Item Test ® Heat Link Made in Canada by Mixing Valve Reset Control 31360 Power: 120 V + 10% 50/60 Hz 1300 VA Floating Output: 24 V (ac) 0.34 A 8 VA Relays: 240 V (ac) 10 A 1/3 hp, pilot duty 240 VA...
® Mixing Valve Reset Control Stk# 31360 is designed to control the supply water temperature to a hydronic system in order to provide outdoor reset or setpoint operation. The control uses a floating action mixing valve to regulate the supply water temperature, while protecting the boiler against flue gas condensation.
® the LCD in order to set up and monitor the operation of your system. The Stk# 31360 has three push buttons (Item, “Up”, “Down”) for selecting, viewing, and adjusting settings. As you program your control, record your settings in the ADJUST menu table which is found in the second half of this brochure.
Next, the software version is displayed for 2 seconds. Finally, the control enters into the normal operating mode. Operation The Stk# 31360 uses a floating action mixing valve to vary the supply water temperature to a hydronic system. The supply water temperature is based on either the current outdoor temperature, or a fixed setpoint.
Page 5
Floating Action A 24 V (ac) floating action actuator motor is connected directly to the Stk# 31360 on the R Opn, R Cls and C terminals (9, 10 and 11). The Stk# 31360 pulses the actuator motor open or close to maintain the correct mixed supply water temperature at the mix sensor when there is a mixing demand.
System Pump Operation (Sys Pmp) The system pump contact (Sys Pmp, terminal 5) closes whenever there is a mixing demand and the Stk# 31360 is not in WWSD. The system pump segment is displayed in the LCD. After the mixing demand has been satisfied, the Stk# 31360 continues to operate the system pump for 20 seconds.
Page 7
The MIX MIN is the lowest temperature that the control is allowed to use as a MIX TARGET temperature. During mild conditions, if the Stk# 31360 calculates a MIX TARGET temperature that is below the MIX MIN setting, the MIX TARGET temperature is adjusted to match the MIX MIN setting.
Stk# 31360 is not in WWSD. The system pump segment is displayed in the LCD. After the mixing demand has been satisfied, the Stk# 31360 continues to operate the system pump for 20 seconds. This allows some residual heat to be purged out to the heating system.
Page 9
When using a Characterized Heating Curve, the control requires the selection of a terminal unit. The terminal unit determines the shape of the Characterized Heating Curve according to how the terminal unit delivers heat into the building space. The Stk# 31360 provides for selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube convector, radiator and baseboard.
Page 10
MIN segment will be displayed in the LCD when either the MIX TARGET or (77) MIX temperature is being viewed. If an indoor sensor is used, and the Stk# 31360 is operating at the MIX MIN temperature, the system pump is cycled using Pulse (66) Width Modulation (PWM) with a 15 minute cycle length.
No Boiler Sensor The 31360 is capable of operating without a boiler return sensor if desired. Without a boiler return sensor, the 31360 provides a boiler enable as described in the BOILER ENABLE section, but is unable to provide boiler protection.
Boiler Enable (30% Enable / 10% Enable) The Stk# 31360 has a DIP switch that allows for the selection between a 30% boiler enable and a 10% boiler enable. This switch is only functional when the Boiler Sensor DIP switch is set to Return.
Check the contents of this package. If any of the contents listed are missing or damaged, please contact your wholesaler or HeatLink ® sales representative for assistance. Type Stk# 31360 includes: One Mixing Valve Reset Control Stk# 31360, One HeatLink Outdoor Sensor Stk# 30070, Two HeatLink Universal ®...
Page 14
System Pump Contact (Sys Pmp) The Sys Pmp output terminal (5) on the Stk# 31360 is a powered output. When the relay in the Stk# 31360 closes, a120 V (ac) is provided to the SysPmp terminal (5) from the Power L terminal (3).
Indoor Sensor (European version only) If an indoor sensor is used, connect the two wires from the sensor to the Com and Indr terminals (16 and 18). The indoor sensor is used by the Stk# 31360 to measure the room air temperature. Unoccupied Switch If an external timer or switch is used to provide an unoccupied period, connect the two wires from the external switch to the UnO Sw and Com terminals (12 and 13).
Page 16
The boiler is controlled as described in Boiler Sensor Placement Page 12. For systems where the Stk# 31360 provides a heat demand to an external boiler control, the boiler sensor should be installed on the return side of the boiler loop. When the boiler sensor is installed on the return side of the boiler loop, the DIP switch must be set to Return. The Stk# 31360 enables the boiler when the position of the mixing valve exceeds the boiler enable DIP switch setting.
® Heat Link Installation / Quick Setup HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com Quick Setup European Version Only The quick setup can be used for both outdoor reset and setpoint operation. To enter the installer programming mode, set the Advanced / Installer DIP switch to Installer.
Page 18
® Heat Link Quick Setup HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com European Version Only ADJUST ˚ F Press and release the Item button to advance to the units adjustment. Use the “Up” or “Down” button to set the scale to °F or °C.
® Heat Link View Menu HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com View Menu North American and European Versions (differences where noted) “Installer” and “Advanced” levels on European version only. Display Description Range OUTDR VIEW Outdoor Current outdoor air temperature as measured by the outdoor ß...
® Heat Link Adjust Menu HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com Adjust Menu North American and European Versions (differences where noted) “Installer” and “Advanced” levels on European version only. Actual Display Description Range Setting ADJUST Room Occupied The desired room air temperature during ß...
Page 21
The Stk# 31360 continually monitors the sensors, and displays an error message whenever testing a fault is found. See the following pages for a list of the Stk# 31360’s error messages and possible causes. testing paused When the Test button is pressed, the test light is turned on. The individual outputs and relays are tested in the T est following test sequence.
® Heat Link Testing & Troubleshooting HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com Troubleshooting North American & European Versions When troubleshooting any heating system, it is always a good idea to establish a set routine to follow. By following a consistent routine, many hours of potential headaches can be avoided.
® Heat Link Error Messages HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com Error Messages North American & European Versions VIEW The control was unable to read a piece of information from its EEPROM. This error can be caused by a noisy power source.
® Heat Link ELECT 5.1 HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com 1 Circuit (Fully Modulating Floor Heating) Application: Automatic indoor/outdoor controller activating a 4-way mixing valve motor, boiler, plus primary (P-2) and system (P-1) pumps. (Optional secondary zone control can be provided with individual room thermostats)
® Heat Link ELECT 5.2 HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com Indoor/Outdoor controller c/w Optional Standard Thermostats Application: StatLink controls activating individual manifold module zone motors and automatic mixing ® valve reset controller which in turn activates boiler plus primary (P-2) and system (P-1) pumps.
® Heat Link ELECT 5.3a HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com StatLink Controls Activating Low & High Temp. Circuits ® Application: StatLink controls activating individual zone motors for both primary and secondary circuit loops. ® For the secondary low temp. circuit, StatLink activates the indoor/outdoor control, which in turn ®...
Page 31
® Heat Link ELECT 5.3b HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com StatLink Controls Activating Low & High Temp. Circuits ®...
® Heat Link TECH 5.4 HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com 6 Circuit (Mod. Fl. Ht. & Snowmelt. plus Additional Htg. Components) Application: 4-Way Mixing Cast iron high mass boiler and 6 circuits (two low temp. circuit - fully automatic modulating water temp. for floor heating and snow melting) (four high temp.
® Heat Link ELECT 5.4a HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com StatLink Controls Activating Circuits plus Snowmelt. Controller ® Application: StatLink controls activate the mixing valve control for the low temp. circuit which in turn activates ®...
Page 35
® Heat Link ELECT 5.4b HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com StatLink Controls Activating Circuits plus SnowMelt. Controller ®...
® Heat Link TECH 5.5 HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com 4 Circuit (Mod. Fl. Ht. plus Fan Coil, IFHWH & Secondary Ht. Exchanger) Application: 4-Way Mixing Cast iron high mass boiler and 4 circuits (one low temp. circuit - fully automatic modulating water temp. for floor heating) (two high temp.
® Heat Link ELECT 5.5a HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com StatLink Activating Low Temp. plus Independent High Temp. Circuits ® Application: StatLink controls activating individual zone motors for both primary and secondary circuit ® loops. For the secondary low temp. circuit, StatLink activates the indoor/outdoor control, which ®...
Page 39
® Heat Link ELECT 5.5b HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com StatLink Activating Low Temp. plus Independent High Temp. Circuits ®...
® Heat Link TECH 5.6 HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com Multiple Low Temperature Circuits Application: 4-Way Mixing Cast iron high mass boiler c/w multiple low temperature circuits (Commercial application for multiple low temp. circuits - fully automatic modulating water temp. for floor heating)
® Heat Link ELECT 5.6 HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com Indoor/Outdoor Controller c/w Multiple Standard Room Thermostats Application: Automatic indoor/outdoor controller activating a 4-way mixing valve motor, boiler, plus primary (P-2) and system (P-1) pumps. Secondary zone control provided by individual room/zone thermostats.
Page 42
® Heat Link User Notes HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com...
Page 43
® Heat Link User Notes HeatLink Mixing Valve Reset Control Stk# 31360 ® www.heatlinkgroup.com...
30% Enable Advanced Return To increase or decrease the OUTDR DSGN DIFF VIEW ADJUST HeatLink Mixing Valve Reset Control Stk# 31360 Floating Action ® building temperature: Boiler Sensor BOIL TARGET ˚ F ˚ C Press the Item , , buttons...