Pickup An':! DroE_g�_ Test
l .
Connect re l ay studs l and 2
box so that the current can be contro l l ed over a range of 0. 1 to 2.0 amperes.
Turn the time dia l to the ZERO T I M E D IAL position.
2 .
Increase the current s l ow l y until the seal -in unit picks up .
3 .
4.
Move the time dial away from the ZERO T I M E D IAL position, the sea l -in unit shou l d remain in the
picked up position.
Decrease the current s l ow l y unti l the seal -in unit drops out.
The re l ay shoul d be insta l l ed in a c l ean, dry l ocation, free from dust, and wel l l ighted to facil itate
inspection and testing.
The rel ay shoul d be mounted on a vertica l surface.
Figure 20 shows the semi-fl ush mounting and Figure 21 shows various methods of surface
Figures 20 and 21 .
mounting.
The interna l connection diagrams for the re l ays are shown in Figures 3, 4 and 5 .
connections are shown in Figures 8 and 1 0 .
I N STAL LAT I ON TESTS
The fo l l owing tests are to be performed at the time of insta l l ation:
Time Overcurrcr.t Unit
Set the tap b l ock to the desired tap setting and the time dial to the 0. 5 position.
15
circuit in Figure
gradua l l y appl y current until the contacts just cl ose.
defined as pickup and shoul d be within three percent of tap val ue.
Check the operating time at some mu l tip l e of tap va l ue and the desired time dia l setting.
of tap va l ue may be five times tap rating or the maximum faul t current for which the re l ay must coordinate.
This val ue used is l eft to the discretion of the user.

Hi- Seismic Target and Sea l -in Unit

l.
Make sure that the tap screw is in the desired tap.
2.
Perform pickup and dropout tests as out l ined in the ACCE PTANCE TEST section.

Hi-Seismic Instantaneous Unit

l .
Se l ect the desired range by setting the l ink in the proper position.
Connections Diagram
continuous rating.
Set the instantaneous unit to picK up at the desired current l eve l .
2 .
UNIT in the ACCEPTANCE TE ST section.
(
See the test circuit of Figure 1 8 ) to a d-e source, ammeter and l oa d
TA P
P ICKUP
C U RRENT
0 . 2
0 . 12 - 0. 20
2 . 0
1 . 2
- 2 . 0
I N STAL LAT I O N
)
.
Whenever possibl e al ways se l ect the higher range since it has higher
GEK-45376
See Tab l e 12.
See Tab l e 12.
TABL E 12
DROP-OUT
CURRENT
0 . 05 or more
0 . 5 0 or more
The out l ine and pane l dri l l ings are shown in
12
Typical external
Using the test
This va l ue of current is
This mul tipl e
(
See Figure 1 and the Interna l
See S E TT I N G TH E I N STANTANEOUS
f