Eaton MRLDS-450 Quick Start Manual
Eaton MRLDS-450 Quick Start Manual

Eaton MRLDS-450 Quick Start Manual

Refrigerant gas detector for machinery rooms, cold rooms and freezers

Advertisement

Quick Links

Refrigerant Gas Detector (MRLDS-450)
for Machinery Rooms, Cold Rooms and Freezers
Quick Start Guide
The MRLDS-450 refrigerant gas detector is designed for use in refrigeration
applications and may be used as a stand-alone device, or connected to a facility's
building management system (BMS). It enables compliance with refrigerant
safety codes (ASHRAE 15 and EN378) and features audible and visual alarms to
alert personnel in the event of a refrigerant leak.
1. Safety Instructions
DANGER: The MRLDS-450 is NOT certified or approved for operation in
oxygen-enriched atmospheres. Failure to comply may result in severe injury or
death.
WARNING: Use this product ONLY for the purposes and under the conditions
listed in the user manual. Failure to comply may result in injury and/or damage
to the product. The MRLDS-450 has not been designed to be intrinsically safe
for use in areas classified as being hazardous locations. For your safety, DO NOT use in
hazardous locations. Consult a qualified professional before connecting the MRLDS-450 to devices not mentioned in
this manual. Failure to comply may result in injury and/or damage to the product.
WARNING: The gas diffusion path can become occluded (moisture, dust, debris, frozen condensation) over time, resulting in
reduced or complete lack of gas detection and alarming function. Routine visual inspection of the gas detector and bump
testing are recommended to ensure proper gas detection and alarm function. For information on calibrating the sensor, refer to
the Care and Maintenance section of the MRLDS-450 User Manual P/N 026-1316.
CAUTION: Except for the maintenance detailed in this manual, this product should ONLY be opened and/or
serviced by authorized personnel. Failure to comply may void the warranty.
CODE COMPLIANCE: Comply with all local and national laws, rules and regulations associated with this equipment. Operators
should be aware of the regulations and standards in their industry/locality for the operation of the MRLDS-450.
TECHNICIAN USE ONLY: The MRLDS-450 must be installed by a suitably qualified technician who will install this unit in
accordance with these instructions and the standards in their particular industry/locality. This document is only intended as a
guide and the manufacturer bears no responsibility for the installation or operation of this unit. Failure to install and operate the
unit in accordance with these instructions and with industry guidelines may cause serious injury or death and the manufacturer
will not be held responsible in this regard.
Document Part # 026-4417 Rev 2
©2020 Emerson Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emerson.com for the latest technical documentation and updates.
Figure 1 - Refrigerant Gas Detector
Page 1 of 9

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MRLDS-450 and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton MRLDS-450

  • Page 1 MRLDS-450. TECHNICIAN USE ONLY: The MRLDS-450 must be installed by a suitably qualified technician who will install this unit in accordance with these instructions and the standards in their particular industry/locality. This document is only intended as a guide and the manufacturer bears no responsibility for the installation or operation of this unit.
  • Page 2: Component Overview

    2. Component Overview Figure 2 - Component Locations Component Description M16 Cable Glands (x6) Rubber Gasket Internal Alarm Buzzer Power Connections (x2) Digital Connection (Modbus) Analog Connection Tactile Switch #1 Ribbon Cable Connection (To Sensor) Tactile Switch #2 Relay 3 Connection (FAULT) Relay 2 Connection (HIGH) Relay 1 Connection (LOW) Magnetic (Mag) Switch #1...
  • Page 3: Product Specifications

    STEP 1: Mount Gas Detector & Remove Lid CAUTION: DO NOT allow the lid/sensor to hang from the ribbon cable. Failure to comply may result in damage to the product. 1. Mount the MRLDS-450 according to the product dimensions, maximum wiring lengths, and following considerations: •...
  • Page 4 • Application: the specifics of the application (possible leaks, air movement/draft, etc.) when selecting a location. • Accessibility: the degree of accessibility required for maintenance purposes when selecting a location. • Target Gas: the specific gravity of the target gas when selecting the height of the instrument. 2.
  • Page 5 4. Using a 5/32” (4 mm) hex key/allen wrench, tighten the lid screws in an X tightening pattern: Figure 6 - Tightening Pattern 5. MRLDS-450 Network Setup for Site Supervisor and E2 For Modbus end-of-line termination, use 150 ohm resistor or termination block P/N 537-2711. Do not use MRLDS 120 Ω...
  • Page 6 5a. Site Supervisor Device and COMM Setup Figure 7 - Site Supervisor Setup Document Part # 026-4417 Rev 2 Page 6 of 9 ©2020 Emerson Retail Solutions, Inc. This document may be photocopied for personal use. Visit our website at http://www.emerson.com for the latest technical documentation and updates.
  • Page 7 5b. E2 Device and COMM Setup *For MODBUS setup of E2, please see the Quick Setup Guide P/N 026-4419 Figure 8 - E2 Setup Document Part # 026-4417 Rev 2 Page 7 of 9 ©2020 Emerson Retail Solutions, Inc. This document may be photocopied for personal use. Visit our website at http://www.emerson.com for the latest technical documentation and updates.
  • Page 8: Operation Overview

    6. Connect MRLDS-450 to MRLDS-400 Series App (User Discretion) The MRLDS-450 uses a smartphone application to allow users to interface with the gas detector. IMPORTANT: Default alias, passkey, and unlock code can be changed via the MRLDS-400 Series App’s configuration menu.
  • Page 9: Part Number And Ordering Information

    R513A 0-1,000ppm 809-1066 R422D 0-1,000ppm 809-1166 R422D 0-1,000ppm 809-1068 R449A 0-1,000ppm 809-1168 R449A 0-1,000ppm MRLDS-450 Accessories 809-1190 Calibration Adapter Kit 809-1191 Horn + strobe 24VDC; blue lens 809-1192 Horn + strobe 24VDC; amber lens 809-1193 Horn + strobe 24VDC; red lens 809-1194 Horn + strobe;...