ABB Symphony Harmony Series Instruction page 46

Digital input modules
Hide thumbs Also See for Symphony Harmony Series:
Table of Contents

Advertisement

Table 1-4. Specifications
Property
Power requirements
Operating voltage
Over voltage category
(ANSI/ISA S82.01-1994
and IEC 61010-1)
Digital inputs
Voltage (±10%)
Current
Turn-on voltage (min.)
Turn-off voltage (max)
Maximum input current
at minimum turn-on
Off-leakage current
(max)
DC response time
(debounce filter)
Mounting
Environmental
Ambient temperature
(per IEC 68-2-1, 2,14)
Relative humidity
(per IEC 68-2-3)
Atmospheric pressure
Air quality (per ISA
S71.04, Class LA, LB,
LC - level 1)
Insolation
(IEC 61010-1,
IEC 60255-5, IEC 60060)
WBPEEUI240767B0
95 mA at 5 VDC (typical), 115 mA maximum
I for power
I for circuits >150 V, II for circuits <150 V
16 channels
IMDSI13/22
IMDSI14/22
24 VDC
48 VDC
5.5 mA
4.7 mA
19.5 VDC
26.7 VDC
13 VDC
13 VDC
4 mA at
2 mA at
19.5 VDC
26.7 VDC
50 nA (at V
50 nA (at V
in
≤10.5 VDC
≤10.5 VDC)
Occupies one slot in a standard module mounting unit
Temperature rating within the cabinet or enclosure applies. Internal
cabinet rating: 0° to 70° C (32° to 158° F)
5% to 95% up to 55° C (131° F), noncondensing
5% to 45% at 70° C (158° F), noncondensing
Pollution degree: 1
Sea level to 3 km (1.86 miles)
Noncorrosive
Test
Insulation resistance (100/500 VDC)
Dielectric VAC (45 -65 Hz) or VDC
Impulse voltage
Characteristic/Value
IMDSI22
125 VDC
4.5 mA
90.5 VDC
55 VDC
2.4 mA at
90.5 VDC
1 µA (at V
1.6 mA (at V
in
in
≤50.8 VDC)
17 ms (fixed)
Common Mode
100 M
1.4 kV
/1min. or
RMS
1.95 kVDC/1min.
±2.55 kVp
Specifications
120 VAC
6 mA
81 VAC
45 VAC
3.8 mA at
81 VAC
in
≤45 VAC)
Normal
Mode
N/A
N/A
±1 kVp
1 - 5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Symphony imdsi13Symphony imdsi14Symphony imdsi22

Table of Contents