Swegon REACT Va Instructions For Use Manual page 9

Table of Contents

Advertisement

Replacing the damper motor
Figure 13. Dismantling the damper motor.
1. Disconnect the cable.
2. Disconnect the measuring tubes.
3. Set damper motor to the open position.
4. Loosen the nuts on the spindle clamp (nuts: 8mm).
5. Dismantle 2 screws for the locking strip (screws: TX20).
6. Lift off the damper motor and spindle adapter
(The rectangular design has a round damper spindle and no spindle adapter).
7. Reassemble in the reverse order.
NOTE!
Normal motor
Positioning of the damper blade and locking strip, see figures 14 and 15.
Figure 14. Recess in the damper spindle indicates the position
of the damper.
Figure 15. Damper open. Jumper to the left.
20200928
Swegon reserves the right to alter specifications.
REACT V