AVR BL4-U is connected with the main stator windings and the exciter field windings to provide closed loop control of the output voltage. In addition to being powered from the main stator, AVR BL4-U also derives a sample voltage from the output windings for voltage control purposes. In response to this sample voltage, AVR BL4-U...
- An under frequency trimmer - A frequency selection DIP switches - Electric protection with fuse. The electronic is sealed with resin (it is a perfect protection against vibrations and humidity). SINCRO® is a brand of Soga Energy Team ITALY | sogaenergyteam.com | info.sincro@sogaenergyteam.com...
If no hand potentiometer is required terminals Ext and Pot will be fitted with a shorting link. STABILITY ADJUSTMENT The AVR BL4-U includes stability or damping circuit to provide good steady state and transient performance of the alternator. The correct setting can be found by running the alternator at no load and slowly turning the stability ST clockwise until the alternator voltage starts to become unstable.
Page 6
UNDER FREQUENCY KNEE ADJUSTMENT AVR BL4-U incorporates an underspeed protection circuit (UF) which gives a volts/Hz characteristic when the alternator speed falls below a presettable threshold known as the "knee" point. The UF knee adjustment is preset at factory at the 47Hz on a 50Hz system or 57Hz on a 60Hz system.
3Ph 400Vac. The sensing will be accomplished using the line voltage at input contacts named 400, 230, 115 and 0. AVR BL4-U Connection diagram: 3Ph - sensing 400 V AVR BL4-U Connection diagram: 1Ph - sensing 230V SINCRO® is a brand of Soga Energy Team ITALY | sogaenergyteam.com | info.sincro@sogaenergyteam.com...
Page 8
The power supply is 230V. For the machine 3Ph 400V connect the line U and the neutral N to the terminals AuxL and AuxN. AVR BL4-U Connection diagrams without auxiliary winding: 3Ph - sensing 400 V SINCRO® is a brand of Soga Energy Team ITALY | sogaenergyteam.com | info.sincro@sogaenergyteam.com...
6. Carefully turn volts trimmer “V” (or external pot, if fitted) clockwise until rated voltage is reached 7. If instability is present at rated voltage, refer to stability adjustment, and then re-adjust voltage if necessary SINCRO® is a brand of Soga Energy Team ITALY | sogaenergyteam.com | info.sincro@sogaenergyteam.com...
- UF protection adjusted for a very the nominal frequency FUSE BLOWS low frequency (so the fuse burn during CONTINUOUSLY the turn-off procedure) Replace the AVR - Faulty AVR SINCRO® is a brand of Soga Energy Team ITALY | sogaenergyteam.com | info.sincro@sogaenergyteam.com...