Broyce Control ELRV-30 Quick Start Manual

Broyce Control ELRV-30 Quick Start Manual

True rms earth leakage relay variable - type a

Advertisement

Quick Links

Type: ELRV-30
True RMS Earth Leakage Relay (Variable) - Type A
q
70mm DIN rail housing
q
Designed to monitor and detect true RMS, earth fault currents (up to 30A) in conjunction with a separate toroid
q
Fast response time of <25mS
q
Digital LED Display shows measured leakage current, various user settings and diagnostics
q
Microprocessor controlled with internal monitoring (self-checking)
q
Sensitivity (I∆n) and time delay (∆t) adjustable using simple 2-button operation
q
"Display" push button allows user to view settings without needing to open the tamperproof cover. The "last recorded" peak
trip current can also be recalled using the same push button
q
Single button operation for "Test / Reset" and connection facility for remote "Test" and "Reset" push buttons
q
Connection for remote lamp facility warning user prior to a trip condition (level adjustable by user)
q
Toroid open and short circuit detection (unit forced to trip during open circuit condition)
q
2 x SPDT relay output 8A. LED indication of user settings / fault condition after unit has tripped
• FUNCTION DIAGRAM
Trip level (I n)
Reset level
Standard
output
Positive safety
output
td
INSTALLATION
BEFORE INSTALLATION, ISOLATE THE SUPPLY.
Connect the unit as shown in the diagram below (N.B. certain features may not be required and
therefore do not need to be connected).
Operational and setting information can be found on the reverse of this data sheet.
This unit should be installed in conjunction with the latest wiring regulations and practices (IEE, etc)
• CONNECTION DIAGRAM
A1 (+ve)
A2 (-ve)
Note: The voltage
across the fault level
output MUST NOT
exceed 240V~ (For
400V~ units used in
1
3
5
3-Phase installations,
connect the load between
terminal 2 and neutral)
Fault level output*
2
4
6
(i.e. lamp)
Both relays are shown
in the de-energised state
(i.e. where power is not
present on terminals 1 and 3)
positive safety
output
* Only available on AC supply models
• MOUNTING DETAILS
Telephone: +44 (0) 1902 773746 Facsimile: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: http://www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user's own risk.
1
to fault currents that are 5 x greater than the set trip current
supply
interrupted
fault
current
failure of connection
∆t
td
"reset"
"test"
(combined test/reset button pressed)
Installation work must be carried
out by qualified personnel.
L1
L2
L3
N
E
50m* max.
toroid
7
9 11 13
The Earth MUST NOT pass through
8 10 12
14
the toroid.
For single phase applications, only the live
and neutral need to be passed through the
toroid.
*Cabling:
For distances >1m, use twisted pair cable between
standard
the unit and toroid. Always ensure cables to toroid
output
and remote test / reset switches ARE KEPT AWAY
from mains and data cables in the same installation.
85
45
Insert screwdriver
to release clip
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England
1
• TECHNICAL SPECIFICATION
Supply voltage Un (1, 3):
Supply frequency:
Isolation:
to toroid
Rated impulse
withstand voltage:
(1.2 / 50µS) IEC 60664
Power consumption (max.): 6VA (AC supplies), 5W (DC supply)
Monitored leakage current: 2mA to 30A (50/60/400Hz)(through external toroid with
Sensitivity I∆n:
Trip level:
Hysteresis:
Accuracy:
Time delay ∆t:
Measured current:
Display Resolution:
Reset time:
Power on delays:
(from application of supply
to terminals 1 and 3)
Memory:
Ambient temp:
Relative humidity:
Output :
Output rating:
Electrical life:
Dielectric voltage:
Rated impluse
E
withstand voltage:
Remote "test" / "reset"
(5, 7, 9)
Contact closure time:
Fault level output (1, 2):
Hysteresis:
Load (resistive):
Housing:
Weight:
Mounting option:
Terminal conductor size:
Approvals:
For other supply voltages, alternative trip levels or time delays, please consult the sales office.
Note:
( ) Numbers in brackets shown above refer to terminal numbers on the relay housing.
Dims:
to DIN 43880
W. 70mm
"inst." time delay setting / fault current <30A
12 – 60V DC (85 – 115% of U)
24, 115, 230, 400V AC (85 – 115% of Un)
Galvanic isolation between the supply and the toroid and
remote test / reset connections on AC supply versions.
50/60/400Hz (AC supplies)
Over voltage cat. III
800V (24V AC supply
2.5kV (115V AC supply)
4kV (230V, 400V AC supplies)
1000:1 ratio and connected to terminals 11 and 13)
6, 10, 30, 50, 75, 100, 300, 500, 750mA
1, 3, 5, 7.5, 10, 15, 20, 25, 30A (user selectable)
75% of I∆n (nominal)
8% of I∆n or 2mA, whichever greater
±15% (valid range 10 .... 110% of I∆n or 2mA,
whichever greater)
inst., 50, 250, 500mS, 1, 2.5, 5, 10 sec. (user selectable)
Note: For I∆n settings of 30mA or less, the time delay is fixed
to inst. (instantaneous, <25mS) and is not adjustable.
Displayed on auto ranging 2 digit 7-segment red LED display
100uA min.
<200mS (from supply interruption)
Self test duration: <5 secs.
Delay before P.S.O. relay energises "td":
will energise during self test period assuming no fault present)
storage of the leakage fault and reset with "test / reset" button
-5 to +60°C
-5 to +40°C (in accordance with IEC 755)
+95%
2 x SPDT relay (4, 6, 8 / 10, 12, 14)
AC1
250V 8A (2000VA)
AC15
250V 2.5A
DC1
25V 8A (200W)
≥ 150,000 ops at rated load
2kV AC (rms) IEC 60947-1
4kV (1.2 / 50µS) IEC 60664
Requires two N.O. contacts. (i.e. push buttons)
>100mS
50% of I∆n (factory set)
User adjustable from 10 - 65% in 5% increments
8% of I∆n or 2mA, whichever greater
40mA max. @ 240V
Note: A remote lamp can only be connected when terminals 1
and 3 are being supplied with an AC supply
Grey flame retardant Lexan UL94 VO
≈ 250g (AC supplies), ≈ 170g (DC supply)
On to 35mm symmetric DIN rail to BS5584:1978
(EN50 002, DIN 46277-3)
≤ 2.5mm
stranded. ≤ 4mm
2
Conforms to: IEC 755. IEC 61543 (EMC)
Radiated Immunity: IEC 61000-4-3: 1.89GHz @ 30V/m
and
pending. CE and
Options
Accessories – Toroids
Toroid Type:
Internal diameter:
35mm ∅
BZCT035
BZCT070
70mm ∅
BZCT120
120mm ∅
BZCT210
210mm ∅
Terminal Protection to IP20
Please state Supply
voltage when ordering.
600mS
(Note: relay
2
solid
Compliant.
I∆n (min.) A
0.03
0.03
0.1
0.3
ELRV30-2-A RMS
012366 Page 1 of 2

Advertisement

loading

Summary of Contents for Broyce Control ELRV-30

  • Page 1 ( ) Numbers in brackets shown above refer to terminal numbers on the relay housing. ELRV30-2-A RMS Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England 012366 Page 1 of 2 Telephone: +44 (0) 1902 773746 Facsimile: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: http://www.broycecontrol.com...
  • Page 2 Ensure the supply to the unit is present on terminals 1 and 3 and is within the operational limits specified. For DC units, ensure the polarity of the supply is correct. ELRV30-2-A RMS Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England 012366 Page 2 of 2 Telephone: +44 (0) 1902 773746 Facsimile: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: http://www.broycecontrol.com...