Heating & Air Conditioning INSTALLATION INSTRUCTIONS HIGH EFFICIENCY WALL-MOUNT AIR HANDLERS 1.5-2Tons FEATURING R-410A OR R22 REFRIGERANT RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION WARNING These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjust- ment and operation of this unit.
This document is customer property and is to remain with this unit. These instructions do not cover all the different variations systems nor does it provide for every possible contingency to be met in connection with installtion. All phases of this installation must comply with NATIONAL STATE AND LOCAL CODES.
Page 4
WARNING The unit must be permanently grounded. Failure to do so can result in electrical shock causing personal injury or death. WARNING PROPOSITION 65: This appliance contains fiberglass insulation. Respirable particles of fiberglass are known to State of California to cause cancer. All manufacturer products meet current federal OSHA Guidelines for safety.
Page 5
WARNING The first 36 inches of supply air plenum and ductwork must be constructed of sheet metal as required by NFPA 90B. The supply air plenum or duct must have a solid sheet metal bottom directly under the unit with no openings, registers or flexible air ducts located in it.
2.0 GENERAL 2.1 UNIT DIMENSIONS Liquid line comection Low voltage copper (sweat) connection Vapor line comection copper (sweat) Breaker switch (for electric heater High voltage connection only) 1-3/8’’ dia knock outs Front return shown. Units may also be installed as bottom return.
3.0 AIR HANDLER MOUNTING OPTIONS The air handler comes standard with two different options for mounting, wall mount or frame mount. Both mounting options require the unit to be level from side to side and from front to back in order to allow condensate to properly drain from the unit.
FIGURE 6 FRAME MOUNT WALL STRUCTURE SUPPORTING 2"X4" STRUCTURE WOOD SCREWS STUD ATTACHMANT HOLES SUPPORTING 2"X4" STRUCTURE Fig.3 FRAME MOUNT 3.3 ACCESSORIES-KITS-PARTS INSTALL FRONT COIL PANEL KIT COMES WITH THUMB SCREWS AND INSERT NUTS REMOVE BOTTOM COIL PANEL OFF PLATE Fig.4 DIFFERENT AIR SUPPLY •...
Page 9
KIT COMES WITH THUMB SCREWS AND INSERT NUTS LOUVERED CABINET GRILL Fig.5 GRILL INSTALLATION • Louvered Cabinet Grill is used as decorative grill which covers the return air opening of the front return air handler. ELECTRIC HEATER KITS SUPPLY AIR Fig.6 HEATER ELEMENTS INSTALLATION...
3.4 INSTALLATION IN AN UNCONDITIONED SPACE IMPORTANT: There are two pairs of coil rails in the air handler for default and counter flow application. If the air handler is installed in an unconditioned space, the two unused coil rails should be removed to minimize air handler surface sweating. The coil rails can be easily removed by taking off the 6 mounting screws from both sides of the cabinet.
4.2 CONTROL WIRING IMPORTANT: Class 2 low voltage control wiring should not be run in conduit with main power wiring and must be separated from power wiring, unless class 1 wire of proper voltage rating is used. • Low voltage control wiring should be 18 Awg. color-coded. For lengths longer than 100 ft., 16 Awg.
4.4 ELECTRICAL DATA NOMINAL CIRCUIT MINMUM CIRCUIT MAXIMUM CIRCUIT RATED VOLTAGE HERTZ SPEEDS COOLING AMPS. AMPACITY PROTECTOR 208/230 1075 0.68 15(A) 208/230 1075 0.95 15(A) COOLING 0.68 208/230 1075 15(A) COOLING 0.95 208/230 1075 15(A) HEATING 5.0 AIRFLOW PERFORMANCE Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size external static applied to unit allows opera- tion within the minimum and maximum limits shown in table below for both cooling and electric heat operation.
The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this reason, the contractor should use only industry-recognized procedures. Heat pump systems require a specified airflow. Each ton of cooling requires between 350 and 450 cubic feet of air per minute (CFM), or 400 CFM nominally.
7.0 REFRIGERANT CONNECTIONS Keep the coil connections sealed until refrigerant connections are made. See the Installation Instructions for the outdoor unit for details on line sizing, tubing installa- tion, and charging information. Coil is shipped with “No charge”. Evacuate the system before charging with refriger- ant.
9.0 FILTER INSTALLATION DIMENSIONS DIMENSIONAL DATA Return length FILTER SIZE Return width MODEL "W" IN [mm] "D" IN [mm] "H" IN [mm] "B" IN IN [mm] "A" IN 18/24 16Χ20[406Χ508] 20.8[528] 16.8[426] 1[25.4] 14.5[368] 18.5[470] AIR FILTER REMOVAL • 1.Remove bolts manually, remove air filter recover, see in Fig 6; 2.
10.0 WIRING DIAGRAM 1. To avoid the electrical shock, please connect the air conditioner with the ground lug. The main power plug in the air conditioner has been joined with the ground wiring, please don't change it freely. 2. The power socket is used as the air conditioner specially. 3.
Page 17
SEE NOTE 6 HEATER KIT PLUG SEE NOTE 5 PLUG PLATE SEE NOTE 4 POWER SEE NOTE 3 SEE NOTE 1 NOTES: 1: For the Air handler without installing Electric Heat; connect the supply power to L1 and 2: For the Air handler with Electric Heat, connect the supply power to circuit breaker. If you order the Heat Kit without circuit breaker, connect the power supply to the terminal block provided on the heater.
Page 18
Fig.10: Indoor Unit Wiring Diagram for Electric Heat. E L E C T R I C W I R I N G G A U G E Wiring gauge for A/C systems Model(Btu/h) 18000/24000 Phase Single Power frequency/Votage 208/230V, 60Hz Input Current Fuse Indoor unit (A) Line Quantity...
Page 19
Wiring gauge for H/P systems Model(Btu/h) 18000/24000 Phase Single Power frequency/Votage 208/230V, 60Hz Input Current Fuse Indoor unit (A) Line Quantity Indoor Unit Power Line Line Diameter(AWG) Line Quantity Outdoor Unit Power Lines Line Line Diameter(AWG) Gauge Line Quantity Outdoor -Indoor Singal Line Line Diameter(AWG) Line Quantity...