INSTALLATION INSTRUCTION
SELF-DIAGNOSTICS/SELF-TESTING OPTION
SAVE THESE INSTRUCTIONS
1. When AC power is supplied to xture, the unit will automatically initiate a self-test and self-diagnostic
test as follows:
(1) Veries battery disconnection, charger board failure, lamps failure and transformer failure at every 5 seconds.
(2) One-minute self-testing every month.
(3) 30 minutes self-testing on the 6th month of the year after installation.
(4) 90 minutes self-testing on the 12th month of the year after installation.
2. Dual color LED lamp indicator shows the following status:
(1) Green color: ON/ Ready
Blinking: Testing
(2) Red color (Service Alert)
(3) Service Alert LED Code (Red color LED lamp indicator)
One blink ON/pause
Two blinks ON/pause
Three blinks ON/pause (4 seconds)
Four blinks ON/pause
Five blinks ON/pause
Six blinks ON/pause
Seven blinks ON/pause (4 seconds
CAUTION:
After solving the fault of emergency equipment, please press test button for 2 seconds without releasing to reset.
LED indicator will show green.
3. For manual test, press test button as follows:
Press test button once
Press test button twice
Press test button 3 times
Press test button 4 times
4. Remote Capacity for Self-Test Option (when applicable):
In order to connect remote lamp heads with self-diagnostics/self-testing option, please refer to the instruction on the next page.
(4 seconds)
(4 seconds)
(4 seconds)
(4 seconds)
(4 seconds)
(within 2 seconds)
(within 2 seconds)
(within 2 seconds)
(within 2 seconds)
Battery is not connected
Battery is shorted or battery voltage drops below acceptable level
Charger board circuit fault
Transfer System Failure
Emergency lamp fault
Remote head's emergency lamp fault (if installed)
Exit LED strip fault (for Exit signs only)
1 minute test
5 minutes test
30 minutes test
90 minutes test