Drain Piping - LG ARNU483TMC2 Installation Manual

Ceiling cassette - 4way air conditioners
Hide thumbs Also See for ARNU483TMC2:
Table of Contents

Advertisement

Installation

Drain Piping

• Drain piping must have down-slope (1/50 to 1/100): be sure not to
provide up-and-down slope to prevent reversal flow.
• During drain piping connection, be careful not to exert extra force
on the drain port on the indoor unit.
• The outside diameter of the drain connection on the indoor unit is
32 mm(1-1/4 inch).
Piping material: Polyvinyl chloride pipe inner diometes
Ø 25 mm(1 inch) and pipe fittings
• Be sure to install heat insulation on the drain piping.
Heat insulation material: Polyethylene foam with thick-
ness more than 8 mm(5/16 inch).
Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Feed water
Drain Pump
Drain pan
CAUTION : The supplied flexible drain
hose should not be curved, neither
screwed. The curved or screwed hose
may cause a leakage of water.
16
Indoor Unit
Flexible drain hose
(accessory)
Main
drain pipe
Drain
port
Glue the joint
Drain hose connection
Use the clip (accessory)
Pipe clamp
Indoor unit
Maintenance
drain port
• Connect the main drain pipe to the exterior
and leave it provisionally until the test comes
to an end.
• Feed water to the flexible drain hose and
check the piping for leakage.
• Be sure to check the drain pump for normal
operating and noise when electrical wiring is
complete.
• When the test is complete, connect the flexi-
ble drain hose to the drain port on the indoor
unit.
Flexible drain hose
Upward
routing
not allowed
1/50~1/100
• TE : 700 mm
MAX
(27-9/16 inch)
• TM/TN/TP : 800 mm
(31-12 inch)
Flexible drain hose
Flexible drain hose
Flexible drain hose
1/50~1/100
• TE : 700 mm
MAX
(27-9/16 inch)
• TM/TN/TP : 800 mm
Flexible drain hose
(31-12 inch)