Page 1
MACON MACON MULTI-FUNCTION WATER TO WATER Macon Cooling and Heating Energy-efficient Equipment Co., Ltd Macon Cooling and Heating Energy-efficient Equipment Co., Ltd...
Multi-Function Water To Water Heat Pump MACON I. Introduction 1. Notice 1. Notice 1.1 This manual includes all necessary information of proper installation, debugging, operation and maintenance. 1.2 In order to use this product better and safer, please read this instruction carefully before install and operate it.
Multi-Function Water To Water Heat Pump MACON 4. Product work principle(The dotted line in the box only heat recovery models.) 4. Product work principle(The dotted line in the box only heat recovery models.) 4-way vavle 4-way vavle Exchanger Exchanger Tank...
MACON Multi-Function Water To Water Heat Pump 3. Product appearance and installation dimension 1. Installation dimensions of integrated type unit MACON Dimensions MACON Dimensions...
MACON Multi-Function Water To Water Heat Pump III. Installation 1. Unit installation position Unit installation position Please keep enough space around the unit for repair. Correct and wrong means as below: Wrong Correct 1.2 The unit can be installed inside floor or any other inside convenient place and reliable load -bearing.
Multi-Function Water To Water Heat Pump MACON 4.Installation of terminal equipment 4.1.Indoor terminal equipment installation (such as: fan coil, radiator heater or floor heating), the equipment should be installed in accordance with relevant regulatory requirements. 4.2.In accordance with the requirements of engineering design drawings, installation and construction.
Multi-Function Water To Water Heat Pump MACON 5.14.The unit water inlet and outlet must install a thermometer, water pressure gage, to facilitate inspection when operate. Note: 1) Tubing pipeline should be separate test pressure, must not test with hot water unit or tanks.
Multi-Function Water To Water Heat Pump MACON 7.4 Wiring construction must be installed by professional technicians refer to circuit diagram. 7.5 Power lines and signal line layout should be neat, rational, strong and weak lines separate and can not interfere with each other, while not contacted with the connecting pipe and the valve body.
Page 12
Multi-Function Water To Water Heat Pump MACON 8.3 Caution of Ground The internal motor protector does not protect the compressor against all possible conditions. Please be sure that the system utilizes the ground connection when installed in the field. 8.4 Warning: To avoid fire, electric shock and other accidents, keep in mind about these tips: 8.4.1 Only use power supply voltage indicated on the label, if you do not know the family of voltage,...
Multi-Function Water To Water Heat Pump MACON 9.Trial run 9.1.Check the hot water side, air-conditioning side and solar side of the water system piping and all accessories are installed correctly, heat pumps, water tanks, terminal equipment piping connections are correct. The fill water supply of hot water side, air-conditioning side and solar side are normal, the replenishment port whether installed pressure relief valve, one-way valve, filter and other accessories.
Multi-Function Water To Water Heat Pump MACON 10. Installation schemes Installation schemes 1. Installation sketch for the unit with heat recovery. 1. Installation sketch for the unit with heat recovery. Floor heating Air condition closed expansion tank closed expansion tank...
Page 15
Multi-Function Water To Water Heat Pump MACON 2.Electrical connection diagram 2.1.S trong current connection diagram Solar cycle pump 3-Way valve Hot water cycle pump Air condition cycle pump (Power supply input Ground source cycle pump 380V/3ph/50hz) (220V/1ph/50hz power output) 2.2.control signal...
ON/OFF Press this button to enter the main menu interface Press this button to return to the previous BACK Welcome to use MACON screen Modify theparameter values or turn to Energy center next page Modification parameter values or turn to...
Page 17
MACON Multi-Function Water To Water Heat Pump 1.3.Corresponds to enter the parameters setting mode Under the main interface,press: enter into parameter setting interface,choose "Main menu ", press button,choose "Mode select",press into the mode setting,press to view and choose,press again to go into the modify parameter interface,the corresponding parameter value is...
Page 18
MACON Multi-Function Water To Water Heat Pump 1.4.1.Host type: air to water on/off A.C. Inlet temp. Compressor 1 A.C. Outlet temp. Compressor 2 on/off Hot water temp. 4way-valve on/off Rec. Inlet temp. Fan motor on/off on/off Sys1. Evap. Temp. A.C. Water pump Sys2.
Page 19
MACON Multi-Function Water To Water Heat Pump 1.5.System parameter setting: On the main interface,press the button enter into page2(picture1),press for 5 second until hear the beep ,one more parameter parameter)appear, press to view the parameter, choose Parameter and press to enter the paremters setting interface,press...
Page 20
MACON Multi-Function Water To Water Heat Pump 1.6.The maintenance time inquires ; In the interface ,press to enter parameter setting interface,choose "Maintenance'' and press to enter Maintenance time inquires, press to turn a choice, and press returns the last menu.
MACON Multi-Function Water To Water Heat Pump 2. Controller parameter Table Setting data explanation or Parameter Display code1 Display code2 Default Remarks working state setting range Main menu A.C. mode Cooling/heating/off Cooling/heating/off Heating Adjustable Cooling /Heating /Off Adjustable Cooling inlet temp.
Page 22
Multi-Function Water To Water Heat Pump MACON Parameter Setting data explanation or Display code1 Display code2 Default Remarks working state setting range Unit status A.C. Inlet temp. air condition water inlet tempture measured value A.C. Outlet temp. air condition water outlet tempture measured value Hot water temp.
Page 23
Multi-Function Water To Water Heat Pump MACON Setting data explanation or Parameter Display code1 Display code2 Default Remarks working state setting range Parameter High-temperature sterilization auxiliary Adjustable 3.3 anti-virust heating start temperature difference setting Start heating the compressor oil Adjustable 3.4 Comp.
Multi-Function Water To Water Heat Pump MACON V Maintenance and repair 1. Malfunction Indicating Table. Determine and solve the malfuction by malfuction code as below: Motherboard Display Malfunction and Reason Solution Mode travel light Protection Name Standby normal start cooling/heating inlet water 1.Check whether the connection of sensor is poor.