Instruction Manual — Series 200 Remote Meter Panels 500 PPD (10 kg/h) Maximum Capacity 100 PPD (2 kg/h) Maximum 200 PPD (4 kg/h) Maximum (250 PPD [5 kg/h] Chlorine only) 500 PPD (10 kg/h) Maximum - 1 - 100.6015.10...
Page 2
De Nora Water Technologies, Inc. cannot be responsible for the overall system design of which our equipment may be an integral part of or any unauthorized modifications to the equipment made by any party other that De Nora Water Technologies, Inc.
INTRODUCTION General The ADVANCE remote meter panels are expertly engineered and carefully tested to assure years of ® satisfactory operation. The meter panels are constructed of the finest materials available for gas service. Proper installation and care will ensure the best operation. Read instructions carefully and retain for future reference.
OPERATION General The remote meter panel is designed to complement the Capital Controls’ Series 200 vacuum regulators. When multiple chlorine gas feed points from the same vacuum regulator are required, a remote meter panel is utilized. Each remote meter panel is manually set, via the rate valve, to meter the proper amount of chlorine gas to the feed point.
START-UP Follow the instructions provided in the vacuum regulator instruction manual 100.6010 for complete system start-up procedures. After the system has been tested for leaks and is operating, adjust the rate valve to the desired gas flow rate. The flow rates are in PPD (pounds per day) of chlorine. If feeding sulfur dioxide, the actual flow rate is 0.95 of the scale value.
SERVICE Preventative maintenance kits for each of the assemblies are available from the factory. Each kit contains all the parts and detailed instructions that are required for complete maintenance. All o-rings and gaskets that have been disturbed during the disassembly must be replaced during reassembly in order to insure safe, trouble free operation.
TROUBLESHOOTING CHART Since the operating performance of the remote meter panel can be effected by the vacuum regulator and ejector, also refer to the Troubleshooting Chart in bulletin 100.6005, 122.6006, 122.6010, or 122.6015. TROUBLE PROBABLE CAUSE CORRECTIVE ACTION 1. The required gas feed rate is a.