FläktGroup ETCE Instructions For Installation, Operation And Maintenance

Fire damper

Advertisement

Quick Links

Fire Damper
ETCE and ETCS
INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE

Advertisement

loading

Summary of Contents for FläktGroup ETCE

  • Page 1 Fire Damper ETCE and ETCS INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE...
  • Page 3: Installation

    Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance Installation Fire dampers ETCE and ETCS (with stainless steel casing) must be installed according to this installation manual, see pages 3-8. Operation and function testing According to CE marking, a fire damper must always be equipped with a tripping mechanism based on temperature.
  • Page 4 Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance Installation into building elements with fire classification EI 60 (Ø100 - Ø1000) Figure 1 Figure 2 t (mm) t (mm) EI 60 S ≥ 100 EI 60 S ≥...
  • Page 5 Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance Installation of fire damper into rigid Installation of fire damper into flexible building elements (walls and building elements (gypsum board walls intermediate floors) with fire or similar) with fire classification EI 60 classification EI 60 (Fig.
  • Page 6 Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance Installation into building elements with fire classification EI 90 / EI 120 (walls Ø100 - Ø800 and intermediate floors Ø100 - Ø1000) t (mm) t (mm) Figure 5 Figure 6 ≥...
  • Page 7 Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance Installation of fire damper into rigid Installation of fire damper into flexible building elements (walls and inter- building elements (gypsum board walls mediate floors) with fire classification or similar) with fire classification EI 90 EI 90 / EI 120 (Fig.
  • Page 8 Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance 7. Check the functioning of the fire damper and proper Access panel should be placed next to the fire damper movement of the blade. Clean the damper, if necessary.
  • Page 9 Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance Electrical wiring for motorized fire damper Only a trained electrician is allowed to perform the elec- trical wiring according to separate drawings and wiring diagrams. Wiring diagram for fire damper actuator is shown below.
  • Page 10 Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance How to change microswitch to indicate open position 1. Release the mechanism with the test button (1) – close the fire damper. Figure 10. 2. Remove the cover (2) and the two screws (3). Figure 11.
  • Page 11 Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance Replacing fuse part ETFF-99-1 NOTE! Safety gloves should be used when replacing the fuse part. 1. Release the mechanism with the test button (1) – close the fire damper. Figure 14.
  • Page 12 WWW.FLAKTGROUP.COM ETCE, ETCS 9503 FläktGroup is the European market leader for smart and energy efficient Indoor Air and Critical Air solutions to support every application area. We offer our customers innovative technologies, high quality and outstanding performance supported by more than a century of accumulated industry experience.