Carrier WeatherMaster 50HCQ04-12 Service And Maintenance Instructions page 57

Single package rooftop heat pump/electric heat with puron (r-410a) refrigerant
Table of Contents

Advertisement

Table AH — 50HCQD12 2-Stage Cooling with Single Speed Indoor Fan Motor
VOLTAGE RANGE
V-Ph-Hz
MIN
MAX
208-3-60
187
253
230-3-60
187
253
460-3-60
414
506
575-3-60
518
633
Table AI — 50HCQD12 2-Stage Cooling with 2-Speed Indoor Fan Motor
VOLTAGE RANGE
V-Ph-Hz
MIN
208-3-60
187
230-3-60
187
460-3-60
414
575-3-60
518
APPENDIX D — ELECTRICAL INFORMATION (cont)
COMP
(Cir 1)
RLA
LRA
15.6
110
15.6
110
7.7
52
5.8
39
COMP 1
MAX
RLA
LRA
253
15.6
110
253
15.6
110
506
7.7
52
633
5.8
39
COMP
OFM
(Cir 2)
(ea)
RLA
LRA
WATTS
15.9
110
280
15.9
110
280
7.7
52
280
5.7
39
280
COMP 2
OFM (ea)
RLA
LRA
WATTS
280
15.9
110
280
280
280
15.9
110
280
280
280
7.7
52
280
280
280
5.7
39
280
280
57
IFM
FLA
TYPE
EFF at Full Load
STD
80%
1.5
MED
80%
HIGH
89.5%
STD
80%
1.5
MED
80%
HIGH
89.5%
STD
80%
0.8
MED
80%
HIGH
89.5%
STD
80%
0.7
MED
80%
HIGH
89.5%
IFM
FLA
TYPE
EFF at Full Load
1.5
STD
77%
1.5
MED
85%
1.5
HIGH
90%
1.5
STD
77%
1.5
MED
85%
1.5
HIGH
90%
0.8
STD
77%
0.8
MED
85%
0.8
HIGH
90%
0.7
STD
80%
0.7
MED
84%
0.7
HIGH
94%
FLA
6.8
8.4
17.0
6.7
8.3
15.0
3.4
4.2
7.6
2.0
2.8
6.1
FLA
7.1
8.6
20.4
6.8
7.8
20.4
3.8
3.8
10.2
3.5
4.5
9.0

Advertisement

Table of Contents
loading

Table of Contents