ICAS FIRE PANEL IFP–2.32
1) DESCRIPTION
IFP-2.32 is a microprocessor controlled Fire
Panel with 2 loops intended either for privat
Homes & Apartments or larger installations.
The two loops are balanced by
resistor
mounted at the last detector in each
loop. The device is named as IFP-Y.X, where
Y describes number of loops and X number of
detectors in the loop. IFP-2.32 can handle 32
detectors of standard 12V Icas detectors type
500-IDx or Icas type CHOR-E (9V) in each
loop.
Connection of Detectors:
-
500-IDx detectors
sirene but the sirene are triggered from
the Fire Panel. A 4 wire solution is used
to activate the integrated sirene. An external siren can also be used. The siren is con-
trolled by the
al siren control.
-
CHOR-E detectors (9V detector) can be connected only "Alarm in one Alarm in all"
function.
The different functions are chosen by use of jumper.
The IFP-2.32 is supplied by 230V AC and the internal backup
equipped with one internal siren, fault relay, alarm relay and 2 open collectors, each for one
loop. The IFP-2.32 is controlled by 4 underlighted pushbuttons. In the IFP-2.32 is possible to
control each loop separately by the functions for Switch OFF/ON loops, also Switch OFF/ON
the Test of loops, remove Alarm and Fault in loops. The IFP-2.32 includes also complete
functions for battery testing and firmware testing.
When the Alarm is triggered, the internal siren of IFP-2.32 and siren of detectors / External
sirenes can be silenced with pushbutton SIREN. This will stop the sirens of detectors. Remov-
ing of Alarm and other control functions are described in chapter Button Functions.
___________________________________________________________________________
ICAS AS
IFP-2.32 Manual
2k7 Ohm
have integrated
IFP-2.32
Fire Panel. The alarm relay of
salg@icas.no
IFP-2.32
12V/0,8Ah.
1
can be used for extern-
The IFP-2.32 is
www.icas.no

Advertisement

Table of Contents
loading

Summary of Contents for ICAS IFP-2.32

  • Page 1 Test of loops, remove Alarm and Fault in loops. The IFP-2.32 includes also complete functions for battery testing and firmware testing. When the Alarm is triggered, the internal siren of IFP-2.32 and siren of detectors / External sirenes can be silenced with pushbutton SIREN. This will stop the sirens of detectors. Remov- ing of Alarm and other control functions are described in chapter Button Functions.
  • Page 2 Low power terminals side Battery Switch jumper Connect the 230V into the terminal on the left side of the IFP-2.32. Connect the Detectors and siren. Follow pictures on the page 2 and page 3. The recommended detector cable type is AF CEI 20-22 IEC 332 or VD-04 shielded cable, or equivalent type.
  • Page 3 19.04.2013 ICAS FIRE PANEL IFP–2.32 “CONNECTION 500-IDX SMOKE DETECTORS” “CONNECTION CHOR-E SMOKE DETECTORS” (Connection meets EN52-2 with only the exception of clause 8.2.4. - Removal of a point) JUMPERFIX: ___________________________________________________________________________ ICAS AS salg@icas.no www.icas.no...
  • Page 4: Battery Switch

    19.04.2013 ICAS FIRE PANEL IFP–2.32 500-IDX SWITCH Shorted – 12V loop output voltage Open – 9V loop output voltage BATTERY SWITCH Shorted – Backup battery connected (Normal operation). Open – Backup battery is not connected (The Detectors do not work after power cut).
  • Page 5: System Fault

    19.04.2013 ICAS FIRE PANEL IFP–2.32 Loop open or short – Loop A or Loop B  When the fault is removed – The signalization can be switched off manually only  in level 2 or automatically in 1 min. sound can be suppressed in level 1 ...
  • Page 6: Button Functions

    19.04.2013 ICAS FIRE PANEL IFP–2.32 4) BUTTON FUNCTIONS There are two levels of the manual control. Following tables can be used for simple guide to control IFP-2.32 unit. “Button Function 1-Level 1 Control”: Button function 1 - LEVEL 1 Control...
  • Page 7 19.04.2013 ICAS FIRE PANEL IFP–2.32 Button function 2 - ALARM RESET LOOP B A+B at the same time Enter into LEVEL 2 Press and hold B LOOP B Choice 1x A ALARM LOOP B Reset Choice (Button LAMP is used at the end as...
  • Page 8 19.04.2013 ICAS FIRE PANEL IFP–2.32 Button function 3 - FAULT Reset LOOP B A+B at the same time Enter into LEVEL 2 Press and hold B LOOP B Choice 2x A FAULT LOOP B Reset Choice (Button LAMP is used at the end as...
  • Page 9 19.04.2013 ICAS FIRE PANEL IFP–2.32 Button function 4 – LOOP B OFF/ON A+B at the same time Enter into LEVEL 2 Press and hold B LOOP B Choice 3x A LOOP B is in Off / On Choice (Button LAMP is used at the end as...
  • Page 10 19.04.2013 ICAS FIRE PANEL IFP–2.32 A+B at the same time Enter into LEVEL 2 Press and hold B LOOP B Choice 4x A LOOP B is in Test Off / On Choice (Button LAMP is used at the end as...
  • Page 11 19.04.2013 ICAS FIRE PANEL IFP–2.32 “Simple Map of Button functions”: A+1x pressed B for ALARM Reset A+2x presed B for FAULT Reset A+3x pressed B (press not release) for Switch Off/On Applied for LOOP A A+4x pressed B for Switch Test Off/On...
  • Page 12: Mechanical Specification

    19.04.2013 ICAS FIRE PANEL IFP–2.32 5) PARAMETERS POWER SUPPLY Power supply: 230V ( + 10% / - 15% ) ~ 50Hz Operating voltage: 14 V Power consumption normal: <60 mA Minimal load ( Imin ) 32 mA Maximal load (Imax a)
  • Page 13 19.04.2013 ICAS FIRE PANEL IFP–2.32 1293 ICAS AS, Grini Naeringspark 15 1361 Oesteraas, Norway 1293-CPD-0372 EN54-2:1999, EN54-2:2007/A1 EN54-4:1999, EN54-4:2003/A1, EN54-4:2007/A2 Control Unit for electrical fire alarm systems for buildings Power Supply for electrical fire alarm systems for buildings IFP-2.32 Optional requirements: State Test Documentation: IFP-2_32-Manual_EN.pdf ver.04/2013...
  • Page 14: Maintenance

    Place the detector back into the socket in accordance with point 3 of the 500-IDx installation manual. Switch off the fire alarm and fault alarm of the IFP-2.32 in both loops. See section 2 and 3 of chapter 4. Wait until loops are in LOOPS GUARD MODE.