual   ® Delete User Enter User No. ID: [123456] User Deleted √ - OK X - Cancel 2.4 Edit User Settings This menu allows users to edit settings to users already added to the database.
  • Page 38   MicroEngine XP-GT/GTR Programming Manual   ® [4] is by Token, Pin and Fingerprint vi. [5] is by Fingerprint only vii. [6] is by Fingerprint and Pin Press ' √ ' to proceed to the next screen. Edit User Setting...
  • Page 39: Clear Anti Passback

      MicroEngine XP-GT/GTR Programming Manual   ® 2.5 Clear Anti PassBack The Clear AntiPassBack menu lets users clear anti passback statuses for all users. To clear anti passback statuses for all users, please follow steps below: Enter Configuration Menu. Press 2 for Database Menu.
  • Page 40: Clear All User

      MicroEngine XP-GT/GTR Programming Manual   ® Screen as below will be shown when the controller is clearing all card lockout statuses. A success notification will be shown once the card lockout statuses is cleared. Clear Card LockOut Clearing All User Card LockOut..
  • Page 41: Fingerprint Menu

      MicroEngine XP-GT/GTR Programming Manual   ® 3. Fingerprint Menu 1) Add Fingerprint 3) Fingerprint Menu 2) Delete Fingerprint 3) Clear Fingerprint 4) Template Enrolled 5) Set Security Level NOTE:- The Fingerprint Menu is only available to XP-GT (1200, 3200, 1200L, 3200L, 3500L, 3500ABL) series only.
  • Page 42   MicroEngine XP-GT/GTR Programming Manual   ® The screen below will be shown. Enter the finger index of the new user as per √ the finger index representation as shown in Table 2. Press to proceed to the next screen.
  • Page 43: Delete Fingerprint

      MicroEngine XP-GT/GTR Programming Manual   ® 3.2 Delete Fingerprint This menu lets users delete a fingerprint from the database. To delete fingerprint, please follow steps below: Enter Configuration Menu. Press 3 for Fingerprint Menu. Press 2 for Add Fingerprint. Screen as below will be shown. Enter the User ID of the user's fingerprint to be deleted.
  • Page 44: Template Enrolled

      MicroEngine XP-GT/GTR Programming Manual   ® A success notification will be prompted to notify users when all fingerprint templates have been cleared. 3.4 Template Enrolled This menu will indicate how many templates are currently installed in the fingerprint database.
  • Page 45   MicroEngine XP-GT/GTR Programming Manual   ® √ Screen as below will be shown. Press to save. Security Level Press √ to save. Security Level [1] √ - OK X – Cancel Menu 3.5 Set Security Level is only available to XP-GT (1200, 3200, NOTE:- 1200L, 3200L) series only.
  • Page 46: Maintenance Menu

      MicroEngine XP-GT/GTR Programming Manual   ® 4. Maintenance Menu 4) Maintenance Menu 1) Change MasterPin 2) Clear Transaction 3) Test Watchdog 4) Show Version 5) Show Information 4.1 Master PIN Master PIN is a six-digit PIN used to access the Configuration Menu. The default Master PIN is “123456”.
  • Page 47: Clear Transaction

      MicroEngine XP-GT/GTR Programming Manual   ® 4.2 Clear Transaction Clear Transaction lets users clear the entire transaction record in the controller. To clear the transaction record, please follow the steps below: Enter Configuration Menu. Press 4 for Maintenance Menu.
  • Page 48: Show Version

      MicroEngine XP-GT/GTR Programming Manual   ® The controller should reset itself less than 10 seconds. If it takes longer than that or does not reset at all, please return the controller to the manufacturer for further investigation. 4.4 Show Version This menu allows users to check the firmware version number and model number of the controller.
  • Page 49: Alarm Menu

      MicroEngine XP-GT/GTR Programming Manual   ® 5. Alarm Menu 1) Arm/Disarm Sensor 2) Arm Delay 1) Input Setting 3) Trigger Delay 5) Alarm Menu 4) Sensor Arm TZ 5) View Sensor State 1) Output On/Off 2) Output Setting 2) Output Type...
  • Page 50   MicroEngine XP-GT/GTR Programming Manual   ® Press 2 for Arm Delay. Screen as below will be shown. Press 1 or 2 to select the sensor. Press to confirm and proceed to set the Arm Delay time. √ Enter duration between “0000” and “3599” in seconds and press to save changes.
  • Page 51: Output Setting

      MicroEngine XP-GT/GTR Programming Manual   ® Sensor Arm TZ Enter Input No.[?] (Min=01, Max=02) Arming TZ: [FF] √ - OK X - Cancel 5.1.5 View Sensor State This menu lets users view the sensor state; whether connected or not connected.
  • Page 52   MicroEngine XP-GT/GTR Programming Manual   ® 5.2.2 Output Type This menu lets users specify the output type; whether the output connected is a constant-on alarm or a pulsing-on alarm. To specify the output type, please follow steps below: Enter Configuration Menu.
  • Page 53: Panel Status

      MicroEngine XP-GT/GTR Programming Manual   ® 5.2.4 Output TZ This menu lets users specify the Time Zone to activate the output alarm. This will determine the day of the week and the time of the day to activate the output alarm.
  • Page 54: Exit Programming Menu

      MicroEngine XP-GT/GTR Programming Manual   ® 6. Exit Programming Menu If the controller does not receive input for 30 seconds inside Configuration Menu, the controller will automatically exit from Configuration Menu and return to Idle Mode. Users can also exit Configuration Menu by pressing the button at the main programming menu.
  • Page 55: Appendix 1 - General Wiring For Xp-Gt Using Mas-Rbt

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 1 – General Wiring for XP-GT using MAS-RBT [XP-GT/GTR (1200, 3000, 3200, 1200l, 3000L, 3200L)]   v4.00  55   ...
  • Page 56: Appendix 2 - General Wiring For Xp-Gtr Using Mas-Rbu

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 2 – General Wiring for XP-GTR using MAS-RBU [XP-GT/GTR (1200, 3000, 3200, 1200l, 3000L, 3200L)]   v4.00  56   ...
  • Page 57: Appendix 3 - General Wiring For Two Xp-Gt Using Mas-Rbt

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 3 – General Wiring for Two XP-GT using MAS-RBT [XP-GT/GTR (1200, 3000, 3200, 1200l, 3000L, 3200L)]   v4.00  57   ...
  • Page 58: Appendix 4 - Connection For Xp-Gt Using Sounder Feature

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 4 – Connection for XP-GT using Sounder Feature [XP-GT/GTR (1200, 3000, 3200, 1200l, 3000L, 3200L)]   v4.00  58   ...
  • Page 59: Appendix 5 - Connection For Xp-Gtr Using Sounder Feature

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 5 – Connection for XP-GTR using Sounder Feature [XP-GT/GTR (1200, 3000, 3200, 1200l, 3000L, 3200L)]   v4.00  59   ...
  • Page 60: Appendix 6 - Connection For Xp-Gt And Xp-Gtr Using Fire Release Feature

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 6 – Connection for XP-GT and XP-GTR using Fire Release Feature [XP-GT/GTR (1200, 3000, 3200, 1200l, 3000L, 3200L)]   v4.00  60   ...
  • Page 61: Appendix 7 - Connection For Xp-Gtr To Mio44

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 7 – Connection for XP-GTR to MIO44 [XP-GT/GTR (1200, 3000, 3200, 1200l, 3000L, 3200L)]   v4.00  61   ...
  • Page 62: Appendix 8 - General Wiring For Xp-Gt Using Mas-Rbm

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 8 – General Wiring for XP-GT using MAS-RBM [XP-GT/GTR (1500L, 3500L, 1500ABL, 3500ABL)]   v4.00  62   ...
  • Page 63: Appendix 9 - General Wiring For Xp-Gtr Using Mas-Rbu

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 9 –General Wiring for XP-GT using MAS-RBU [XP-GT/GTR (1500L, 3500L, 1500ABL, 3500ABL)]   v4.00  63   ...
  • Page 64: Appendix 10 - Wiring Connection For Two Xp-Gt Using Mas-Rbm

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 10 – Wiring Connection for Two XP-GT using MAS- [XP-GT/GTR (1500L, 3500L, 1500ABL, 3500ABL)]   v4.00  64   ...
  • Page 65: Appendix 11 - Wiring Connection For Xp-Gt Using Sounder Feature

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 11 – Wiring Connection for XP-GT using Sounder Feature [XP-GT/GTR (1500L, 3500L, 1500ABL, 3500ABL)]   v4.00  65   ...
  • Page 66: Appendix 12 - Wiring Connection For Xp-Gtr Using Sounder Feature

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 12 – Wiring Connection for XP-GTR using Sounder Feature [XP-GT/GTR (1500L, 3500L, 1500ABL, 3500ABL)]   v4.00  66   ...
  • Page 67: Appendix 13 - Wiring Modification For Xp-Gt To Fire Alarm Signal With Voltage Source

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 13 – Wiring Modification for XP-GT to Connect to Fire Alarm Signal with Voltage Source (Wet Contact) [XP-GT/GTR (1500L, 3500L, 1500ABL, 3500ABL)]   v4.00  67   ...
  • Page 68: Appendix 14 - Wiring Modification For Xp-Gtr To Fire Alarm Signal With Voltage Source

      MicroEngine XP-GT/GTR Programming Manual   ® Appendix 14 – Wiring Modification for XP-GTR to Connect to Fire Alarm Signal with Voltage Source (Wet Contact) [XP-GT/GTR (1500L, 3500L, 1500ABL, 3500ABL)]   v4.00  68   ...

Table of Contents